| | ** DENIED PLANS REVIEW ** |
| | |
| | 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST 2009 AND |
| | ADOPTION OF FAC SECTIONS 69A-69.004 AND 69A-3.012 |
| | ADOPTED DECEMBER 31ST 2008 SHALL FALL UNDER THE |
| | FOLLOWING DESIGNS. |
| | SOME CODE ON COVER SHEET FOR EXAMPLE ARE OK, HOWEVER |
| | ONE SUCH CODE NOTED IS A 2008 NFPA-101. |
| | THIS SHOULD BE THE 2006 NFPA-101 WHICH WAS ADOPTED |
| | DECEMBER 31ST, 2008 BY FAC SECTIONS GIVEN ABOVE. |
| | THE COVER SHEET ON THE ELECTRICAL PLANS STATE THE 2008 |
| | NFPA-70. AT THIS TIME THE STATE OF FLORIDA HAS NOT YET |
| | ADOPTED THE 2008 EDITION. |
| | PLEASE BE SURE THE THIS IS ADOPTED TO THE 2005 EDITION |
| | OF NFPA-70 |
| | |
| | 2) NOTE: ARCHITECTURAL TITLE BLOCK NEEDS TO CONTAIN ALL |
| | INFORMATION AS REQUIRED PER FAC 61G1-16.004 AND FS |
| | 481.219. |
| | PLEASE KNOW THAT ANY SHEETS WHICH CONTAIN THE |
| | INFORMATION OF THE ARCHITECTURAL FIRM MUST CONTAIN THIS |
| | INFORMATION. PLEASE KNOW THAT ANY SHEETS WHICH DO NOT |
| | NEED TO BE REPRINTED MAY HAVE INFORMATION PLACED NEATLY |
| | ON DOCUMENTS. THIS WILL ALLEVIATE THE RE-PRINTING OF |
| | DOCUMENTS. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | 3) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.AB.5. THERE ARE AREAS IN WHICH |
| | THE DESIGN IS OVER THE ALLOWANCE. |
| | PLEASE ALSO SEE AREA 1532 WHICH IS NOTED AS *OPEN |
| | AREA*. AN OPEN AREA ALLOWANCE WOULD BE 1.1, PLANS STATE |
| | 1.3. WOULD NOT THIS BE A CONFERENCE ROOM ALLOWANCE? |
| | |
| | 4) NOTE: PLEASE ADJUST LIGHTING CONTROLS PER |
| | 13-415.AB.1, .1.1, .1.2 AND .1.3. |
| | SEE NEW REVISIONS TO CHAPTER 13 AS THE ADOPTED 2009 |
| | SUPPLEMENTS. THERE ARE SUBSTANTIAL CHANGES. |
| | |
| | EXAMPLE: DISPLAY OR ACCENT LIGHTING SEPARATE CONTROLS? |
| | PLEASE SEE ROOM 1532 WHICH INDICATE ACCENT LIGHTS ON |
| | THE TC CIRCUIT L13A-4 YET DOES NOT HAVE ANY OVER RIDE |
| | OR CONTROL IN THIS SEPARATE ROOM. |
| | EACH SEPARATE SPACE NEEDS CONTROLS. |
| | |
| | EXAMPLE: AREA 1533 ALSO HAS ACCENT LIGHTING ON THIS |
| | SAME CIRCUIT NOTED TO THE SAME TC. WHERE IS THE |
| | SEPARATE CONTROL DEVICE? |
| | OCCUPANT MUST SEE LIGHTING WHICH IS BEING CONTROLLED. |
| | |
| | EXAMPLE: PLEASE SEE 1542 WHICH INDICATES DEVICES FOR |
| | LIGHTING CONTROLS WHICH ARE NOT LOCATED ON THE SYMBOL |
| | LEGEND. |
| | |
| | |
| | |
| | ** THERE ARE REVISIONS TO CHAPTER 13 FOR LIGHTING |
| | CONTROLS. |
| | |
| | 5) NOTE: PANELS L13A INDICATES FEED-THRU LUGS TO L13B. |
| | HOWEVER L13B DOES NOT INDICATE ANY FEED-THRU LUGS FOR |
| | L13C. RISER SHOWS THIS PANEL BEING FED FROM L13B. |
| | PLEASE SHOW HOW PANEL IS FED. IT IS ASSUMED PANEL B IS |
| | TO BE FEED THRU LUGS HOWEVER THIS CAN NOT BE ASSUMED. |
| | 240.4,215.5, 310.16, GIVEN AS GENERAL SECTIONS FOR |
| | RISER COORDINATION. |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION OF |
| | PLANS. |
| | |
| | 6) NOTE: PLEASE PROVIDE INFORMATION ON CLEARANCES OF |
| | EQUIPMENT. 110.26. THE TRANSFORMER SHOWN APPEARS TO |
| | ENCROACH ON PANEL H13A CLEARANCES. THE RISER OTHER |
| | INDICATES OTHER EQUIPMENT WHICH IS NOT SHOWN ON ROOM |
| | LAYOUT. IS THE TRANSFORMER FLOOR MOUNTED? |
| | PLEASE CHECK LAYOUT AND ADJUST. |
| | |
| | 7) NOTE: PLEASE PLACE NOTED ON PLANS FOR ROOM 1504. |
| | THIS IS NOT AN IT ROOM PER NEC 645.4 1-5. WIRING |
| | METHODS IN NEC 645 ARE NOT PERMITTED. OR WORDS TO THAT |
| | AFFECT. |
| | IF WIRING METHODS OF NEC 645 ARE NEEDED OR IN REQUEST |
| | BY OWNERS IT STAFF, PLEASE KNOW THAT ALL ITEMS IN 1-5 |
| | MUST BE MET. |
| | ANY OTHER CONSTRUCTION REQUIREMENTS SHALL BE |
| | NFPA-752003 EDITION AS ADOPTED PER FAC69A-3.012 |
| | |
| | 8) NOTE: NO ACCESS CONTROL SYSTEM IS PART OF THE |
| | SUBMITTED PLANS. ANY PROPOSED SYSTEM SHALL BE UNDER |
| | SEPARATE PERMITS AND PLANS. |
| | ** NFPA-101 2006 CHAPTER 7 DESIGN. |
| | ** J-BOXES MAY BE INSTALLED AS PART OF THE SCOPE SHOWN |
| | ON THIS PLAN. |
| | |
| | 9) NOTE: LOW VOLTAGE FOR DATA/PHONE SHALL BE UNDER |
| | SEPARATE PERMIT. SCOPE OF WORK MAY BE REFERENCED ON |
| | PERMIT APPLICATION TO THIS MAIN SET OF PLANS FOR A TURN |
| | AROUND PERMIT. SEPARATE FEES ON LV PERMIT. |
| | |
| | 10) NOTE: PLEASE KNOW THAT AT THIS TIME THE SCOPE OF |
| | WORK SHOWN ON PLANS FOR AREAS 1500, 1501, 1531, 1575, |
| | AND 1576 WILL BE HOLD FOR REVIEW AND SCOPE OF WORK |
| | UNDER THIS PERMIT APPLICATION. |
| | THIS IS COMMON AREA ELECTRICAL AND SPACE WHICH IS BEING |
| | SHOWN FED FROM THE TENANT SPACE ELECTRICAL SYSTEM. PER |
| | PLANS ANY FUTURE TENANT IN THE NW CORNER OF THE FLOOR |
| | WOULD ACTUALLY BE IN THIS TENANT SPACE TO ACCESS THEIR |
| | SPACE. WHERE IS TENANT SEPARATION? |
| | BUILDING ELECTRICAL ROOM IS ALSO SHOWN INSIDE THE |
| | TENANT SPACE. THIS IS NOT A NEW NOTE TO THIS BUILDING |
| | LOCATION ON SEVERAL DOCUMENTS ON PREVIOUS REVIEW. |
| | ACCESS, QUALIFIED PERSONNEL, ETC 24/7. |
| | THIS IS NOT AN ENTIRE TENANT OCCUPIED FLOOR. THERE IS |
| | OTHER TENANT SPACE SHOWN. |
| | AS NOTED ABOVE IN LIGHTING PERFORMANCE CALCULATION |
| | DESIGNS IN SOME AREAS ARE ABOVE ALLOWANCES BY SPACE BY |
| | SPACE. |
| | |
| | ** THERE ARE SEVERAL QUESTIONS ON DESIGN INTENT. PLEASE |
| | SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT |
| | ELECTRICAL PLANS. PLEASE KNOW THAT EVEN IF COMMENTS ARE |
| | NOT MADE BY OTHER TRADES COORDINATION OF ALL PLANS |
| | SHALL BE MET. |
| | |
| | 11) NOTE: PLEASE SEE 250.30A3 AND 250.66 FOR THE SIZING |
| | OF THE GROUNDING ELECTRODE ON THE DERIVED SIDE OF THE |
| | TRANSFORMER. RISER NOTES A #6, YET THE DERIVED |
| | CONDUCTORS ARE 600MCM. SEE 250.66. |
| | |
| | |
| | 12) NOTE: PLEASE KNOW THAT THE LIGHTING LISTED IN H |
| | PANEL WILL BE REQUIRED TO NOTED TO AREAS AND LOCATIONS |
| | MORE THAN SHOWN. THIS CAN BE A PROVISO ITEM. |
| | 408.4. |
| | |
| | |
| | 13) NOTE: ALL STROBE/HORN STROBE DEVICES ON FA0.1 ARE |
| | SHOWN AT 110 CD, YET SHEET FA2.1 DOES INDICATE SEVERAL |
| | AT 75CD. PLEASE COORDINATE. |
| | 11-4.28.1,.2 AND.3. FOR LOCATION/HEIGHTS/LEVELS. |
| | FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, COORDINATION |
| | OF RECORD PLANS. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |