Plan Review Details - Permit 09060085
Plan Review Stops For Permit 09060085
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 19:56 Rev Time 0.00
Received By shill Date 2009-07-22 Time 19:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-30 Cont ID  
Sent By jwitmer Date 2009-06-30 Time 15:00 Rev Time 1.33
Received By jwitmer Date 2009-06-30 Time 12:00 Sent To  
Notes
2009-06-30 15:15:25BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, 2007 EXISTING BUILDING
 CODE WITH 2009 SUPPLEMENTS, PLEASE INDICATE LEVEL OF
 ALTERATION TO BE COMPLETED UNDER THIS PERMIT. 2007
 EXISTING BUILDING CODE 401.4 A DESIGN PROFESSIONAL OR
 OWNER MUST ELECT ONE OR A CPMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTION 403,404 AND 405 OF THIS
 CODE.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 2 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER5,
 TABLE 503, CHPTER 6 & TABLE 601.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 3 (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. SHEET 5 OF 8
 INDICATES A NEW WALL TO BE BUILT AROUND THE KOOLER
 LOCATED NEXT TO THE BAR, BUT NO DETAILS AS TO TYPE OF
 MATERIALS.
  
 4) PLANS INDICATE THE RAISEDF LOOR AREA TO BE REMOVED
 BUT NO INFORMATION IS PROVIDED FOR THE INSTALATION OF
 BAR SEATING. ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 5) SHEET 3 & 4 INDICATE NEW DECO WALL FINISH PLEASE
 PROVIDE FLAME SPREAD AND SMOKE DEVELOPMENT ON THIS
 PRODUCT. SECTION 803.1 AND TABLE 803.5.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-04 Cont ID  
Sent By kconrad Date 2009-06-04 Time 09:34 Rev Time 0.00
Received By kconrad Date 2009-06-04 Time 09:32 Sent To  
Notes
2009-06-04 09:34:34PREINSPECT APPROVED AS STATED. REQUIRE THE SUBMITTAL OF
 PLANS FOR BUILDING/ELECTRICAL AND PLUMBING REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By btrobaug Date 2009-07-22 Time 18:18 Rev Time 0.00
Received By btrobaug Date 2009-07-22 Time 17:08 Sent To  
Notes
2009-07-22 18:19:39PROVISO-ADD 200 AMP BREAKER FOR PANEL "A"./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By dpalmer Date 2009-06-29 Time 16:33 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 16:33 Sent To  
Notes
2009-06-29 16:33:55 
 ** DENIED REVIEW **
  
 ** PLANS SUBMITTED ARE NOT COMPLETE FOR *MINIMUM CODE
 COMPLIANCE*. PLEASE KNOW THERE MAY BE NEW COMMENTS ON
 THE FOLLOWING REVIEW ONCE INFORMATION IS SUBMITTED.
  
 1) NOTE: PLEASE SUBMIT PLANS SHOWING MINIMUM DESIGNS
 AND INSTALLATIONS PER CODES WHICH ARE REQUIRED TO BE
 REFLECTED ON PLANS.
 THE INCORRECT CODES ARE STATED.
 PLANS SHOULD REFLECT THE FOLLOWING CODES AT A MINIMUM
 FOR ELECTRICAL REVIEW.
  
 2007 FBC WITH 2009 REVISIONS
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-72 ( WHERE APPLICABLE)
  
 2) NOTE: PLEASE SUBMIT AND SHOW COMPLIANCE FOR NEW
 LIGHTING CONTROLS BEING INSTALLED FOR MINIMUM
 PRESCRIPTIVE COMPLIANCE UNDER FBC 13-415.AB.1.1,.1.2,
 .1.3.
  
 3) NOTE: PLEASE SHOW COMPLIANCE WITH FBC 13-415.AB.5
 FOR LIGHTING PERFORMANCE CALCULATIONS. PLEASE KNOW THAT
 NEW LIGHTING MAY NOT BE ADDED UNLESS THE EXISTING
 LEVELS WITH NEW CAN BE CONFIRMED.
  
 4) NOTE: RISER IS MISSING METHOD OF EQUIPMENT GROUNDING
 AFTER THE FIRST MEANS OF DISCONNECT. PLEASE ALSO
 INCLUDE NOTE FOR FLOATING NEUTRAL KIT REQUIRED.
 250.6,250.24,250.110, 250.122 ETC
  
 5) NOTE: PLEASE SEE RISER. THE RISER SHOWS THE 200AMP
 PANEL BEING FED FROM THE 400 AMP MLO, HOWEVER THE PANEL
 SCHEDULE DOES NOT INCLUDE ANY SUB FEED FOR THE 200AMP
 PANEL. NO INFORMATION ON A BRANCH BREAKER OR ANY OTHER
 MEANS TO FEED THE NEW SUB PANEL.
 240.4,310.16, 215.5 ETC.
 FBC 106.1.1,106.1.2,106.3.5.1.2
  
 6) NOTE: PLEASE COORDINATE LOCATION OF PROJECT ON ALL
 SHEETS/PLANS AND DOCUMENTS SUBMITTED. SOME SHOW 6901
 OKEECHOBEE BLVD, SOME SHOW 1910 OKEECHOBEE BLVD,
 FAC 61G1-16.004, 61G15-23.002, FBC 106.5
  
 7) NOTE: COVENANT CONSULTING GROUP SHALL INDICATE THEIR
 REQUIRED LICENSING ON PLANS/TITLE BLOCKS PER
 FAC61G15-23.002, FS 471.023.
 DESIGN FIRMS NOT LICENSED UNDER FS 471, 481 SHALL NOT
 DESIGN OR BE PART OF COMMERCIAL BUILDINGS AND DESIGN
 PROJECTS. FS 481.229, 471.003
  
 8) NOTE: AS OF THE DATE OF THIS REVIEW, THE LICENSE FOR
 FIRM LISTED ON TITLE BLOCKS AS GMB ENGINEERING INC IS
 CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION. A PRINT OUT HAS BEEN
 ATTACHED TO REVIEW NOTES WHICH INDICATES THE STATUS AS
 OF 6/29/09, 4:06 PM.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By mawillia Date 2009-07-24 Time 10:12 Rev Time 0.00
Received By mawillia Date 2009-07-24 Time 09:53 Sent To B
Notes
2009-07-24 10:12:23*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS 3, 5, AND 6A WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-17 Cont ID  
Sent By mawillia Date 2009-07-17 Time 11:50 Rev Time 0.00
Received By mawillia Date 2009-07-17 Time 11:06 Sent To  
Notes
2009-07-17 11:18:36*****DENIED*****
  
 1. THE SUBMITTED PLAN SHEETS SHALL BE COORDINATED AND
 INCLUDED AS ONE SET. BE ADVISED THERE IS A SET FOR
 SHEETS 1 OF 8 THRU 8 OF 8, AND SHEETS 6A & 6B OF 10
 THAT HAS BEEN ALSO SUBMITTED.
  
 2. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET. BE ADVISED OF THE DIFFERENT ADDRESS SHOWN
 ON SHEETS 1 THRU 7 FOR THE ESTABLISHMENT AND ANOTHER
 COMPLETELY DIFFERENT NAME AND ADDRESS SHOWN IN SHEET
 8'S TITLE BLOCK.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. SPECIFY THE NEW WALL INTERIOR FINISH MATERIAL IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 14:10 Rev Time 0.00
Received By shill Date 2009-07-22 Time 14:10 Sent To  
Notes
2009-07-22 14:11:16C18 **EXPEDITED REVIEW PER CONTRACTOR REQUEST**

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2009-07-17 Cont ID  
Sent By mawillia Date 2009-07-17 Time 11:06 Rev Time  
Received By mawillia Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status N Date 2009-06-18 Cont ID  
Sent By rkussner Date 2009-06-18 Time 10:28 Rev Time 0.00
Received By rkussner Date 2009-06-18 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-07-16 Cont ID  
Sent By rregueir Date 2009-07-16 Time 11:55 Rev Time 0.00
Received By rregueir Date 2009-07-16 Time 11:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By dwise Date 2009-07-24 Time 16:47 Rev Time 0.00
Received By dwise Date 2009-07-24 Time 16:47 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-06-25 Cont ID  
Sent By kstevens Date 2009-06-25 Time 14:07 Rev Time 0.00
Received By kstevens Date 2009-06-25 Time 14:07 Sent To  
Notes
2009-06-25 14:16:40DENIED
 REFERENCE:
 FBC-2007 WITH 2009 SUPPLEMENTS
 FBC-2007 CHAPTER 1 ADMIN.
 FBC-2007 PLUMBING
  
 1. PLANS AND OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A PERMIT. LOOSE
 SHEETS ARE NOT APPROVED AND SHALL BE BOUND INTO THE
 SETS. SECTION 106.1.
  
 2. SHT 1 OF 8 SHEET INDEX SHALL REFLECT THE SHEETS
 SUBMITTED. PLEASE INCLUDE SHEETS 6A & 6B OF 10 TO SHEET
 INDEX. SECTION 106.1.1
  
 3. ALL SHEETS SHALL SHALL INDICATE THE CORRECT ADDRESS
 OF THE PROJECT IN THE TITLE BLOCKS. SECTIONS 106.1.1 &
 110.1.2(2)
  
 4. THE CODE CYCLE SHALL BE INDICATED ON THE PLANS.
 SECTION 110.1.2(7). THIS IS REQUIRED ON SHEET 6 0F 8
 PLUMBING NOTES #1 WHICH STILL REFERENCES THE STANDARD
 CODE AND SHT 6B OF 10 WHICH INDICATES FBC-2004. ALL
 APPLICATIONS FOR PERMIT ON OR AFTER MARCH 1 2009 SHALL
 BE DESIGNED TO THE CORRECT CODE CYCLE.
  
 3. SHT 6B SANITARY RISER DIAGRAM. FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. FLOOR SINKS OR A HUB
 DRAINS ARE REQUIRED. SECTIONS 802.3 & 802.3.2.
  
 4. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED. SECTION
 106.3.5.1.3(3)(10)(13). SHOW ALL PIPE SIZES, VALVES &
 (WHERE REQUIRED BY SECTION 604.9), WATER HAMMER
 ARRESTORS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  