Plan Review Details - Permit 09060140
Plan Review Stops For Permit 09060140
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-10-28 Cont ID  
Sent By shill Date 2009-10-28 Time 13:29 Rev Time 0.00
Received By shill Date 2009-10-28 Time 13:29 Sent To  
Notes
2009-10-28 13:29:37ALTERNATE MATERIALS & METHODS OK PER DW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-08 Cont ID  
Sent By shill Date 2009-10-08 Time 15:45 Rev Time 0.00
Received By shill Date 2009-10-08 Time 15:45 Sent To  
Notes
2009-10-08 15:46:11REVISION, ASK09
 BLDG REVISION SUBMITTED 10/5/9
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-10 Cont ID  
Sent By shill Date 2009-09-10 Time 15:18 Rev Time 0.00
Received By shill Date 2009-09-10 Time 15:18 Sent To  
Notes
2009-09-10 15:19:13REVISION, CEILING BRACING AT DUCTWORK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 20:49 Rev Time 0.00
Received By shill Date 2009-07-22 Time 20:18 Sent To  
Notes
2009-07-22 20:54:14***PROVISO***
  
 ARCHITECT IS TO PROVIDE A LETTER, APPROVED BY THE
 BUILDING OFFICIAL, AT TIME OF INSPECTION WHICH REQUESTS
 THE USE OF FBC104.11 ALTERNATE MATERIALS AND METHODS.
  
 A LETTER, SIGNED AND SEALED BY THE DESIGNER OF RECORD,
 IS TO BE SUBMITTED TO THE BUILDING OFFICIAL REQUESTING
 USE OF ALTERNATE MATERIALS AND METHODS. THIS LETTER
 SHOULD CLEARLY STATE THE CODE REQUIREMENT AND PRESENT
 THE ALTERNATE METHOD OR MATERIAL ALONG WITH ANY
 SUPPORTING ARGUMENT AND/OR SUPPORTING DOCUMENTS. THIS
 WILL BE REVIEWED BY THE BUILDING OFFICIAL AND THE FIRE
 MARSHALL.
  
 THIS LETTER, APPROVED BY THE BUILDING OFFICIAL AND FIRE
 MARSHALL, IS TO BE PROVIDED TO THE INSPECTOR. THIS
 PERMIT IS ISSUED AT CONTRACTOR'S RISK.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 17:35 Rev Time 0.00
Received By shill Date 2009-06-15 Time 15:36 Sent To  
Notes
2009-06-15 18:02:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC1004, OCCUPANT LOAD NOT TO BE LESS THAN FBC TABLE
 1004.1.1; THEREFORE, PLEASE ROUND UP WHEN CALCULATING
 OCCUPANT LOAD (185 OCCUPANTS RATHER THAN 184).
  
 2. DESIGN INTENT REGARDING FIRE RATED WALLS IS NOT
 CLEAR (SEE OTHER COMMENTS FOR EXAMPLES). TO AVOID FIELD
 AND PLAN REVIEW ISSUES, PLEASE NOTE ALL FIRE RATED
 WALLS CONSISTENTLY ON THE PLAN. FOR INSTANCE, A0.1
 SHOWS ONLY TWO AREAS WITH RATED WALLS; THE AREA N.I.C.
 AND THE AREA ADJACENT TO ROOM 1560. THE WALL AT ROOM
 1560 IS SHOWN AS PARTIALLY RATED, NOT CONTINUOUS (SEE
 THE WALL BETWEEN COUNTER AND HALL).
  
 3. ELEVATOR LOBBY REQUIRED IN ACCORDANCE WITH
 FBC707.14.1, OR NOTE EXCEPTION TO THE REQUIRED ELEVATOR
 LOBBY ON THE PLAN. ALTHOUGH THE ELEVATOR AREA IS NOTED
 AS AN ELEVATOR LOBBY, THIS AREA IS OPEN TO OTHER AREAS,
 AND AN OCCUPANT IS FORCED TO GO THROUGH THIS AREA TO
 ACCESS THE EXIT.
  
 4. FBC708.1(7), TENANT SEPARATION REQUIRED BETWEEN THE
 TENANT SPACES AND THE COMMON AREA (TENANCY IN COMMON),
 PER BUILDING OFFICIAL. PLEASE CLEARLY NOTE EACH
 SEPARATE TENANT AREA; IT IS NOT CLEAR WHETHER ONE
 TENANT IS INCLUDED IN THIS PERMIT OR TWO (DUE TO A FIRE
 RATED WALL BETWEEN TWO AREAS). PLEASE REVISE WALL
 CONSTRUCTION TO INCLUDE 1 HOUR WALLS WHERE REQUIRED.
  
 5. OPENING PROTECTION REQUIRED (3/4 HOUR) FOR ALL
 OPENINGS IN TENANT SEPARATION WALLS, FBC TABLE 715.4.
  
 6. A0.1 STATES THERE ARE 5 EXITS; PLEASE SEE DEFINITION
 OF EXIT, FBC1002. IT APPEARS THAT THERE ARE TWO EXITS;
 PLEASE REVISE.
  
 7. A0.1, SITE LOCATION OR GENERAL NOTES, ITEM 10, NOC
 IS TO BE POSTED ON JOB AT ALL TIMES; LANGUAGE IN THIS
 NOTE IS INCORRECT. PLEASE EITHER REVISE NOTE TO COMPLY
 WITH FS713.13 OR REMOVE THE NOTE.
  
 8. PROVIDE A HEAD OF WALL ASSEMBLY (HW) FOR THE TOP OF
 THE RATED PARTITION WALL, FBC708.4.
  
 9. THE ARCHITECT'S SEAL IS TO INCLUDE A DATE, FS481.
  
 10. SHOW REQUIRED KNEE SPACE FOR SINK, A4.2,
 FBC11-4.24.
  
 11. SHOW HOW DOOR F COMPLIES WITH FBC1003.6, MEANS OF
 EGRESS CONTINUITY.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-06 Cont ID  
Sent By dpalmer Date 2009-10-06 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2009-10-06 Time 08:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-28 Cont ID  
Sent By dpalmer Date 2009-07-28 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2009-07-28 Time 19:03 Sent To  
Notes
2009-07-28 19:04:49PROVISO/ BEFORE ROUGH
  
  
 1) NOTED FOR INFORMATION: 2HR WALL RATING AROUND ROOM
 1504 WITH A G TYPE DOOR WHICH IS STATED 45MIN/1HR DOOR
 ON DOOR SCHEDULE. IF THE INTENT BASED ON ELECTRICAL
 PLANS IS TO HAVE ROOM BE CONSIDERED AN IT ROOM MEETING
 DEFINITIONS OF 645.4 (1.5) AND NFPA-75 THIS MAY BE AN
 ITEM TO BE REVISED. THIS IS NOT A COMMENT TO CORRECT
 ARCHITECTURAL PLANS AS REVIEW HAS ALREADY BEEN PASSED
 BY THE BUILDING REVIEWER.
  
 2) NOTE: THE EFFECTIVE WATTAGE CAN NOT BE LESS THAN
 DESIGN/ PER 13-415.AB.5 DISPLAY AND ACCENT LIGHTING IS
 NO LONGER EXEMPT. THE FACT THE EFFECTIVE IS SHOWN LESS
 IS THE DIFFERENCE WATTAGE ON DISPLAY AND ACCENT
 LIGHTING. THE DESIGN IS STILL LESS THAN ALLOWANCE.
 CHECK PROGRAM AS THERE WAS A GLITCH UPDATE.
 UPDATE CALCULATIONS
  
 3) NOTE: LIGHTING CONTROLS FOR ACCENT LIGHTING IN
 LOCATIONS SUCH AS ROOM 1532 AND 1533 ARE NOT CLEAR.
 NOTES ON PLANS MENTIONS TO SEE DETAIL ON TC-1 ON SHEET
 E0.1 HOWEVER THE TC-1 DETAIL ON SAID NOTED SHEET DOES
 NOT MENTION ANY CONTROL FOR 1533 ONLY 1532.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 21:33 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 21:33 Sent To  
Notes
2009-07-24 21:34:09 
 ** DENIED 2ND REVIEW. **
  
 1) NOTE: ONE SET OF MEP PLANS ARE NOT SIGNED, DATED OR
 SEALED AS REQUIRED UNDER FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002. THE FAC IS
 SPECIFIC WHICH REQUIRES *ALL* COPIES INCLUDING SETS OF
 PLANS AND DOCUMENTS FOR OWNER AND OWNER REPRESENTATIVE
 TO CONTAIN THE SIGNATURE, DATE AND SEAL. THE EXACT
 WORDING HAS BEEN EXTRACTED FROM THE SECTION NOTED
 ABOVE. THIS IS ONLY PART OF THE ENTIRE SECTION AS NOTED
 WHICH CAN BE EASILY VIEWED ONLINE AT THE FOLLOWING
 ADDRESS.
 HTTPS://WWW.FLRULES.ORG/GATEWAY/RULENO.ASP?ID=61G15-23.
 002
  
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN BY HAND THE
 LICENSEE???S HANDWRITTEN SIGNATURE (FACSIMILES ARE NOT
 ACCEPTABLE) AND AFFIX THE LICENSEE???S SEAL:
 (A) TO ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS,
 REPORTS, OR DOCUMENTS PREPARED OR ISSUED BY THE
 LICENSEE AND BEING FILED FOR PUBLIC RECORD; AND
 (B) TO ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER???S REPRESENTATIVE;
  
  
 ** IF THIS WAS THE ONLY COMMENT ENGINEERS OF RECORD
 COULD MAKE TRIP TO OFFICE TO ADDRESS THE ABOVE.
  
 2) NOTE: NOTED FOR INFORMATION: 2HR WALL RATING AROUND
 ROOM 1504 WITH A G TYPE DOOR WHICH IS STATED 45MIN/1HR
 DOOR ON DOOR SCHEDULE. IF THE INTENT BASED ON
 ELECTRICAL PLANS IS TO HAVE ROOM BE CONSIDERED AN IT
 ROOM MEETING DEFINITIONS OF 645.4 (1.5) AND NFPA-75
 THIS MAY BE AN ITEM TO BE REVISED. THIS IS NOT A
 COMMENT TO CORRECT ARCHITECTURAL PLANS AS REVIEW HAS
 ALREADY BEEN PASSED BY THE BUILDING REVIEWER.
  
 3) NOTE: THE EFFECTIVE WATTAGE CAN NOT BE LESS THAN
 DESIGN/ PER 13-415.AB.5 DISPLAY AND ACCENT LIGHTING IS
 NO LONGER EXEMPT. THE FACT THE EFFECTIVE IS SHOWN LESS
 IS THE DIFFERENCE WATTAGE ON DISPLAY AND ACCENT
 LIGHTING. THE DESIGN IS STILL LESS THAN ALLOWANCE.
 CHECK PROGRAM AS THERE WAS A GLITCH UPDATE.
  
 4) NOTE: LIGHTING CONTROLS FOR ACCENT LIGHTING IN
 LOCATIONS SUCH AS ROOM 1532 AND 1533 ARE NOT CLEAR.
 NOTES ON PLANS MENTIONS TO SEE DETAIL ON TC-1 ON SHEET
 E0.1 HOWEVER THE TC-1 DETAIL ON SAID NOTED SHEET DOES
 NOT MENTION ANY CONTROL FOR 1533 ONLY 1532.
  
 ** WITH THE COMMENTS ABOVE NOTE #1 MUST BE ADDRESSED AT
 THIS TIME. OTHER ITEMS COULD BE DONE AS A PROVISO TO BE
 ADDRESSED WITH ANY OTHER REVISIONS BEFORE ROUGH
 ELECTRICAL INSPECTION.
  
 PLEASE CALL TO SET UP A TIME FOR ENGINEERS OF RECORD TO
 COME INTO OFFICE TO SIGN, DATE AND SEAL SAID PLANS SO
 THERE IS NO FURTHER DELAY OF PROJECT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 17:13 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 17:13 Sent To  
Notes
2009-07-04 17:14:03 
  
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS SUBMITTED AFTER MARCH 1ST 2009 AND
 ADOPTION OF FAC SECTIONS 69A-69.004 AND 69A-3.012
 ADOPTED DECEMBER 31ST 2008 SHALL FALL UNDER THE
 FOLLOWING DESIGNS.
 SOME CODE ON COVER SHEET FOR EXAMPLE ARE OK, HOWEVER
 ONE SUCH CODE NOTED IS A 2008 NFPA-101.
 THIS SHOULD BE THE 2006 NFPA-101 WHICH WAS ADOPTED
 DECEMBER 31ST, 2008 BY FAC SECTIONS GIVEN ABOVE.
 THE COVER SHEET ON THE ELECTRICAL PLANS STATE THE 2008
 NFPA-70. AT THIS TIME THE STATE OF FLORIDA HAS NOT YET
 ADOPTED THE 2008 EDITION.
 PLEASE BE SURE THE THIS IS ADOPTED TO THE 2005 EDITION
 OF NFPA-70
  
 2) NOTE: ARCHITECTURAL TITLE BLOCK NEEDS TO CONTAIN ALL
 INFORMATION AS REQUIRED PER FAC 61G1-16.004 AND FS
 481.219.
 PLEASE KNOW THAT ANY SHEETS WHICH CONTAIN THE
 INFORMATION OF THE ARCHITECTURAL FIRM MUST CONTAIN THIS
 INFORMATION. PLEASE KNOW THAT ANY SHEETS WHICH DO NOT
 NEED TO BE REPRINTED MAY HAVE INFORMATION PLACED NEATLY
 ON DOCUMENTS. THIS WILL ALLEVIATE THE RE-PRINTING OF
 DOCUMENTS.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 3) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5. THERE ARE AREAS IN WHICH
 THE DESIGN IS OVER THE ALLOWANCE.
 PLEASE ALSO SEE AREA 1532 WHICH IS NOTED AS *OPEN
 AREA*. AN OPEN AREA ALLOWANCE WOULD BE 1.1, PLANS STATE
 1.3. WOULD NOT THIS BE A CONFERENCE ROOM ALLOWANCE?
  
 4) NOTE: PLEASE ADJUST LIGHTING CONTROLS PER
 13-415.AB.1, .1.1, .1.2 AND .1.3.
 SEE NEW REVISIONS TO CHAPTER 13 AS THE ADOPTED 2009
 SUPPLEMENTS. THERE ARE SUBSTANTIAL CHANGES.
  
 EXAMPLE: DISPLAY OR ACCENT LIGHTING SEPARATE CONTROLS?
 PLEASE SEE ROOM 1532 WHICH INDICATE ACCENT LIGHTS ON
 THE TC CIRCUIT L13A-4 YET DOES NOT HAVE ANY OVER RIDE
 OR CONTROL IN THIS SEPARATE ROOM.
 EACH SEPARATE SPACE NEEDS CONTROLS.
  
 EXAMPLE: AREA 1533 ALSO HAS ACCENT LIGHTING ON THIS
 SAME CIRCUIT NOTED TO THE SAME TC. WHERE IS THE
 SEPARATE CONTROL DEVICE?
 OCCUPANT MUST SEE LIGHTING WHICH IS BEING CONTROLLED.
  
 EXAMPLE: PLEASE SEE 1542 WHICH INDICATES DEVICES FOR
 LIGHTING CONTROLS WHICH ARE NOT LOCATED ON THE SYMBOL
 LEGEND.
  
  
  
 ** THERE ARE REVISIONS TO CHAPTER 13 FOR LIGHTING
 CONTROLS.
  
 5) NOTE: PANELS L13A INDICATES FEED-THRU LUGS TO L13B.
 HOWEVER L13B DOES NOT INDICATE ANY FEED-THRU LUGS FOR
 L13C. RISER SHOWS THIS PANEL BEING FED FROM L13B.
 PLEASE SHOW HOW PANEL IS FED. IT IS ASSUMED PANEL B IS
 TO BE FEED THRU LUGS HOWEVER THIS CAN NOT BE ASSUMED.
 240.4,215.5, 310.16, GIVEN AS GENERAL SECTIONS FOR
 RISER COORDINATION.
 FBC 106.1.1, 106.1.2 FOR CLARITY AND COORDINATION OF
 PLANS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION ON CLEARANCES OF
 EQUIPMENT. 110.26. THE TRANSFORMER SHOWN APPEARS TO
 ENCROACH ON PANEL H13A CLEARANCES. THE RISER OTHER
 INDICATES OTHER EQUIPMENT WHICH IS NOT SHOWN ON ROOM
 LAYOUT. IS THE TRANSFORMER FLOOR MOUNTED?
 PLEASE CHECK LAYOUT AND ADJUST.
  
 7) NOTE: PLEASE PLACE NOTED ON PLANS FOR ROOM 1504.
 THIS IS NOT AN IT ROOM PER NEC 645.4 1-5. WIRING
 METHODS IN NEC 645 ARE NOT PERMITTED. OR WORDS TO THAT
 AFFECT.
 IF WIRING METHODS OF NEC 645 ARE NEEDED OR IN REQUEST
 BY OWNERS IT STAFF, PLEASE KNOW THAT ALL ITEMS IN 1-5
 MUST BE MET.
 ANY OTHER CONSTRUCTION REQUIREMENTS SHALL BE
 NFPA-752003 EDITION AS ADOPTED PER FAC69A-3.012
  
 8) NOTE: NO ACCESS CONTROL SYSTEM IS PART OF THE
 SUBMITTED PLANS. ANY PROPOSED SYSTEM SHALL BE UNDER
 SEPARATE PERMITS AND PLANS.
 ** NFPA-101 2006 CHAPTER 7 DESIGN.
 ** J-BOXES MAY BE INSTALLED AS PART OF THE SCOPE SHOWN
 ON THIS PLAN.
  
 9) NOTE: LOW VOLTAGE FOR DATA/PHONE SHALL BE UNDER
 SEPARATE PERMIT. SCOPE OF WORK MAY BE REFERENCED ON
 PERMIT APPLICATION TO THIS MAIN SET OF PLANS FOR A TURN
 AROUND PERMIT. SEPARATE FEES ON LV PERMIT.
  
 10) NOTE: PLEASE KNOW THAT AT THIS TIME THE SCOPE OF
 WORK SHOWN ON PLANS FOR AREAS 1500, 1501, 1531, 1575,
 AND 1576 WILL BE HOLD FOR REVIEW AND SCOPE OF WORK
 UNDER THIS PERMIT APPLICATION.
 THIS IS COMMON AREA ELECTRICAL AND SPACE WHICH IS BEING
 SHOWN FED FROM THE TENANT SPACE ELECTRICAL SYSTEM. PER
 PLANS ANY FUTURE TENANT IN THE NW CORNER OF THE FLOOR
 WOULD ACTUALLY BE IN THIS TENANT SPACE TO ACCESS THEIR
 SPACE. WHERE IS TENANT SEPARATION?
 BUILDING ELECTRICAL ROOM IS ALSO SHOWN INSIDE THE
 TENANT SPACE. THIS IS NOT A NEW NOTE TO THIS BUILDING
 LOCATION ON SEVERAL DOCUMENTS ON PREVIOUS REVIEW.
 ACCESS, QUALIFIED PERSONNEL, ETC 24/7.
 THIS IS NOT AN ENTIRE TENANT OCCUPIED FLOOR. THERE IS
 OTHER TENANT SPACE SHOWN.
 AS NOTED ABOVE IN LIGHTING PERFORMANCE CALCULATION
 DESIGNS IN SOME AREAS ARE ABOVE ALLOWANCES BY SPACE BY
 SPACE.
  
 ** THERE ARE SEVERAL QUESTIONS ON DESIGN INTENT. PLEASE
 SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS. PLEASE KNOW THAT EVEN IF COMMENTS ARE
 NOT MADE BY OTHER TRADES COORDINATION OF ALL PLANS
 SHALL BE MET.
  
 11) NOTE: PLEASE SEE 250.30A3 AND 250.66 FOR THE SIZING
 OF THE GROUNDING ELECTRODE ON THE DERIVED SIDE OF THE
 TRANSFORMER. RISER NOTES A #6, YET THE DERIVED
 CONDUCTORS ARE 600MCM. SEE 250.66.
  
  
 12) NOTE: PLEASE KNOW THAT THE LIGHTING LISTED IN H
 PANEL WILL BE REQUIRED TO NOTED TO AREAS AND LOCATIONS
 MORE THAN SHOWN. THIS CAN BE A PROVISO ITEM.
 408.4.
  
  
 13) NOTE: ALL STROBE/HORN STROBE DEVICES ON FA0.1 ARE
 SHOWN AT 110 CD, YET SHEET FA2.1 DOES INDICATE SEVERAL
 AT 75CD. PLEASE COORDINATE.
 11-4.28.1,.2 AND.3. FOR LOCATION/HEIGHTS/LEVELS.
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-29 Cont ID  
Sent By mawillia Date 2009-07-29 Time 15:03 Rev Time 0.00
Received By mawillia Date 2009-07-29 Time 14:08 Sent To B1
Notes
2009-07-29 15:03:00*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A2.2, A3.0, A3.1, E2.1,
 FA0.1,FA2.1, FS0.1, AND FS2.1 WERE STAMPED, INITIALED,
 AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By mawillia Date 2009-07-08 Time 15:25 Rev Time 0.00
Received By mawillia Date 2009-07-06 Time 11:21 Sent To  
Notes
2009-07-08 10:26:32*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101
 IS TO BE REFERENCED. AMEND ON SHEET A0.1 IN THE
 BUILDING CODE ANALYSIS - FIRE SECTION.
  
 3. ON SHEET A0.1, IT IS STATED IN THE BUILDING CODE
 ANALYSIS - OCCUPANT LOAD SECTION - THAT FIVE (5) EXITS
 ARE PROVIDED. INDICATE/SHOW THE PROVIDED EXITS.
  
 4. AS PER NFPA 101 - LIFE SAFETY CODE - 2006 EDITION,
 CHAPTER 38 (NOT 36 AS LISTED ON SHEET A0.1 IN THE
 BUILDING CODE ANALYSIS - FIRE SECTION) IS THE REFERENCE
 FOR NEW BUSINESS OCCUPANCY.
  
 5. IF APPLICABLE, ADD TO DOOR HARDWARE SCHEDULE NOTES
 (SHEET A2.2) THAT: DELAYED-EGRESS LOCKING COMPLYING
 WITH 7.2.1.6.1 AND ACCESS-CONTROLLED EGRESS DOORS
 COMPLYING WITH 7.2.1.6.2 OF NFPA 101 SHALL BE
 PERMITTED.
  
 6. THE 2002 EDITION OF NFPA 72 (NATIONAL FIRE ALARM
 CODE) SHALL BE REFERENCED.
  
 7. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT
 THAT: DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM.
  
 8. ON SHEET FS0.1, AMEND GENERAL NOTE #1 TO REFLECT
 2007 FLORIDA BUILDING CODE AND NFPA 13 - 2002 EDITION.
 AMEND NOTE #11 TO THE 2002 EDITION OF NFPA 13 (CURRENT
 ADOPTION BY THIS AHJ).
  
 9.ON SHEET FS2.1, AMEND REMOTE AREA TO REFLECT NFPA 13
 - 2002 EDITION.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-10-06 Cont ID  
Sent By lmartine Date 2009-10-05 Time 09:49 Rev Time 0.00
Received By lmartine Date 2009-10-06 Time 09:49 Sent To  
Notes
2009-10-06 09:50:20GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 10:59 Sent To  
Notes
2009-09-08 10:59:51REVISION CEILING DETAIL TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 10:45 Sent To  
Notes
2009-09-08 10:46:47(-03-09 ENERGY CALCS ROUTED TO D. PALMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 13:46 Rev Time 0.00
Received By shill Date 2009-07-22 Time 13:46 Sent To  
Notes
2009-07-22 13:48:37C41 **EXPEDITED PER CONTRACTOR REQUEST**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-22 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 08:37 Rev Time 0.00
Received By shill Date 2009-06-08 Time 13:59 Sent To  
Notes
2009-07-06 08:37:53C-35 ROUTED TO FIRE MAW /JW
2009-06-08 14:00:10TO C35

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By rregueir Date 2009-07-22 Time 19:41 Rev Time 0.00
Received By rregueir Date 2009-07-22 Time 19:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By rregueir Date 2009-06-17 Time 09:37 Rev Time 0.00
Received By rregueir Date 2009-06-17 Time 09:37 Sent To P
Notes
2009-06-17 09:39:22REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. FIRE RATED SEPARATION IS REQUIRED BETWEEN TENANT
 SPACE AND BUILDING COMMON AREAS (PLEASE SEE BUILDING
 PLAN REVIEW COMMENT #4 FOR ADDITIONAL INFORMATION).
 THERE ARE SEVERAL DUCT PENETRATIONS IN WALLS WHERE
 RATED TENANT SEPARATION WILL BE REQUIRED. PLEASE
 COORDINATE WITH THE ARCHITECT IN DETERMINING THE
 LOCATION OF THESE RATED WALL ASSEMBLIES AND SHOW THAT
 ALL DUCT PENETRATIONS OF THESE WALLS ARE PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5.
  
 2. THE SUPPLY DROP SERVING "BOOKS" ROOM 1543 IS MISSING
 VOLUME DAMPER. VOLUME DAMPERS OR OTHER MEANS OF SUPPLY
 AIR ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR
 AT EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER IN
 ACCORDANCE WITH FBC-M 603.17.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-29 Cont ID  
Sent By dwise Date 2009-07-29 Time 16:47 Rev Time 0.00
Received By dwise Date 2009-07-29 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By kstevens Date 2009-06-29 Time 14:47 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 14:47 Sent To  
Notes
2009-06-29 15:00:43DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1 ADMIN
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH SKB ARCHITECTS TITLE BLOCK. THE FIRM
 LICENSE NUMBER IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.004(2) & FS 481.205.
  
 2. ALL SHEETS SIGNED & SEALED BY THE ARCHITECT SHALL
 HAVE THE PRINTED NAME OF THE PERSON SEALING THE
 DOCUMENT IN THE TITLE BLOCK. FAC 61G1-16.004(6) & FS
 481.2055.
  
 3. SHT A5.1 DETAILS 6 & 12 PER SECTION 11-4.24.6 A
 CLEAR FLOOR SPACE, 30 INCHES BY 48 INCHES EXTENDING A
 MAXIMUM 19 INCHES UNDERNEATH THE SINK IS REQUIRED. THE
 GARBAGE DISPOSAL SHALL NOT BE IN THE CLEAR FLOOR SPACE.
 SEE FIGURE 32. PLEASE SUBMIT A DETAIL SHOWING
 COMPLIANCE. ALSO THE CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE REQUIRED FOR THE FIXTURE. PLEASE
 DELETE THE CABINET DOORS. FORWARD APPROACH IS REQUIRED.
  
 4. SHT A5.1 DETAILS 6 & 12 NOTE INDICATES THE DISPOSAL
 IS ADA COMPLIANT. SEARCH OF PRODUCT SPECIFICATIONS DOES
 NOT INDICATE COMPLIANCE. PLEASE SUBMIT MANUF.
 SPECIFICATIONS SHOWING COMPLIANCE WITH ADA. SECTION
 106.1.2. (MORE INFORMATION REQUIRED).
  
 5. SHT P0.1 WATER ISOMETRIC RISER DIAGRAMS. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE DISH WASHERS.
 SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-12 Cont ID  
Sent By eschneid Date 2009-06-12 Time 11:28 Rev Time 0.25
Received By eschneid Date 2009-06-12 Time 11:28 Sent To  
Notes
2009-06-12 11:29:44INTERIOR BUILDOUT UPPER FLOOR.