Plan Review Details - Permit 09060129
Plan Review Stops For Permit 09060129
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-10-26 Cont ID  
Sent By jwitmer Date 2009-10-26 Time 09:46 Rev Time 0.77
Received By jwitmer Date 2009-10-26 Time 09:46 Sent To  
Notes
2009-10-26 10:07:57BUILDING PROVISO:
  
 1) SKWTCH SK-2 THE FRAME WALL DOES NOT INDICATE IF THIS
 IS INTERIOR OR
 EXTERIOR, IF CONSIDERED EXTERIOR COMPLY WITH:
  
 2304.11.2.6 WOOD SIDING. CLEARANCE BETWEEN WOOD SIDING
 AND EARTH
 ON THE EXTERIOR OF A BUILDING SHALL NOT BE LESS THAN 6
 INCHES (152 MM)
 EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF
 NATURALLY DURABLE
 OR PRESERVATIVE-TREATED WOOD.
  
 2) NO ROOFING PERMIT HAS BEEN APPLIED FOR AT THIS TIME
 (10-26-09)
 FL S S 489.13 QUALIFICATIONS FOR PRACTICE; RESTRICTIONS
 (2) (B) A GENERAL, BUILDING ,OR RESIDENTIAL CONTRACTOR
 SHALL NOT BE REQUIRED TO SUBCONTRACT THE INSTALLATION,
 OR REPAIR MADE UNDER WARRANTY, OF WOOD SHINGLES, WOOD
 SHAKES, OR ASPHALT OR FIBERGLASS SHINGLE ROOFING
 MATERIALS ON A NEW BUILDING OF HIS CONSTRUCTION.
 (G) NO GENERAL, BUILDING OR RESIDENTIAL CONTRACTOR
 CERTIFIED AFTER 1973 SHALL ACT AS, HOLD HIMSELF OUT TO
 BE, OR ADVERTISE HIMSELF TO BE A ROOFING CONTRACTOR
 UNLESS HE IS CERTIFIED OR REGISTERED AS A ROOFING
 CONTRACTOR.
  
 THE FLAT ROOF AND ASSOCIATED NOA'S WILL REQUIRE EITHER
 A REGISTER OR CERTIFIED ROOFING CONTRACTOR TO APPLY AND
 RECEIVE A ROOFING PERMIT.
  
 THE NOA SUBMITTED WITH ENHANCED FASTENING REVIEWED:
 NOA 09-0224.01
 GAF CORP PAGES 29-30, SYSTEM TYPE:E2
 DESIGN PRESSURE -60 PSF
 EXPOSURE : C
 ATLANTIC & CARIBBEAN ROOFING CONSULTING, LLC ENHANCED
 FASTENING P2=71.68 & P3 -101.2.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-11 Cont ID  
Sent By jwitmer Date 2009-08-11 Time 09:48 Rev Time 0.77
Received By jwitmer Date 2009-08-11 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By jwitmer Date 2009-07-07 Time 12:50 Rev Time 0.55
Received By jwitmer Date 2009-07-07 Time 12:11 Sent To  
Notes
2009-07-07 12:34:04BUILDING PLAN REVIEW
 PERMIT: 09060129
 ADD: 8020 S DIXIE HWY
 CONT: FERGUSON CONTRACTING CORP OF SOUTH FL
 TEL: (561)746-3300
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, PLEASE UPDATE PLANS
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLANS WILL NEED TO INDICATE WIND DESIGN INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLEASE INDICATE COMPLIANCE WITH : (19) ASSEMBLY
 AREAS. A) ALL PUBLIC FOOD SERVICE ESTABLISHMENTS, ALL
 ESTABLISHMENTS LICENSED UNDER THE BEVERAGE LAW FOR
 CONSUMPTION ON THE PREMISES, AND PLACES OF ASSEMBLY
 WITH FIXED SEATING SHALL PROVIDE ACCESSIBLE SEATING OR
 SPACES FOR SEATING WHICH COMPLY WITH SECTIONS
 11-4.33.2, 11-4.33.3, AND 11-4.33.4 AND IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS: FOR THE FIRST 100
 SEATS, ACCESSIBLE AND USABLE SPACES SHALL BE PROVIDED
 CONSISTENT WITH THE FOLLOWING TABLE:1 TO 25 / 1
 REQUIRED WHEELCHAIR LOCATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-11 Cont ID  
Sent By dpalmer Date 2009-08-11 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2009-08-11 Time 10:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-30 Cont ID  
Sent By dpalmer Date 2009-06-30 Time 17:02 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 16:59 Sent To  
Notes
2009-06-30 17:02:11 
  
  
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT PLANS SHOWING MINIMUM DESIGNS
 AND INSTALLATIONS PER CODES WHICH ARE REQUIRED TO BE
 REFLECTED ON PLANS.
 THE INCORRECT CODES ARE STATED. PLANS INDICATE THE
 PREVIOUS 2004 FBC WHICH HAS NOT BEEN AN ADOPTED CODE
 SINCE MARCH 1ST, 2009.
 PLANS SHOULD REFLECT THE FOLLOWING CODES COORDINATION
 BETWEEN PLANS IS NEED. ELECTRICAL PLANS STATE DIFFERENT
 CODES FROM BUILDING.
 PLANS REFERENCE 2002 NFPA-72, WILL THERE BE ANY WORK
 PER THIS CODE?
  
 2007 FBC WITH 2009 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
  
 2) NOTE: PLEASE SEE FBC 13-415.AB.5 FOR MINIMUM
 LIGHTING PERFORMANCE CALCULATIONS. FIXTURES NEED TO BE
 COMPLETE AT THIS TIME. THESE MAY ALWAYS BE REVISED AT A
 LATER DATE.
  
 3) NOTE: PLEASE SEE FBC 13-415.AB.1, .1.4 FOR EXTERIOR
 LIGHTING CONTROLS.
  
 4) NOTE: PLEASE INDICATE SIGN CIRCUIT PER 600.5
  
 5) NOTE: PLEASE SEE NFPA-96 FOR ANY SHUT DOWN OF
 ELECTRICAL UNDER HOOD, NEW OR EXISTING? PANEL DOES NOT
 INDICATE ANY SHUNT TYPE BREAKERS.
  
 6) NOTE: PLEASE INDICATE NEW OR EXISTING WP GFI FOR A/C
 EQUIPMENT LOCATIONS PER 210.63,210.8B3
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-12 Cont ID  
Sent By mawillia Date 2009-08-12 Time 11:53 Rev Time 0.00
Received By mawillia Date 2009-08-12 Time 11:25 Sent To B
Notes
2009-08-12 11:53:36*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS WERE STAMPED, INITIALED,
 AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-09 Cont ID  
Sent By mawillia Date 2009-07-09 Time 12:59 Rev Time 0.00
Received By mawillia Date 2009-07-09 Time 12:09 Sent To  
Notes
2009-07-09 12:42:47*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA 101,
 LIFE SAFETY CODE, SHALL BE REFERENCED. AMEND REFERNCE
 TO THE 2003 EDITION AS LISTED ON A1.0 AND E1 SHEETS.
  
 3. ON THE EXTERIOR ELEVATION WHICH FRONTS SOUTH DIXIE
 HIGHWAY, DISPLAY/SHOW THE BUILDING'S ADDRESS NUMBERS.
 AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO
 LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" IN
 WIDTH/STROKE.
  
 4. SHOW THE LOCATION OF RATED FIRE EXTINGUISHER(S)
 WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5. ON SHEET A1.0, ELIMINATE REFERENCE TO NFPA 72
 (NATIONAL FIRE ALARM CODE) IF BUILDING ISN'T EQUIPPED
 WITH A FIRE ALARM SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 14:11 Rev Time 0.00
Received By kstevens Date 2009-09-21 Time 14:11 Sent To  
Notes
2009-09-21 14:11:49REVISION OK -- SHT P1.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 16:48 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 16:48 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 12:54 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 16:36 Sent To  
Notes
2009-07-01 13:07:33DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQURIED FOR THE
 SEPARATE GAS PERMIT:
  
 1. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- PLANS SHOW 2
 PSI AT METER BUT NOTES INDICATED SIZED PER .5 PSI
 TABLE. PLEASE CLARIFY.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2. -- SUBMIT MANUF SHEETS FOR NEW TANKLESS
 WATER HEATER.
  
 3. PER SECTION 404.8 METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE
 PROTECTED IN AN APPROVED MANNER. GALVANIZED PIPE IS NOT
 ALLOWED UNDERGROUND UNLESS PER SECTION 404.8.2 THE PIPE
 PROTECTIVE COATINGS AND WRAPPINGS SHALL BE APPROVED FOR
 THE APPLICATION AND SHALL BE FACTORY APPLIED. PLEASE
 INDICATE METHOD OF PIPE PROTECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-20 Cont ID  
Sent By btrobaug Date 2009-10-20 Time 15:35 Rev Time 0.00
Received By btrobaug Date 2009-10-20 Time 15:33 Sent To  
Notes
2009-10-20 15:35:37TO JIM'S DESK./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2009-07-27 Cont ID  
Sent By btrobaug Date 2009-07-27 Time 10:25 Rev Time 0.00
Received By btrobaug Date 2009-07-27 Time 10:25 Sent To  
Notes
2009-07-27 10:25:36B 18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-09 Cont ID  
Sent By mawillia Date 2009-07-09 Time 12:59 Rev Time 0.00
Received By mawillia Date 2009-06-08 Time 13:27 Sent To  
Notes
2009-06-08 13:27:50TO C32

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-08-03 Cont ID  
Sent By rkussner Date 2009-08-03 Time 15:49 Rev Time 0.00
Received By rkussner Date 2009-08-03 Time 15:49 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By rkussner Date 2009-06-17 Time 13:43 Rev Time 0.00
Received By rkussner Date 2009-06-17 Time 13:43 Sent To  
Notes
2009-06-17 15:38:45***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-443 (C)(2), VEHICULAR USE
 AREAS SHALL BE SCREENED FROM THOROUGHFARES AND
 RESIDENTIAL USES AND DISTRICT BY A LANDSCAPE BUFFER AT
 LEAST FIVE FEET IN WIDTH. TREES SHALL BE PLANTED AT
 30-FOOT INTERVALS AND HEDGES SHALL BE PLANTED AT
 TWO-FOOT INTERVALS FOR EACH REQUIRED LANDSCAPE BUFFER.
 THE WIDTH OF THE BUFFER ALONG THE EAST AND NORTH SIDES
 OF THE SITE DO NOT MEET THIS REQUIREMENT. THE PARKING
 STALL ON THE NORTH SIDE OF THE BUILDING COULD BE
 LIMITED TO 18 FEET IN LENGTH WITH THE BALANCE OF THE
 PAVEMENT BEING REMOVED AND THE AREA CONVERTED INTO
 GREEN SPACE. THIS WILL REDUCE THE NONCONFORMITY.
  
 2. PURSUANT TO SECTION 94-443 (C)(3), OFF-STREET
 PARKING LOTS CONTAINING AT LEAST 12 INTERIOR PARKING
 SPACES SHALL CONTAIN LANDSCAPE AREAS. THE TOTAL SIZE OF
 SUCH LANDCAPED AREAS SHALL BE EQUAL TO TEN SQUARE FEET
 FOR EACH PARKING SPACE AND SHALL BE PROVIDED WITHIN THE
 INTERIOR OF AN OFF-STREET PAKRING AREA. LANDSCAPE AREAS
 SHALL CONTAIN AT LEAST ONE SHADE OR FLOWERING TREE FOR
 EACH 100 SQUARE FEET OF REQUIRED LANDSCAPED AREA.
  
 3. A 5 X 24 FOOT TURNAROUND SHALL BE PROVIDED FOR
 DEAD-END PARKING LOTS. THE WIDTH OF THE PARKING STALLS
 COULD BE REDUCED TO 81/2 FEET IN WIDTH FROM 9 FEET TO
 PICK UP SOME ADDITIONAL AREA. THE NEW PLANTER ON THE
 NORTH END OF THE EAST PARKING ROW COULD BE REDUCED IN
 WIDTH TO FIVE FEET. IF THE PARKING STALLS WERE REDUCED
 IN WIDTH AS WELL AS THE LANDSCAPE ISLAND, AN ADDITIOANL
 PARKING STALL COULD BE ADDED AND THERE WOULD BE ENOUGH
 SPACE FOR THE TURN-AROUND.
  
 4. A TYPICAL HANDICAP SPACE IS 12 FEET X 18 FEET WITH A
 5 FOOT X 18 FOOT MANEUVERING AREA. NO MANEURVEING AREA
 HAS BEEN PROVIDED FOR THE HANDICAP SPACE. IF AN
 ADDITIONAL SPACE IS ADDED TO THE EAST PARKING ROW, THEN
 ONE SPACE COULD BE LOST ON THE WEST PARKING ROW TO
 ALLOW FOR THE MANEUVERING ARE AND ADDTIONAL
 LANDSCAPING.
  
 5. THE NEW RAMP AND APRON ON THE EAST SIDE OF THE
 BUILDING LIMITS THE REQUIRED 24 FOOT BACK-UP AREA TO 22
 FEET. THE 24 FEET MUST BE MAINTAINED.
  
 6. THE DUMPSTER IS UNDERSIZED. BECAUSE IT MUST BE
 REBUILT, IT SHOULD BE REBUILT TO CITY STANDARDS. ALSO,
 THERE IS A GATE THAT CLOSES OFF THE PARKING LOT. HOW IS
 THE DUMPSTER GOING TO BE ACCESSED IF THE GATE ON THE
 PARKING LOT IS CLOSED?
  
 7. THERE IS A UTILITY EASEMENT ALONG THE EAST AND SOUTH
 SIDES OF THE PROPERTY. THE APPLICANT SHALL OBTAIN
 WRITTEN AUTHORZATION FROM THE EASEMENT HOLDER TO PLANT
 WITHIN THOSE EASEMENTS.
  
 8. ALL PROHIBITED PLANT SPECIES SHALL BE REMOVED FROM
 THE SITE, INCLUDING THE RIGHT-OF-WAY AND THE CANAL
 EMBANKMENT. THE CANAL BANK SHALL BE STRIPPED OF TREES
 AND SHRUBS WITH SOD AND IRRIGATION INSTALLED.
  
 9. PLEASE PROVIDE A CROSS-SECTION OF THE SLOPE WITH
 LANDSCAPING AND IMPROVEMENTS SHOWN FROM THE PARKING LOT
 TO THE WATER'S EDGE OF THE CANAL.
  
 10. PURSUANT TO SECTION 94-443 (C)(5)(A), LANDSCAPE
 AREAS SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE
 CHARACTERIZED AS "TYPE D".
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-11-02 Cont ID  
Sent By kstevens Date 2009-11-02 Time 14:55 Rev Time 0.00
Received By kstevens Date 2009-11-02 Time 14:55 Sent To  
Notes
2009-11-02 14:56:40REVISION OK -- SHT P1.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-21 Cont ID  
Sent By kstevens Date 2009-09-21 Time 14:12 Rev Time 0.00
Received By kstevens Date 2009-09-21 Time 14:12 Sent To  
Notes
2009-09-21 14:12:19REVISION OK -- SHT P1.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 16:49 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 16:49 Sent To  
Notes
2009-08-07 16:50:07A LICENSED PLUMBING CONTRACTOR IS REQUIRED TO INSTALL
 THE BACKFLOW FOR THE IRRIGATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 13:08 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 16:37 Sent To  
Notes
2009-07-01 13:19:04DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHT P1 THE WATER ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE FLOOR PLAN SHOWS ONLY COLD
 WATER TO THE MOP SINK AND THE HOSE BIBB LINE CONNECTING
 BY THE ICE MAKER. SECTION 106.1.1 PLEASE CORRELATE. --
 ALSO THE HOSE BIBB REQUIRES A SHUT OFF VALVE ON THE
 SUPPLY LINE TO THE HOSE BIBB. SECTION 606.2(2).
  
 2. SHT P1 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN FOR THE FLOOR DRAIN DOWNSTREAM OF THE MOP
 SINK. PLEASE CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-08-03 Cont ID  
Sent By kdfreema Date 2009-08-03 Time 09:11 Rev Time 0.00
Received By kdfreema Date 2009-08-03 Time 09:11 Sent To  
Notes
2009-08-03 09:14:00***PROVISO***
  
 TYPE D CURBING SHALL BE INSTALLED AS NOTED ON THE SITE
 PLAN BY YELLOW HIGHLIGHTS.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, 561-822-1435 OR
 [email protected] WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By kdfreema Date 2009-06-18 Time 08:59 Rev Time 0.00
Received By kdfreema Date 2009-06-18 Time 08:59 Sent To  
Notes
2009-06-18 10:25:43***FAILED***
  
 1. WAS THE SIGN AT THE NW CORNER OF THE SITE
 CONSTRUCTED WITH A PERMIT? IF SO, IT MAY REMAIN, IF
 NOT, IT SHALL BE RELOCATED TO COMPLY WITH THE
 REQUIREMENTS OF SEC. 94-408(A)(2).
  
 2. ARE THE AWNING AREAS BEING REDUCED ALONG WITH THE
 DECK AREAS? THE PLANS ARE UNCLEAR IN THAT RESPECT. THE
 SITE PLAN DOES NOT INDICATE THE MAXIMUM EXTENT OF THE
 AWNINGS AND THE DEMOLITION PLAN IS NOT SPECIFIC AS TO
 WHAT WILL HAPPEN TO THEM BEYOND REFURBISHMENT. PLEASE
 NOTE THAT AWNINGS MAY NOT ENCROACH MORE THAN FOUR FEET
 INTO A REQUIRED SETBACK AND BE SUPPORTED BY MEANS OTHER
 THAN ATTACHMENT TO A BUILDING.
  
 3. THE EXISTING DUMPSTER ENCLOSURE DOES NOT MEET THE
 MINIMUM DIMENSIONAL REQUIREMENTS. UNLESS APPROVED TO
 REMAIN BY ENGINEERING SERVICES, IT SHOULD BE REPLACED
 WITH A CODE-COMPLIANT DUMPSTER ENCLOSURE IF SPACE
 EXISTS FOR IT TO BE ACCOMODATED. I'VE ATTACHED A
 DIAGRAM TO THE HARD COPY OF THESE COMMENTS FOR YOUR
 USE.
  
 4. THE PROPOSED ON-STREET LOADING ZONE DOES NOT MEET
 THE MINIMUM DIMENSIONAL REQUIREMENTS OF 10 FEET BY 20
 FEET. IT SHOULD BE REMOVED FROM THE PLAN.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1458
 OR [email protected] QUESTIONS OR COMMENTS.