| 2009-07-03 09:26:31 | |
| | ** DENIED PLANS * |
| | |
| | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| | FOLLOWING MINIMUM CODES. |
| | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| | PLANS. |
| | 2007 FBC W/ 2009 AMENDMENTS. |
| | 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE) |
| | 2002 NFPA-72 (OK) |
| | 2006 NFPA-1 |
| | 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN |
| | ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE |
| | THE 2008 NEC. |
| | |
| | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| | |
| | |
| | 2) NOTE: PLEASE SEE 210.8B2 FOR ALL RECEPTACLES IN |
| | KITCHEN AREAS TO BE GFI OR GFI PROTECTED WHETHER OR NOT |
| | THEY SERVE COUNTER SPACES. THE CODE WAS REVISED THAT IT |
| | IS NO LONGER ONLY RECEPTACLES WITHIN 6FT OF SINKS. THIS |
| | WOULD INCLUDE AREAS WHERE KITCHEN EQUIPMENT SUCH AS ICE |
| | MACHINES, DISHWASHERS AND OTHER SERVICE EQUIPMENT IS |
| | LOCATED. AREAS WHERE FLOORS ETC ARE WET IS A HIGH AREA |
| | OF HAZARD IN KITCHENS IN COMMERCIAL LOCATIONS. PLEASE |
| | SEE COMMENTARY IN THE 2005 NEC. |
| | |
| | 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, |
| | AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. |
| | THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR |
| | INFORMATION ON SYMBOL LEGEND. |
| | |
| | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE 13-415.AB.5. IS THERE OTHER EXISTING LIGHTING? |
| | |
| | 5) NOTE: PLEASE SHOW LIGHTING PER NFPA-101 7.8, |
| | 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN FOR |
| | MINIMUM EGRESS LIGHTING. |
| | ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE |
| | OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER |
| | EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR |
| | LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS |
| | COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS. |
| | PLEASE BE SURE TO GO OVER THIS WITH BUILDING |
| | OWNER/MANAGEMENT. |
| | OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED |
| | UNDER EMERGENCY POWER. |
| | |
| | 6) NOTE: PLEASE INDICATE THE REQUIRED LIGHTING CONTROLS |
| | PER FBC 13-415.AB.1,.1.2, .1.3. SOME ARE SHOWN ON PLANS |
| | HOWEVER NOT ALL. SEE AREAS 200,201, ONLY WHAT APPEARS |
| | AS A SINGLE POLE SWITCH IS SHOWN. AS THE SYMBOL LEGEND |
| | DOES NOT INCLUDE THIS DEVICE IT IS UNCLEAR AT THIS |
| | TIME. OTHER AREAS IN THE BACK OF HOUSE DO SHOW THE |
| | REQUIRED CONTROLS. |
| | |
| | 7) NOTE: PLEASE SEE 422.13, WATER HEATER LOAD IS |
| | CONSIDERED CONTINUOUS WHICH REQUIRES THIS TO BE FIGURED |
| | AT 125%. |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |