| Plan Review Stops For Permit 09060183 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-22 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-21 |
Time |
20:53 |
Sent To |
|
|
| Notes |
| 2009-07-22 09:49:53 | PASSED W/REDLINE; PLYWOOD TO BE FRT @ ENGINEER'S | | | REQUEST FBC601.3 | | | SPOKE WITH ARCHITECT AND STRUCTURAL ENGINEER | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-06-23 |
Time |
10:28 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-06-23 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2009-06-23 10:51:41 | BUILDING PLAN REVIEW | | | PERMIT: 09060183 | | | ADD: 222 LAKEVIEW 1ST, 2ND & 3RD FL GARAGE ELEVATOR | | | LOBBIES | | | CONT: G3 CONSTRUCTION | | | TEL: (561) 445-3769 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | | | | SHEET A1.4 INDICATES A NEW MASONRY WALL WITH NO | | | REINFORCEMENT INFORMATION AND OR INFORMATION ON THE NEW | | | TILE VENEER ON WALLS (A1.3 NOTE# 3). PLEASE PROVIDE BY | | | FIRST INSPECTION: | | | | | | 1) THE NEW BLOCK WALL PLEASE INDICATE COMPLIANCE WITH | | | 2103.1 JOINT REINFORCEMENT. JOINT REINFORCEMENT SHALL | | | COMPLY WITH ASTM A 951. THE MAXIMUM SPACING OF | | | CROSSWIRES IN LADDER-TYPE JOINT REINFORCEMENT AND POINT | | | OF CONNECTION OF CROSS WIRES TO LONGITUDINAL WIRES OF | | | TRUSS-TYPE REINFORCEMENT SHALL BE 16 INCHES (400 MM). | | | | | | 2) SHEET A1.4 ALSO NEEDS TO COMPLY WITH INSTALATION OF | | | WALL TIES TYING THE NEW WALL TO EXISTING BUILDING | | | STRUCUTRAL MEMBERS: 2104.1.3 INSTALLATION OF WALL TIES. | | | THE ENDS OF WALL TIES SHALL BE EMBEDDED IN MORTAR | | | JOINTS. WALL TIE ENDS SHALL ENGAGE OUTER FACE SHELLS OF | | | HOLLOW UNITS BY AT LEAST 1/2 INCH (12.7 MM). WIRE WALL | | | TIES SHALL BE EMBEDDED AT LEAST 11/2 INCHES (38 MM) | | | INTO THE MORTAR BED OF SOLID MASONRY UNITS OR | | | SOLID-GROUTED HOLLOW UNITS. WALL TIES SHALL NOT BE BENT | | | AFTER BEING EMBEDDED IN GROUT OR MORTAR. | | | | | | 3) SHEET A1.3 NOTE 3 INDICATES NEW TILE TO BE INSTALLED | | | BUT METHOD OF ATTACHMENT NOT DECIDED, PLEASE PROVIDE | | | DOCUMENTATION FOR EITHER ADHERED MASONARY VENEER OR | | | ANCHORED MASONRY VENEER, SEE 1405 INSTALLATION OF WALL | | | COVERINGS. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-21 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-21 |
Time |
18:56 |
Sent To |
B |
|
| Notes |
| 2009-07-21 18:53:34 | | | | *** REDLINED PLANS. | | | | | | TO VERIFY NEW OR EXISTING BATTERY BACK UP EGRESS/EM LTS | | | MEETING NFPA-101 7.8,7.9, FBC 1016, NEC 700.12F | | | REVISE PLANS IF NEEDED TO BE INSTALLED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-03 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-03 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2009-07-03 09:14:00 | | | | ** DENIED PLANS * | | | | | | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE | | | FOLLOWING MINIMUM CODES. | | | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL | | | PLANS. | | | 2007 FBC W/ 2009 AMENDMENTS. | | | 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE) | | | 2002 NFPA-72 (OK) | | | 2006 NFPA-1 | | | 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN | | | ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE | | | THE 2008 NEC. | | | | | | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 | | | | | | | | | 2) NOTE: WILL LIGHTING BE 24 HR OPERATION OR CONTROLS | | | PER 13-415.AB.1 BE INSTALLED? | | | | | | 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, | | | AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. | | | THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR | | | INFORMATION ON SYMBOL LEGEND. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE 13-415.AB.5. IS THERE OTHER EXISTING LIGHTING? | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-22 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-22 |
Time |
11:01 |
Sent To |
B |
|
| Notes |
| 2009-07-22 11:18:01 | *****APPROVED***** | | | | | | PLAN SHEETS A1.1, A1.3, A1.4, AND E1 & E2 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2009-06-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-06-30 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-06-30 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2009-06-30 13:27:05 | *****APPROVED**** | | | | | | PLAN SHEETS A1.3, E1, AND E2 WERE STAMPED, INITIALED, | | | AND DATED. PROVISO WAS ADDED TO SHEET A1.3 AS FOLLOWS: | | | | | | STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-07-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-08 |
Time |
11:53 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2009-07-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-09 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-09 |
Time |
10:23 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2009-06-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-18 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-18 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2009-06-18 10:56:11 | NOTE: NO PLUMBING WORK SHOWN, NOR PLUMBING PLANS | | | SUBMITTED. |
|
|