Plan Review Details - Permit 09060135
Plan Review Stops For Permit 09060135
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 12:59 Rev Time 0.50
Received By jwitmer Date 2009-07-24 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By jwitmer Date 2009-06-22 Time 08:22 Rev Time 0.44
Received By jwitmer Date 2009-06-22 Time 07:55 Sent To  
Notes
2009-06-22 08:16:15BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) 1603.1.4 WIND DESIGN DATA. THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING
 SYSTEM OF THE BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED. NOTE THIS IS A "C"
 EXPOSURE AND
 MEAN ROOF HEIGHT MULTIPLIER. BUILDING HEIGTH IS
 APPROXIMATELY 230 FEET.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
 INDICATE IF THIS IS A INTERIOR ZONE(4) OR END ZONE (5)
 WITH THE ASSOCIATED HIGHER PRESSURES.
  
 3) IN THE PRODUCT APPROVAL PLEASE CIRCLE THE SQUARE
 FOOTAGE AND TYPE OF GLASS TO BE INSTALLED AND THE
 ASSOCIATED PRESSURE.
  
 4) SHEET A1 INDICATES THE USE OF 3/4 INCH CDX PLYWOOD,
 NOTE THIS IS A TYPE IA BUIULDING. SEE SECTION 603.1
 FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN:
 (1.2) NON-BEARING EXTERIOR WALLS WHERE NO FIRE RATING
 IS REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-30 Cont ID  
Sent By dpalmer Date 2009-07-30 Time 09:10 Rev Time 0.00
Received By dpalmer Date 2009-07-30 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 09:56 Sent To  
Notes
2009-07-04 09:56:39 
  
 ** DENIED REVIEW **
  
 ** PLANS WERE STAMPED BY ELECTRICAL AND COMMENTS
 REDLINED HOWEVER HAVE BEEN VOIDED BASED ON BUILDING
 REVIEW COMMENTS. THE SHEET WHICH ELECTRICAL IS SHOWN
 WILL NEED TO BE UPDATED. PLEASE ADDRESS THE OTHER MINOR
 ELECTRICAL COMMENTS BELOW AT THE SAME TIME.
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN THE CODES UNDER
 ADOPTION BY THE STATE OF FLORIDA.
  
 ELECTRICAL SHALL CONTAIN:
 2005 NFPA-70
 2006 NFPA-101
  
 PLEASE SEE FAC 69A-60.004 AND 69A-3.012.
 FS 553.73 AND 2007 FBC WITH 2009 SUPPLEMENTS
  
 2) NOTE: THE SCOPE SHOWN INCLUDES ENCLOSING AREA TO BE
 PART OF A HABITABLE ROOM. PLEASE SEE 210.52 AS
 RECEPTACLES SPACING SHALL MEET REQUIRED SPACING WITHIN
 6FT OF A DOOR. THE FIXED GLASS PANELS ARE COUNTED AS
 WALL SPACE THEREFORE REQUIRING THE RECEPTACLE TO BE
 WITHIN 6FT OF DOOR OPENING.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-30 Cont ID  
Sent By mawillia Date 2009-07-30 Time 12:19 Rev Time 0.00
Received By mawillia Date 2009-07-30 Time 12:11 Sent To  
Notes
2009-07-30 12:17:59*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEET A1 WAS STAMPED, INITIALED,
 AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-26 Cont ID  
Sent By mawillia Date 2009-06-26 Time 14:44 Rev Time 0.00
Received By mawillia Date 2009-06-26 Time 14:16 Sent To  
Notes
2009-06-26 14:39:03*****DENIED*****
  
 1. INCLUDE IN GENERAL NOTES THAT: NFPA 101 - LIFE
 SAFETY CODE - 2006 EDITION SHALL BE REFERENCED.
  
 2. PLEASE SHOW FIRE SPRINKLER AND SMOKE ALARM COVERAGE
 FOR THE PROPOSED SCOPE OF WORK AREA.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 14:27 Rev Time 0.00
Received By shill Date 2009-07-15 Time 14:27 Sent To  
Notes
2009-07-15 14:29:10B13
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-13 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 12:04 Sent To  
Notes
2009-06-08 12:05:08T0 B4

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-13 Cont ID  
Sent By rregueir Date 2009-07-13 Time 13:28 Rev Time 0.00
Received By rregueir Date 2009-07-13 Time 13:28 Sent To R
Notes
2009-07-13 13:30:26NO MECHANICAL PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status P Date 2009-06-25 Cont ID  
Sent By aaponte Date 2009-06-25 Time 10:50 Rev Time 0.00
Received By aaponte Date 2009-06-25 Time 10:50 Sent To  
Notes
***NONE***