| 2009-06-03 11:12:12 | BUILDING PLAN REVIEW |
| | PERMIT: 09060067 |
| | ADD: 6882 N JOG RD |
| | CONT:WEST CONSTRUCTION |
| | TEL: (561)248-3868 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 08090593 6880 N. JOG RD. OFFICE BUILDING TYPE II-B |
| | 5,600 SQ FT |
| | 6890 N. JOG RD. S-2 MAINTENANCE BUILDING TYPE II-B |
| | 1,200 SQ FT |
| | 6882 N JOG RD. PAVILION TYPE II-B 685 SQ FT. |
| | |
| | THE BUILDING OFFICIAL HAS REQUESTED THAT 3 SEPERATE |
| | PERMIT APPLICATIONS WITH SEPERATE TRACKING NUMBERS AND |
| | ADDREESSES BE ASIGNED TO ALLOW FOR THE MULTIPLE |
| | INSPECTIONS THAT WILL BE REQUIRED FOR EACH BUILDING, |
| | AND SEPERATE TRACKING OF INSPECTIONS. |
| | |
| | THE TWO SETS OF PLANS AND BACK UP DOCUMENTATION WILL BE |
| | ALL THAT IS NEEDED, THE (MASTER 08090593)) PERMIT |
| | NUMBER WILL HAVE ALL THE REVIEW DOCUMENTATION. |
| | |
| | 1) , 1ST UNDER PERMIT APPLICATION. THE RESPONSE |
| | COMMENTS INDICATE THIS TO BE A PAVILION, TO BE PART OF |
| | THIS PERMIT WE DO NEED INFORMATION AS FAR AS COMPONENTS |
| | AND CLADDING YOU INDICATE THIS IS A PRE-ENGINEERED |
| | CANOPY, EITHER IT HAS GONE THROUGH THE MANUFACTURED |
| | BUILDING PROGRAM WITH THE STATE AND IS APPROVED AS A |
| | MANUFACTURED MODULAR BUILDING PROGRAM WITH STATE |
| | APPROVED PLANS OR IT WILL NEED PRODUCT APPROVALS FOR |
| | THE ROOFING ASSEMBLY. WITHOUT PLANS THIS AREA WILL BE |
| | EXEMPTED FROM THE PERMIT AND PLANS TO BE SUBMITTED |
| | UNDER A SEPERATE PERMIT. |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | YOUR RESPONCE AS TO SECTION 503.1.1 DEALS WITH SQUARE |
| | FOOTAGE OF FIRE AREA AND THERE NOT BEING REQUIREMENTS |
| | FOR RATED WALLS BEING BUILDINGS AND OPENING |
| | PROTECTIVES. ONE ISSUE THAT WE HAVE IS WITH NO PLANS, |
| | NO STRUCTURAL COLUMNS, BEAMS NOR ROOF SHEATHING IS |
| | PROVIDED. THE ROOFING PRODUCT APPROVAL SUBMITTED 2004 |
| | FL 3778-R1 |
| | IS FOR NON-STRUCTURAL ROOF METAL, REQUIRING |
| | SUBSHEATHING DECK. 1507.4.1. |
| | |
| | 2) SHEET S-4 INDICATES A FOOTING TYPE A BUT THE PLANS |
| | ARE LACKING COLUMN AND BEAM INFORMATION, 1609.2.1 PART |
| | OFTHE MAIN WIND FORCE-RESISTING SYSTEM. PLEASE PROVIDE |
| | ADDITONAL INFORMATION, 106.1..2. 106.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | |
| | 3) SHEET A-4 ALSO INDICATES THE ROOFING ASSEMBLY TO BE |
| | A PREMANUFACTRED CANOPY, PLEASE PROVIDE PRODUCT |
| | INFORMATION, TO BE PART OF THIS PERMIT WE DO NEED |
| | INFORMATION AS FAR AS COMPONENTS AND CLADDING YOU |
| | INDICATE THIS IS A PRE-ENGINEERED CANOPY, EITHER IT HAS |
| | GONE THROUGH THE MANUFACTURED BUILDING PROGRAM WITH THE |
| | STATE AND IS APPROVED AS A MANUFACTURED MODULAR |
| | BUILDING PROGRAM WITH STATE APPROVED PLANS OR IT WILL |
| | NEED PRODUCT APPROVALS FOR THE ROOFING ASSEMBLY. |
| | WITHOUT PLANS THIS AREA WILL BE EXEMPTED FROM THE |
| | PERMIT AND PLANS TO BE SUBMITTED UNDER A SEPERATE |
| | PERMIT. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| | BUILDINGS. |
| | |
| | INFORMATIONAL: GENERATOR PAD IS SHOWN ON SHEET SD-1, IS |
| | THIS PAD AND GENERATOR AND ATTACHMENT TO SLAB WILL BE |
| | REVIEWED UNDER A SEPERATE PERMIT. 1609.1.3 ANCHORAGE |
| | AGAINST OVERTURNING, UPLIFT AND SLIDDING. ANCHORAGE |
| | AGAINST OVERTURNING IS NOT THE RESPONSIBILITY OF THE |
| | GENERATOR MANUFACTURER BUT THE DESIGNER OF RECORD. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |
| | |