Plan Review Details - Permit 09060113
Plan Review Stops For Permit 09060113
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By jwitmer Date 2009-10-01 Time 11:56 Rev Time 0.20
Received By jwitmer Date 2009-10-01 Time 11:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-06 Cont ID  
Sent By jwitmer Date 2009-07-06 Time 16:35 Rev Time 0.30
Received By jwitmer Date 2009-07-06 Time 16:19 Sent To  
Notes
2009-07-06 16:20:29BUILDING PLAN REVIEW
 PERMIT: 09060113
 ADD: 828SOUTHERN BLVD
 CONT: TITAN PROPANE
 TEL: (561)499-1229
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) MISSING WIND DESIGN CRITERIA: THE FOLLOWING I 2007
 FBC 1609.1.1 & CHAPTER 35 REFERENECED STANDARDS
 RECOGNIZES ASCE 7-05 . ALSO 1603.1.4 WIND DESIGN DATA.
 NFORMATION RELATED TO WIND LOADS SHALL BE SHOWN.
 1603.1.4 WIND DESIGN DATA.
 2A) BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B) WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C) WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D) THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2E) COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-30 Cont ID  
Sent By dpalmer Date 2009-09-30 Time 16:48 Rev Time 0.00
Received By dpalmer Date 2009-09-30 Time 16:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-26 Cont ID  
Sent By dpalmer Date 2009-06-26 Time 08:48 Rev Time 0.00
Received By dpalmer Date 2009-06-26 Time 08:48 Sent To  
Notes
2009-06-26 08:48:21 
 ** DENIED PLANS **
  
 *** STORES #50, 319, AND 651
  
 *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION
 NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE
 COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE
 OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT
 WHICH IS PERMANENTLY INSTALLED AND DESIGN COST. EVEN IF
 ANY OF THESE ARE OWNER SUPPLIED. THE VALUE SUBMITTED IS
 LOW FOR THE COMPLETE SCOPE OF WORK AS SHOWN.
 THE VALUE ON THE BASE BUILDING/REMODEL SCOPE OF WORK
 WAS NOT ADJUSTED EVEN THOUGH THE SCOPE OF WORK WAS
 SUBSTANTIALLY INCREASED.
 FBC 108.3
  
 2) NOTE: PLEASE SEE THE COVER SHEET FOR THE SUBMITTED
 PROJECT WHICH PROVIDES A LIST OF ALL SHEETS SUBMITTED.
 THE E-1, ELECTRICAL RISER SHEET IS CLEARLY STATED
 HOWEVER NO E-1 SHEET WAS SUBMITTED. THIS WAS GONE OVER
 SPECIFICALLY IN PREVIOUS MEETINGS THAT EACH PERMITTED
 SCOPE OF WORK SET OF PLANS NEEDS TO CONTAIN THE MINIMUM
 SHEETS FOR RECORD PLANS.
 PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON
 PLANS. THE ONLY SHEET THAT HAS ANY CODE REFERENCES IS
 THE P SHEET.
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-110
  
 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE MINIMUM
 RUN TIMES FOR EMERGENCY LIFE SAFETY SYSTEMS BACK UP PER
 NFPA-101 7.8, 7.9. THIS SHOULD BE A NOTE ON THE
 E-SHEETS FOR LIGHTING ALSO.
 PLUMBING SHEETS DO CONTAIN THE NOTE FOR THE 14HRS WHICH
 IS OK.
  
 4) NOTE: PLEASE BE SURE TO PROVIDE ELEVATION OF THE
 GENERATOR FOR ANY AREAS IN WHICH THE GENERATOR MAY BE
 LOCATED IN A FLOOD ZONE A. PLEASE SEE CHAPTER 7 OF
 NFPA-110 FOR LOCATIONS. PLEASE SEE 7.2.3 FOR HEIGHTS.
 NOT ALL STORE LOCATIONS ARE IN FLOOD ZONES. PLEASE BE
 SURE THE ELEVATION FOR 100YEAR STORM OR SLOSH CHARTS
 ARE INDICATED.
  
 5) NOTE: PLEASE SEE NFPA-110 7.11.4. LIGHTNING
 PROTECTION FOR UNITS EPS UNITS LOCATED OUTSIDE. THE
 ADOPTED APPLICABLE STANDARD IS NFPA-780, 2003.
  
 6) NOTE: PLEASE BE SURE TO INCLUDE CIRCUITS AND PANEL
 SCHEDULE FOR ITEMS SUCH AS ANY BLOCK HEATER, BATTERY
 CHARGER ETC.
 408.4, 240.4,310.16 ETC NEC. SECTION 7.12 OF NFPA-110.
  
 7) NOTE: PLEASE SEE SECTION 7.9 OF NFPA-110.
 PLEASE ALSO BE SURE TO SEE SECTION 7.9.3.1. THIS IS A
 COMMON ITEM IN WHICH INSPECTIONS AND/OR INSTALLATIONS
 ARE FAILED DUE TO CHANGES MADE. THE PLANS STATE THE
 BLACK STEEL, HOWEVER PLEASE BE SURE THIS IS NOT
 ADJUSTED IN FIELD.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-08 Cont ID  
Sent By mcarsill Date 2009-10-08 Time 11:35 Rev Time 0.00
Received By mcarsill Date 2009-10-08 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-24 Cont ID  
Sent By mawillia Date 2009-07-24 Time 11:11 Rev Time 0.00
Received By mawillia Date 2009-07-24 Time 11:10 Sent To  
Notes
2009-07-24 11:13:51*****DENIED*****
  
 SEE COMMENTS WHICH WERE MISTAKENLY ENTERED UNDER THE
 FUEL REVIEW.

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status N Date 2009-10-08 Cont ID  
Sent By lmartine Date 2009-10-08 Time 14:43 Rev Time 0.00
Received By lmartine Date 2009-10-08 Time 14:43 Sent To  
Notes
2009-10-08 14:45:42SEE FIRE APPROVAL FROM CARSILLO, DATED 10/8/09

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By mcarsill Date 2009-07-20 Time 11:19 Rev Time 0.00
Received By mcarsill Date 2009-07-20 Time 11:15 Sent To  
Notes
2009-07-20 11:19:24PERMIT APPLICATION INDICATED "INSTALLING GENERATOR"
  
 1. PROPER LABELS OR SIGNS SHALL BE PROVIDED FOR THE NEW
 LP FUEL TANK. THESE SHALL INCLUDE PRODUCT NAME AND NO
 SMOING OR OPEN FLAME.
  
 2. SUITABLE DEVICES SHALL BE PROVIDED TO PROTECT THE
 TANK FROM MECHANICAL DAMAGE.
  
 3. NO CODE REFERENCES PROVIDED ON THE DRAWINGS PROVIDED
 BY PBS&J.
  
 4. WHAT SYSTEMS OR DEVICES WILL THE GENERATOR SUPPLY
 POWER TO AND FOR HOW LONG.
  
 5. ALL ELECTRICAL WORK SHALL COMPLY WITH NFPA 70, THE
 NATIONAL ELECTRICAL CODE.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 12:38 Rev Time 0.00
Received By kstevens Date 2009-09-28 Time 12:27 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By kstevens Date 2009-06-29 Time 13:21 Rev Time 0.00
Received By kstevens Date 2009-06-29 Time 13:21 Sent To  
Notes
2009-06-29 13:23:36DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
 FBC-2007 CHAPTER 1
  
 1. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE CORRESPONDING LENGHTS ARE
 NOT SUBMITTED.
  
 B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- TO BE VERIFIED WHEN
 COMMENT "A" IS ADDRESSED.
  
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2. - SHEETS SHALL SHOW THE BTU LOAD FOR BOTH
 NATURAL AND LP GAS AT 100% LOAD.
  
 2. SEE COMMENT NUMBER ONE OF THE ELECTRICAL PLAN REVIEW
 CONCERNING THE CALCULATED VALUATION FOR THE PROJECT.
 SECTION 108.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-17 Time 13:10 Rev Time 0.00
Received By lmartine Date 2009-09-17 Time 13:10 Sent To  
Notes
2009-09-22 13:13:16C-10
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-07-24 Time 13:09 Rev Time 0.00
Received By lmartine Date 2009-06-04 Time 15:33 Sent To  
Notes
2009-06-05 15:34:12C-31

Review Stop L LANDSCAPING
Rev No 2 Status N Date 2010-01-20 Cont ID  
Sent By rkussner Date 2010-01-20 Time 16:37 Rev Time 0.00
Received By rkussner Date 2010-01-20 Time 16:37 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2009-09-29 Cont ID  
Sent By rkussner Date 2009-09-29 Time 13:22 Rev Time 0.00
Received By rkussner Date 2009-09-29 Time 11:22 Sent To  
Notes
2009-09-29 13:24:43***LANDSCAPE REVIEW NOT REQUIRED***
  
 A HEDGE IS REQUIRED TO BE PLANTED AROUND THE ENCLOSURE
 BUT BECAUSE OF SITE CONDITIONS, PLANTING IS NOT AN
 OPTION.
  
 ROBERT KUSSNER

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-24 Cont ID  
Sent By jroach Date 2009-09-24 Time 14:08 Rev Time 0.00
Received By jroach Date 2009-09-24 Time 14:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-14 Cont ID  
Sent By jroach Date 2009-07-14 Time 15:35 Rev Time 0.00
Received By jroach Date 2009-07-14 Time 15:35 Sent To  
Notes
2009-07-14 15:42:22ZONING PLAN REVIEW
  
 PERMIT NO.: 09060113
 ADDRESS: 828 SOUTHERN BLVD.
 CONTRACTOR/CONTACT: GARY PLUMMER
 TELEPHONE NO.: 561-4991229
 SCOPE OF REVIEW: INSTALLING GENERATOR.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SITE PLAN
 SHALL BE PROVIDED. THE SURVEY SHALL NOTE THE LOCATION
 OF THE PROPOSED GENERATOR AS WELL AS ALL PROPOSED
 SETBACKS FROM THE ADJACENT PROPERTY LINES.
  
 2) PURSUANT TO SECTION 94-444(B) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS, GENERATORS SHALL NOT
 BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED.
 SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. LANDSCAPING SHALL ALSO BE
 PROVIDED ALONG THE EXTERIOR AND SHALL CONSIST OF
 SHRUBS/HEDGES PLATED AT 2-FOOT INTERVALS. THE PROPOSED
 SCREENING SHALL ENCOMPASS ALL MECHANICAL EQUIPMENT
 (INCLUDING THE GAS TANK) AND SHALL BE SCREENED AT THE
 FULL HEIGHT OF THE GENERATOR.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved