| 2009-06-22 13:49:41 | |
| | |
| | ** DENIED PLANS ** |
| | |
| | *** IT IS IMPORTANT TO KNOW THAT THERE IS INFORMATION |
| | NOT YET SHOWN OR SUBMITTED FOR REVIEW OF MINIMUM CODE |
| | COMPLIANCE. THEREFORE THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING ADDRESS WHICH HAS |
| | BEEN ASSIGNED IS NOTED ON TITLE BLOCKS ALONG WITH OTHER |
| | SUPPORTING DOCUMENTS SUCH AS ENERGY CALCULATIONS. |
| | 8101 OKEECHOBEE BLVD. |
| | FBC 106.5 |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS WELL |
| | AS BUILDING REVIEW COMMENTS WHICH WILL BE FORTHCOMING. |
| | THE SUBMITTED PLANS CONTAIN WORK ON THREE SEPARATE |
| | PARCELS. IF THE THREE ARE NOT LEGALLY JOINED THEN IT IS |
| | NOT PERMITTED TO FEED LIGHTING FOR EXAMPLE LOCATED ON |
| | ANOTHER LEGAL PROPERTY FROM THE MAIN BUILDING. THIS MAY |
| | REQUIRE A UNITY OF TITLE OR ALL WORK ON OTHER PARCELS |
| | SHALL BE UNDER SEPARATE PERMITS AND REQUIRE ANY SITE |
| | ELECTRICAL SUCH AS SITE LIGHTING TO COME FROM MORE THAN |
| | ONE SERVICE. |
| | AS THE INTENT OF SCOPE OF WORK IS NOT YET KNOW SOME |
| | ASPECTS OF REVIEW WILL BE BASED ON THIS BEING ALL ONE |
| | LEGAL PROPERTY. SEE NOTES ON SITE LIGHTING WHICH WILL |
| | BE BELOW. IF UNDER SEPARATE PERMITS REVIEW FOR SOME OF |
| | THESE ITEMS MAY BE DISCARDED. |
| | |
| | 3) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING |
| | CODES AT A MINIMUM. SOME ARE CURRENT AND OK ON |
| | ELECTRICAL PLANS HOWEVER SHEET A.1 CONTAINS REFERENCE |
| | TO THE 2002 NEC/ NFPA-70. PLEASE KNOW AS OF DECEMBER 8, |
| | 2006 THE STATE OF FLORIDA ADOPTED THE 2005 NEC/NFPA-70. |
| | ANOTHER CODE WHICH NEEDS TO BE REFERENCE ON PLAN IS THE |
| | 2003 NFPA-75. |
| | SEE NOTES BELOW WITH RESPECT TO IT ROOM AS NOTED ON |
| | PLANS. |
| | NFPA-75 2003 IS ADOPTED PER FAC 69A-3.012 |
| | ALSO THERE ARE OTHER DESIGNS ON PLANS WITHOUT CODE |
| | REFERENCES SUCH AS THE GENERATOR. ( NFPA-110) |
| | |
| | 2007 FBC W/ 2009 REVISIONS |
| | 2002 NFPA-110 |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2003 NFPA-75 |
| | 2002 NFPA-72 |
| | |
| | ** THESE ARE CODES REQUIRED BY THE ELECTRICAL REVIEW AT |
| | THIS TIME. SOME ARE NOTED AS THEY EXIST ON PLANS. |
| | |
| | |
| | 4) NOTE: LANDSCAPE ARCHITECT: PLEASE SEE FLORIDA |
| | STATUTES 481.319 FOR REQUIRED CERTIFICATE OF |
| | AUTHORIZATION. PLEASE CONFIRM WITH THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. |
| | ** PLEASE ALSO BE SURE TO COORDINATE ALL SITE LIGHTING |
| | WITH THE MEP DESIGN TEAM AND SEE COMMENTS ABOVE WITH |
| | RESPECT TO SEPARATE LEGAL PROPERTIES. THERE ARE |
| | CONFLICTS ON LANDSCAPE PLANS COMPARED TO ELECTRICAL |
| | SHEETS. |
| | |
| | 5) NOTE: PLEASE SUBMIT A COMPLETE SET OF PLANS. THE |
| | PLANS MAKE NOTE AND REFERENCES TO FIRE ALARMS PLANS |
| | HOWEVER NO FA SHEETS COULD BE LOCATED IN THE SUBMITTED |
| | SETS. THE PLANS STATE FIRE ALARM SYSTEM BY OTHERS |
| | HOWEVER IF THE FA IS A REQUIRED SYSTEM THEN THE BASE |
| | DESIGN MUST BE SHOWN AT THIS TIME. |
| | PLEASE SEE FS 633 AS ALL BASE BUILDING PLANS SHOWING |
| | MINIMUM DESIGNS FOR FIRE AND LIFE SAFETY SHALL BE PART |
| | OF THE BASE BUILDING DESIGN INTENT. |
| | |
| | 6) NOTE: AS NOTED FOR COMMENT #4 ABOVE, IF THERE IS A |
| | FIRE ALARM SYSTEM PLEASE BE SURE TO SEE FBC |
| | 11-4.28.1,.2 AND .3 FOR MINIMUM HEIGHTS, LEVELS, |
| | LOCATIONS ETC FOR ADA COMPLIANCE. |
| | |
| | 7) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED ATS. THE GENERATOR WILL BE |
| | UNDER A SEPARATE PERMIT HOWEVER IT IS VERY IMPORTANT TO |
| | SEE COMMENTS BELOW WITH RESPECT TO THE LOCATION OF THE |
| | UNIT AND THE NG LINE IN THE BUILDING. |
| | THE SPECS FOR THE ATS ARE REQUIRED AT THIS TIME AS IT |
| | NOTES BEING SERVICE ENTRANCE RATED AND ONE OF THE |
| | MAINS. THERE WILL BE COMMENTS BELOW WITH RESPECT TO |
| | FEEDERS AND SHUT DOWN OF POWER. |
| | ** IF A PRODUCT IS NOT KNOWN THEN PLEASE PROVIDE SPECS |
| | ON A CODE COMPLIANT ITEM AT THIS TIME. 110.3,90.7, |
| | 230.70,71, ETC |
| | THE PRODUCT MAY ALWAYS BE REVISED AT A LATER DATE. |
| | |
| | 8) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN |
| | COMPLIANCE WITH THE FBC CHAPTER 13. THE FOLLOWING WILL |
| | BE NOTED FOR EXAMPLES OF NONE COMPLIANCE AND IS ** |
| | NOT** ALL POSSIBLE ITEMS. THE INPUT DATE REPORT WILL BE |
| | NOTED AS IDR. |
| | AS THE FIXTURE LEGEND IS NOT YET COMPLETE THERE ARE |
| | ITEMS WHICH CAN NOT BE CONFIRMED AS BEING CODE |
| | COMPLIANT AT THIS TIME. |
| | 13-415.AB.5. PLEASE ALSO NOTE, IT IS NOT PERMITTED TO |
| | USE MORE THAN ONE METHOD FOR CALCULATIONS. |
| | |
| | FOR EXAMPLE: PLEASE COORDINATE ALL EXTERIOR LIGHTING ON |
| | PLANS WITH THE IDR. THE IDR ONLY INDICATES TWO TYPES OF |
| | FIXTURES. THIS IS NOT POSSIBLE WHEN THE PLANS CONTAIN |
| | MANY OTHER FIXTURES. WHERE ARE ALL THE SITE LIGHTING |
| | FIXTURES WHICH ARE SHOWN AS 400W MH? |
| | |
| | FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTS ON THE PLANS |
| | ARE NOTED AS METHOD *B* YET A METHOD *A* FLA-COM WAS |
| | SUBMITTED. THERE IS A LARGE DESIGN INCONSISTENCY. |
| | THE TOTAL WATTAGE ON THE FLA-COM INTERIOR IS IN EXCESS |
| | OF 18,000 WATTS YET THE PLANS STATE THE TOTAL INTERIOR |
| | DESIGN WATTAGE IS LESS THAN 7000WATTS. HOW IS THIS |
| | POSSIBLE? |
| | THE PLANS CONTAIN FIXTURES AND WATTAGE TYPE NOT ON THE |
| | IDR. PLEASE BE SURE TO GO OVER PLANS FOR ALL FIXTURES. |
| | ANOTHER EXAMPLE ON THE INTERIOR LIGHTING IS THE *J* |
| | FIXTURE. THE PLANS AND THE FIXTURE LEGEND CONTAIN |
| | REFERENCES TO THE FUTURE FIXTURE HOWEVER THERE IS NO |
| | ALLOWANCE FIGURED INTO THE SPACE BY SPACE ON PLANS OR |
| | THE IDR OF THE FLA-COM REPORT. |
| | |
| | FOR EXAMPLE: PLEASE SEE THE NOTES BELOW FOR WATER |
| | HEATERS/ LOADS. THE EXAMPLE HOWEVER FOR CHAPTER 13 |
| | COMPLIANCE IS THE FACT THE IDR IS COMPLETELY BLANK |
| | UNDER *PIPING*. THE BUILDING CONTAINS ELECTRICAL HWH |
| | WHICH THEN ALSO CONTAIN PIPING FOR HOT WATER. PLEASE |
| | SEE SECTION 13-411.AB.2. |
| | |
| | ** THESE ARE A FEW EXAMPLES ONLY. THERE ARE OTHERS, |
| | PLEASE GO OVER ALL COMPONENTS AND SEE POSSIBLE COMMENTS |
| | FROM OTHER TRADES FOR ITEMS SUCH AS ROOFING |
| | INSULATIONS. |
| | |
| | 9) NOTE: PLEASE SUBMIT VOLTAGE DROP CALCULATIONS FOR |
| | WORST CASE FEEDERS AND WORST CASE BRANCH CIRCUITS. |
| | PLEASE SEE 13-413.AB.1.1, .1.2 |
| | |
| | 10) NOTE: PLEASE SEE NOTE #2 ON SHEET E3.03 WHICH |
| | STATES CONDUCTORS #10 AND SMALLER SHALL BE THHN AND |
| | LARGER THAN #1 TO BE THWN. PLEASE BE AWARE THAT THE |
| | SITE LIGHTING FOR EXAMPLE INDICATES CONDUCTORS TO BE |
| | #10. DEPENDING ON COMMENT #9 ABOVE THIS MAY CHANGE |
| | HOWEVER BASED ON NOTES AND PANEL SCHEDULE IF #10 AWG |
| | CONDUCTORS ARE INSTALLED TO SITE LIGHTING THE PLANS DO |
| | NOT STATE THEY NEED TO BE THWN. |
| | PLEASE SEE LISTING FOR THHN AND THWN. THE W IS FOR WET |
| | LOCATIONS, ALL UNDERGROUND PIPING AND WIRING TO SITE |
| | LIGHTING IS CONSIDERED A WET LOCATION. THIS IS VERY |
| | SPECIFIC IN THE NEC. |
| | THEREFORE ALL CONDUCTORS INCLUDING THOSE SMALL THAN #10 |
| | IN WET LOCATIONS SHALL BE RATED AS SUCH. THWN IS ONLY |
| | ONE CHOICE. |
| | 110.3, 300.5, 310.9, 310.8B ETC. |
| | |
| | 11) NOTE: PLEASE SUBMIT PHOTO-METRICS SHOWING MINIMUM |
| | LEVELS FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY |
| | CONDITIONS. PLEASE SEE NFPA-101 7.8.1.3 AS THE STAIR |
| | LEVELS NEED TO MEET 10FT CANDLES UNDER NORMAL AND IS |
| | PERMITTED DOWN TO 1FT CANDLE UNDER EMERGENCY |
| | CONDITIONS. |
| | PLEASE KNOW THAT ROOMS SUCH AS THE MAIN ELECTRICAL ROOM |
| | AND ELEVATOR EQUIPMENT ROOM SHALL CONTAIN BATTERY BACK |
| | UP FIXTURES OF SOME KIND. 700.12F, 700.16. |
| | THIS NEEDS TO COORDINATE WITH COMMENT #17 BELOW. |
| | |
| | 12) NOTE: PLEASE SEE NEC AND FBC WHICH BOTH MAKE |
| | REFERENCE TO ASME-17 2004 FOR ELEVATOR CODES. THIS |
| | OFFICE DOES NOT REVIEW FOR CODE COMPLIANCE FOR ASME |
| | HOWEVER IT SHOULD BE NOTED THAT FOR INFORMATION THERE |
| | ARE SOME ITEMS ON PLANS WHICH DO NOT MEET MINIMUM ASME |
| | CODES. THERE WILL BE SOME ITEMS NOTED BELOW IN OTHER |
| | COMMENTS FOR NEC/ FBC REQUIREMENTS HOWEVER THESE ARE |
| | FOR INFORMATION ONLY. |
| | THE INTENT IS TO PROVIDE INFORMATION WHICH MAY HELP TO |
| | NOT DELAY THE PROJECT WHEN IT COMES TIME FOR ELEVATOR |
| | INSPECTIONS. |
| | |
| | ** PLEASE CHECK THE ELEVATOR PIT LIGHTING REQUIREMENTS, |
| | THE SINGLE FIXTURE SHOWN MOST LIKELY DOES NOT GIVE THE |
| | NEW LEVELS REQUIRED FOR FT CANDLES IN PIT. ( 10FT |
| | CANDLES MIN) |
| | ** PLEASE CHECK THE LIGHTING AT SILLS/LANDINGS IN |
| | HALLWAYS, 10FT CANDLES MINIMUM. |
| | ** PLEASE CHECK LIGHTING IN ELEVATOR EQUIPMENT ROOMS. |
| | 19 FT CANDLES MINIMUM. |
| | |
| | 13) NOTE: PLEASE COMPLETE PLANS FOR ALL CIRCUITING. |
| | THERE ARE SOME ITEMS ON PLANS WHICH DO NOT SHOW |
| | CIRCUITING AT THIS TIME. PLEASE SEE CORRIDOR #4, EXIT |
| | SIGN, PLEASE SEE LIGHTING IN ELEVATOR EQUIPMENT ROOM |
| | AND MAIN ELECTRICAL ROOM. |
| | PANELS SCHEDULE SHALL ALSO BE SPECIFIC. MAY NOTA STATE |
| | *LIGHTING OR RECEPTACLES* IN GENERAL. MAY USE ALPHA OR |
| | NUMERIC DESIGNATIONS. IT WOULD BE *LIGHTING |
| | 101,102,103* ETC. |
| | 408.4, 310.16, 220.12,220.42 |
| | THESE ARE A FEW EXAMPLES |
| | |
| | 14) NOTE: PLEASE SEE NEC 620.23 FOR REQUIRED DEDICATED |
| | CIRCUIT FOR ROOM LIGHTING. |
| | |
| | 15) NOTE: PLEASE PROVIDE CLARITY FOR THE SYSTEM WHICH |
| | IS GOING TO FEED THE ELEVATOR EQUIPMENT ROOM. PER FBC |
| | 3006.2 WHICH REQUIRES A DEDICATED SYSTEM. SHEET E1.02 |
| | STATES TO SEE ME1.01 FOR UNIT TO BE FED FROM CONDENSING |
| | UNIT. HOWEVER ME1.01 SHOWS MORE THAN ONE CU. |
| | THE SYSTEM SHALL BE DEDICATED. PANEL SCHEDULE IS NOT |
| | SPECIFIC. |
| | 408.4, 310.16, 220 ETC LOADS AND OTHER ITEMS NEED TO BE |
| | DETERMINED. |
| | FBC 106.1.1, 106.1.2 FOR CLARITY AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 16) NOTE: PLEASE SHOW A SYSTEM IN COMPLIANCE WITH FBC |
| | CHAPTER 13, 13-415.AB.1.1,.1.2, .1.3 AND .1.4. THE |
| | PLANS CONTAIN MANY NOTES THAT A SYSTEM NOTES AS TIMED |
| | SCHEDULING IS TO BE PROVIDED HOWEVER NO SYSTEM IS |
| | SHOWN. |
| | NEED TO SHOW SYSTEM. |
| | NEED TO SHOW ZONES FOR AREAS OVER SQ FT PERMITTED. |
| | NEED TO SHOW SYSTEM FOR EACH FLOOR AS THE CODE DOES NOT |
| | PERMIT A SINGLE CONTROL FEEDING MORE THAN ONE FLOOR. |
| | NEED TO SHOW LOCATIONS OF ALL OVER RIDES AND/OR |
| | ALTERNATE LOCATIONS MEETING EXCEPTIONS FOR PILOT |
| | LIGHTS. |
| | PLEASE BE SURE TO INCLUDE TIME FOR BACK UP OF EXTERIOR |
| | PROGRAMMING ON ASTRONOMICAL TIME CLOCK. |
| | SEE NOTES FOR OTHER FIXTURES WHICH PER PLANS ONLY SHOW |
| | A SINGLE POLE SWITCH FOR CONTROL. BREAK ROOM FOR |
| | EXAMPLE INDICATES SOME SORT OF FIXTURE YET NO CONTROLS |
| | FOR AUTOMATIC SHUT OFF AS REQUIRED PER |
| | 13-415.AB.1.1,.1.3 AND *BREAK ROOMS* UNDER .1.2. |
| | |
| | ** THERE ARE SEVERAL ITEMS WHICH COULD NOT BE REVIEWED |
| | FOR CODE COMPLIANCE. SEE NOTES FOR FIXTURES ALSO. |
| | |
| | 17) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS AND |
| | COMPLETE A FIXTURE LEGEND SHOWING MINIMUM CODE |
| | COMPLIANCE AT THIS TIME. |
| | FOR EXAMPLE: SD FIXTURES ON PLANS YET NOTHING ON |
| | FIXTURE LEGEND. |
| | FOR EXAMPLE: FIXTURE DL IS NOTED AS BEING 208V, YET THE |
| | PLANS INDICATE THIS CIRCUITED TO A 277/480V PANEL. |
| | FOR EXAMPLE: ONE OF THE ITEMS WHICH IS CONFUSING IS THE |
| | *R* IN THE SMALL CIRCLE ON PLANS LOCATED AT MANY OF THE |
| | FIXTURES. THE SYMBOL LEGEND DOES NOT LIST THIS ITEM. |
| | THE *R* IS LOCATED NEXT TO NUMEROUS RECESSED TYPE |
| | FIXTURES SO ONE WOULD ASSUME THAT PERHAPS THIS WAS FOR |
| | RECESSED LIGHTS. HOWEVER PLEASE SEE THE BREAK ROOM FOR |
| | EXAMPLE AS ONE LOCATION WHICH INDICATES LIGHTING |
| | FIXTURES AS *R* WITH NO OTHER DESIGNATION. IS *R* A |
| | FIXTURE TYPE ? OR SOME OTHER DESIGNATION. |
| | REVIEW FOR ITEMS SUCH AS LIGHTING PERFORMANCE |
| | CALCULATIONS, REQUIRED CONTROLS, LOAD CALCULATIONS, |
| | CIRCUITING ETC CAN NOT BE DETERMINED AT THIS TIME. |
| | |
| | ** THERE ARE MORE ITEMS, PLEASE COMPLETE ALL FIXTURES |
| | AND COORDINATE ALL. |
| | |
| | 18) NOTE: PLEASE EXPLAIN HOW THE POWER FROM THE |
| | GENERATOR WILL BE SHUT DOWN IN AN EMERGENCY. THE MAINS |
| | ARE TURNED OFF BY FIRE PERSONNEL, THE GENERATOR WILL |
| | AUTOMATICALLY TURN ON PLACING HOT 277/480V FEEDERS |
| | INSIDE THE BUILDING TO MANY PANELS. |
| | PLEASE KEEP IN MIND THAT ALL DISCONNECTING MEANS SHALL |
| | BE RATED FOR LOAD SERVED PER 230.76,230.79. |
| | PLEASE GO OVER LOCATION OF UNIT WITH ALL TRADES |
| | INCLUDING FIRE MARSHAL. |
| | PLEASE SEE 445.18, AS THE FUEL SOURCE SHALL BE SHUT |
| | DOWN AND IN CLOSE PROXIMITY TO THE MAIN ELECTRICAL |
| | ROOM. PLANS WOULD ALSO CONTAIN THE GAS LINE INSIDE THE |
| | BUILDING. |
| | THERE ARE SEVERAL ITEMS WHICH COULD CREATE A LIFE |
| | SAFETY AND FIRE HAZARD AS THE GENERATOR WOULD STILL RUN |
| | AFTER TURNING OFF MAINS. |
| | ** PLEASE CALL TO GO OVER AND PLEASE CONTACT THE FIRE |
| | MARSHAL. |
| | PLEASE SEE NFPA-110 FOR LOCATIONS PER CHAPTER 7. |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WITH RESPECT |
| | TO THE 100KW GENERATOR SHOWN ON SOME PLANS HOWEVER NO |
| | SPECIFIC STRUCTURAL DETAILS ON ROOF LOADS ETC ARE |
| | SHOWN. |
| | |
| | 19) NOTE: PLEASE BE SURE TO STATE ON PLANS THAT THE |
| | BACK UP SYSTEM PROVIDED IS AN * OPTIONAL STAND-BY |
| | SYSTEM* ONLY. 702, 700, 701 |
| | FBC 106.1.1 FOR CLARITY AND INFORMATION ON PLANS. |
| | |
| | 20) NOTE: PLEASE SEE FBC 1006.1.2 AND NFPA-101 7.8.1.2 |
| | WHICH REQUIRES ALL OCCUPANCY SENSORS TO BE OF FAIL SAFE |
| | TYPE FOR ANY LIGHTING WHICH IS PART OF THE REQUIRED |
| | EGRESS. |
| | THE PLANS SHOW THAT LIGHTING IN AREAS SUCH AS STAIRS |
| | AND OTHER LOCATIONS MAY OR MAY NOT BE THROUGH THE |
| | LIGHTING CONTROL PANEL. WHAT IS THE DESIGN INTENT? |
| | PLEASE SEE 13-415.AB.1 FOR CHAPTER 13 COMPLIANCE AS |
| | WELL AS SECTIONS NOTED ABOVE. |
| | ARE THERE GOING TO BE PROPOSED NIGHT LIGHTS? IF SO |
| | PLEASE SHOW ON PLANS. |
| | PLEASE KEEP IN MIND NOT ALL FIXTURES WILL BE CONSIDERED |
| | NIGHT LIGHTS. |
| | |
| | 21) NOTE: PLEASE SEE 2003 NFPA-75 AND 2005 NEC FOR IT |
| | ROOM. THIS REQUIRES SEPARATION FROM OTHER AREAS. PLANS |
| | SHOW FILE/STORAGE AREA AS PART OF THE SEPARATED AREA. |
| | PLEASE SEE NEC 645.4 FOR REQUIREMENTS OF AN IT ROOM. IF |
| | THIS IS INDEED AS IT ROOM AS DEFINED IN 645.4 AND |
| | NFPA-75 THEN ALL THE ITEMS IN 645.4 ( 1-5) MUST BE MET. |
| | FOR EXAMPLE: 645.10 FOR REQUIRED DISCONNECTING MEANS |
| | FOR ALL ELECTRICAL FEEDING EQUIPMENT ALONG WITH AIR |
| | CONDITIONING EQUIPMENT. |
| | IF THIS IS NOT GOING TO BE AN IT ROOM, THEN NO WIRING |
| | METHODS PER NEC 645 ARE PERMITTED IN THIS LOCATION. |
| | PLEASE PLACE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 22) NOTE: PLEASE SEE FBC 1020.1.1,.1.2 WHICH UNDER THE |
| | 2004 FBC WAS SECTION 1019. OTHER SYSTEMS SUCH AS |
| | SECURITY SYSTEMS WHICH ARE NOTED ON PLANS ARE NOT |
| | PERMITTED IN THE STAIRWAYS. |
| | PLANS INDICATE RECEPTACLES ALONG WITH A NOTE #14 FOR |
| | SECURITY SYSTEM/OTHER DEVICES TO BE LOCATED IN STAIRS. |
| | THIS IS NOT PERMITTED. |
| | ONLY SYSTEMS PERTAINING TO THE STAIR AND EXIT ENCLOSURE |
| | WHICH ARE A REQUIRED SYSTEM. |
| | |
| | 23) NOTE: NOTED, LOW VOLTAGE SYSTEMS SUCH AS PHONE, |
| | CATV, ACCESS CONTROLS ETC SHALL BE UNDER SEPARATE |
| | PERMIT(S) ALONG WITH THE SITE LIGHTING, GENERATOR AND |
| | OTHERS AS NOTED BY TRADES. |
| | |
| | 24) NOTE: PLEASE SEE 250.6,250.24 ETC. THE RISER |
| | INDICATES *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE |
| | FIRST MEANS OF DISCONNECT. THIS IS NOT PERMITTED. AS |
| | THE FIRST MEANS OF DISCONNECT IS REQUIRED TO BE BONDED |
| | TO THE GROUNDED CONDUCTOR, AS SHOWN THIS WOULD PARALLEL |
| | THE NEUTRAL (GROUNDED ) CONDUCTOR THUS CREATING |
| | OBJECTIONABLE CURRENTS. |
| | PLEASE CALL TO GO OVER IF NEEDED. |
| | |
| | 25) NOTE: PLEASE KNOW THAT SIGNED, DATED AND SEALED |
| | WIND LOAD CALCULATIONS WILL BE REQUIRED FOR SITE |
| | LIGHTING POLES. ALL CALCULATIONS SHALL INCLUDE THE EPA |
| | ( EFFECTIVE PROJECTED AREA) OF FIXTURES. |
| | * THIS MAY BE PART OF THE PERMIT FOR SITE LIGHTING. |
| | |
| | 26) NOTE: PLEASE SHOW THE PHOTO-METRIC LEVELS FOR ALL |
| | AREAS SURROUNDING THE ATM ( AUTOMATED TELLER MACHINES) |
| | PER FS 655.962. |
| | |
| | 27) NOTE: PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN |
| | PER 422.13. PLEASE SEE 2005 NEC HANDBOOK AS ELECTRIC |
| | STORAGE TYPE WATER HEATERS ARE NOW CONSIDERED |
| | CONTINUOUS LOADS. THESE SHALL BE FIGURED INTO SERVICES |
| | AND FEEDERS AT 125%. |
| | |
| | 28) NOTE: PLEASE SEE 422.11, 422.13. SECTION 422.13 |
| | REQUIRES THE MINIMUM OVER CURRENT PROTECTION TO BE |
| | FIGURED AT 125%. HOWEVER 422.11 REQUIRES THE MAXIMUM |
| | OVER CURRENT PROTECTION TO BE 150%. |
| | BASED ON THE PANEL SCHEDULES THE WATER HEATERS ARE BOTH |
| | SHOWN AS 4.5KW UNITS ON 277480V PANELS. THE OCP SHOWN |
| | IS TOO HIGH. THE 30AMP OCP WOULD BE OK IF THESE WERE ON |
| | A 208, OR 240V SYSTEM. |
| | |
| | 29) NOTE: PLEASE KNOW: ANY AND ALL PRODUCT APPROVAL AND |
| | SPECS SHOULD CONTAIN *SHOP DRAWING* REVIEW STAMPS ON |
| | THE COVER SHEETS. THE PLANS AND DOCUMENTS ARE SCANNED |
| | FOR FILE STORAGE HOWEVER THE BACK OF SHEETS AND |
| | DOCUMENTS WHICH ARE ESSENTIALLY BLANK ARE NOT SCANNED. |
| | EVEN IF THESE BACK OF DOCUMENTS WERE SCANNED, THE STAMP |
| | AND SIGNATURE WOULD BE ON BLANK SHEETS. |
| | ** PRODUCT APPROVALS |
| | ** SPEC SHEETS |
| | ETC. |
| | |
| | 30) NOTE: PER BUILDING OFFICIAL, ONE SET OR MORE OF |
| | SUBMITTED PLANS/DOCUMENTS MAY BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |