Plan Review Details - Permit 09060183
Plan Review Stops For Permit 09060183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 09:35 Rev Time 0.00
Received By shill Date 2009-07-21 Time 20:53 Sent To  
Notes
2009-07-22 09:49:53PASSED W/REDLINE; PLYWOOD TO BE FRT @ ENGINEER'S
 REQUEST FBC601.3
 SPOKE WITH ARCHITECT AND STRUCTURAL ENGINEER
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-23 Cont ID  
Sent By jwitmer Date 2009-06-23 Time 10:28 Rev Time 0.77
Received By jwitmer Date 2009-06-23 Time 09:30 Sent To  
Notes
2009-06-23 10:51:41BUILDING PLAN REVIEW
 PERMIT: 09060183
 ADD: 222 LAKEVIEW 1ST, 2ND & 3RD FL GARAGE ELEVATOR
 LOBBIES
 CONT: G3 CONSTRUCTION
 TEL: (561) 445-3769
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 SHEET A1.4 INDICATES A NEW MASONRY WALL WITH NO
 REINFORCEMENT INFORMATION AND OR INFORMATION ON THE NEW
 TILE VENEER ON WALLS (A1.3 NOTE# 3). PLEASE PROVIDE BY
 FIRST INSPECTION:
  
 1) THE NEW BLOCK WALL PLEASE INDICATE COMPLIANCE WITH
 2103.1 JOINT REINFORCEMENT. JOINT REINFORCEMENT SHALL
 COMPLY WITH ASTM A 951. THE MAXIMUM SPACING OF
 CROSSWIRES IN LADDER-TYPE JOINT REINFORCEMENT AND POINT
 OF CONNECTION OF CROSS WIRES TO LONGITUDINAL WIRES OF
 TRUSS-TYPE REINFORCEMENT SHALL BE 16 INCHES (400 MM).
  
 2) SHEET A1.4 ALSO NEEDS TO COMPLY WITH INSTALATION OF
 WALL TIES TYING THE NEW WALL TO EXISTING BUILDING
 STRUCUTRAL MEMBERS: 2104.1.3 INSTALLATION OF WALL TIES.
 THE ENDS OF WALL TIES SHALL BE EMBEDDED IN MORTAR
 JOINTS. WALL TIE ENDS SHALL ENGAGE OUTER FACE SHELLS OF
 HOLLOW UNITS BY AT LEAST 1/2 INCH (12.7 MM). WIRE WALL
 TIES SHALL BE EMBEDDED AT LEAST 11/2 INCHES (38 MM)
 INTO THE MORTAR BED OF SOLID MASONRY UNITS OR
 SOLID-GROUTED HOLLOW UNITS. WALL TIES SHALL NOT BE BENT
 AFTER BEING EMBEDDED IN GROUT OR MORTAR.
  
 3) SHEET A1.3 NOTE 3 INDICATES NEW TILE TO BE INSTALLED
 BUT METHOD OF ATTACHMENT NOT DECIDED, PLEASE PROVIDE
 DOCUMENTATION FOR EITHER ADHERED MASONARY VENEER OR
 ANCHORED MASONRY VENEER, SEE 1405 INSTALLATION OF WALL
 COVERINGS.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 18:56 Sent To B
Notes
2009-07-21 18:53:34 
 *** REDLINED PLANS.
  
 TO VERIFY NEW OR EXISTING BATTERY BACK UP EGRESS/EM LTS
 MEETING NFPA-101 7.8,7.9, FBC 1016, NEC 700.12F
 REVISE PLANS IF NEEDED TO BE INSTALLED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 09:13 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 09:13 Sent To  
Notes
2009-07-03 09:14:00 
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
  
 2) NOTE: WILL LIGHTING BE 24 HR OPERATION OR CONTROLS
 PER 13-415.AB.1 BE INSTALLED?
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 13-415.AB.5. IS THERE OTHER EXISTING LIGHTING?
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 11:18 Rev Time 0.00
Received By mawillia Date 2009-07-22 Time 11:01 Sent To B
Notes
2009-07-22 11:18:01*****APPROVED*****
  
 PLAN SHEETS A1.1, A1.3, A1.4, AND E1 & E2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-06-30 Cont ID  
Sent By mawillia Date 2009-06-30 Time 13:38 Rev Time 0.00
Received By mawillia Date 2009-06-30 Time 13:12 Sent To  
Notes
2009-06-30 13:27:05*****APPROVED****
  
 PLAN SHEETS A1.3, E1, AND E2 WERE STAMPED, INITIALED,
 AND DATED. PROVISO WAS ADDED TO SHEET A1.3 AS FOLLOWS:
  
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-09 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 11:53 Sent To PC
Notes
2009-06-17 11:53:57TO B9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-07-09 Cont ID  
Sent By rregueir Date 2009-07-09 Time 10:23 Rev Time 0.00
Received By rregueir Date 2009-07-09 Time 10:23 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-06-18 Cont ID  
Sent By kstevens Date 2009-06-18 Time 10:55 Rev Time 0.00
Received By kstevens Date 2009-06-18 Time 10:55 Sent To  
Notes
2009-06-18 10:56:11NOTE: NO PLUMBING WORK SHOWN, NOR PLUMBING PLANS