| 2009-06-26 08:48:21 | |
| | ** DENIED PLANS ** |
| | |
| | *** STORES #50, 319, AND 651 |
| | |
| | *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION |
| | NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE |
| | COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE VALUE FOR THE COMPLETE SCOPE |
| | OF WORK SHALL INCLUDE ALL LABOR, MATERIALS, EQUIPMENT |
| | WHICH IS PERMANENTLY INSTALLED AND DESIGN COST. EVEN IF |
| | ANY OF THESE ARE OWNER SUPPLIED. THE VALUE SUBMITTED IS |
| | LOW FOR THE COMPLETE SCOPE OF WORK AS SHOWN. |
| | THE VALUE ON THE BASE BUILDING/REMODEL SCOPE OF WORK |
| | WAS NOT ADJUSTED EVEN THOUGH THE SCOPE OF WORK WAS |
| | SUBSTANTIALLY INCREASED. |
| | FBC 108.3 |
| | |
| | 2) NOTE: PLEASE SEE THE COVER SHEET FOR THE SUBMITTED |
| | PROJECT WHICH PROVIDES A LIST OF ALL SHEETS SUBMITTED. |
| | THE E-1, ELECTRICAL RISER SHEET IS CLEARLY STATED |
| | HOWEVER NO E-1 SHEET WAS SUBMITTED. THIS WAS GONE OVER |
| | SPECIFICALLY IN PREVIOUS MEETINGS THAT EACH PERMITTED |
| | SCOPE OF WORK SET OF PLANS NEEDS TO CONTAIN THE MINIMUM |
| | SHEETS FOR RECORD PLANS. |
| | PLEASE BE SURE THE FOLLOWING CODES ARE REFLECTED ON |
| | PLANS. THE ONLY SHEET THAT HAS ANY CODE REFERENCES IS |
| | THE P SHEET. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE MINIMUM |
| | RUN TIMES FOR EMERGENCY LIFE SAFETY SYSTEMS BACK UP PER |
| | NFPA-101 7.8, 7.9. THIS SHOULD BE A NOTE ON THE |
| | E-SHEETS FOR LIGHTING ALSO. |
| | PLUMBING SHEETS DO CONTAIN THE NOTE FOR THE 14HRS WHICH |
| | IS OK. |
| | |
| | 4) NOTE: PLEASE BE SURE TO PROVIDE ELEVATION OF THE |
| | GENERATOR FOR ANY AREAS IN WHICH THE GENERATOR MAY BE |
| | LOCATED IN A FLOOD ZONE A. PLEASE SEE CHAPTER 7 OF |
| | NFPA-110 FOR LOCATIONS. PLEASE SEE 7.2.3 FOR HEIGHTS. |
| | NOT ALL STORE LOCATIONS ARE IN FLOOD ZONES. PLEASE BE |
| | SURE THE ELEVATION FOR 100YEAR STORM OR SLOSH CHARTS |
| | ARE INDICATED. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-110 7.11.4. LIGHTNING |
| | PROTECTION FOR UNITS EPS UNITS LOCATED OUTSIDE. THE |
| | ADOPTED APPLICABLE STANDARD IS NFPA-780, 2003. |
| | |
| | 6) NOTE: PLEASE BE SURE TO INCLUDE CIRCUITS AND PANEL |
| | SCHEDULE FOR ITEMS SUCH AS ANY BLOCK HEATER, BATTERY |
| | CHARGER ETC. |
| | 408.4, 240.4,310.16 ETC NEC. SECTION 7.12 OF NFPA-110. |
| | |
| | 7) NOTE: PLEASE SEE SECTION 7.9 OF NFPA-110. |
| | PLEASE ALSO BE SURE TO SEE SECTION 7.9.3.1. THIS IS A |
| | COMMON ITEM IN WHICH INSPECTIONS AND/OR INSTALLATIONS |
| | ARE FAILED DUE TO CHANGES MADE. THE PLANS STATE THE |
| | BLACK STEEL, HOWEVER PLEASE BE SURE THIS IS NOT |
| | ADJUSTED IN FIELD. |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |