Plan Review Details - Permit 09060023
Plan Review Stops For Permit 09060023
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-30 Cont ID  
Sent By jwitmer Date 2010-03-30 Time 09:07 Rev Time 0.77
Received By jwitmer Date 2010-03-30 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-01-26 Cont ID  
Sent By jwitmer Date 2010-01-26 Time 11:59 Rev Time 0.50
Received By jwitmer Date 2010-01-26 Time 11:33 Sent To  
Notes
2010-01-26 14:58:31BUILDING PLAN REVIEW
 PERMIT: 09060023
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETERMINED
 TEL: (561)659-2383
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 JAN. 26/2010
  
 PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
  
 1) COMPLIED.
  
 1A) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1.1. COMPLIED. BASIC WIND SPEED (3-SECOND GUST), MILES
 PER HOUR (KM/HR).
  
 1.2. 2ND REQUEST, WIND IMPORTANCE FACTOR, I W , AND
 BUILDING CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1,
 ASCE 7 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE
 7.
 PLEASE REVIEW THE BUILDING CATEGORIES, THIS BUILDING IS
 PART OF THE WATER DISTRIBUTION SYSTEM MAKING THIS A
 BUILDING CATEGORY IV OR A 1.15 IMPORTANCE FACTOR (TABLE
 6-1).
  
 1.3. COMPLIED. WIND EXPOSURE, IF MORE THAN ONE WIND
 EXPOSURE IS UTILIZED, THE WIND EXPOSURE AND APPLICABLE
 WIND DIRECTION SHALL BE INDICATED.
  
 1.4.COMPLIED. THE APPLICABLE ENCLOSURE CLASSIFICATIONS
 AND, IF DESIGNING WITH ASCE 7, INTERNAL PRESSURE
 COEFFICIENT.
  
 1.5. WITH THE 1.15 IMPORTANCE FACTOR THE STATED
 PRESSURES WILL BE LOW. COMPONENTS AND CLADDING. THE
 DESIGN WIND PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE
 USED FOR THE SELECTION OF EXTERIOR COMPONENTS AND
 CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 1B)PATIALLY COMPLIED. WITH THE NEW WIND PRESSURE
 COEFFICIENT PRESSURES WILL NEED TO BE REVIEWED WITH THE
 HIGHER PRESSURES. PROVIDE DOCUMENTATION ON THE WIND
 RESISTANT CURB. COMPONENTS AND CLADDING.1603.1.4(5).
  
 2)) 2ND REQUEST, SHEET M-5 ALSO INDICATES THAT VARIOUS
 EXHAUST DUCTWORK IS BEING DELETED FROM PENETRTING THE
 ROOF, PLANS INDICATE TO PATCH HOLE,. THE RESPONSE
 INDICATES SHEET A1.01 DETAIL 1 WILL LEAVE THE CURBING.
 THE MECHANICAL PLANS MAKES ONE TO THINK THE CURB IS TO
 BE REMOVED! TO PATCH HOLE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By jwitmer Date 2009-06-18 Time 16:20 Rev Time 0.50
Received By jwitmer Date 2009-06-18 Time 15:30 Sent To  
Notes
2009-06-18 16:18:00BUILDING PLAN REVIEW
 PERMIT: 09060023
 ADD: 1009 BANYAN BLVD
 CONT: TO BE DETERMINED
 TEL: (561)659-2383
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
  
 1) SHEET M-5 ROOF TOP UNITS, NOTES INDICATES THAT A
 STRUCTURAL ENGINEER WILL BE EMPLOYED TO VERIFY ROOF
 LOAD CAPACITY AND PROVIDE STRUCTURAL DETAILS FOR
 ADAPTION OF EXISTING ROOF OPENINGS FOR THE NEW ROOF
 CURBS. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 1A) 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 1B) PROVIDE DOCUMENTATION ON THE WIND RESISTANT CURB.
 COMPONENTS AND CLADDING.1603.1.4(5).
  
 2)) SHEET M-5 ALSO INDICATES THAT VARIOUS EXHAUST
 DUCTWORK IS BEING DELETED FROM PENETRTING THE ROOF,
 PLANS INDICATE TO PATCH HOLE, PLEASE PROVIDE DETAILS AS
 TO HOW THIS WILL HAPPEN.
 106.1.2 ADDITIONAL INFORMATION REQUIRED, COMPONENTS AND
 CLADDING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-01 Cont ID  
Sent By dpalmer Date 2010-02-01 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2010-02-01 Time 16:44 Sent To  
Notes
2010-02-01 16:44:43REDLINED 2008 NEC AS THIS WAS APPLIED FOR PERMIT AFTER
 OCTOBER 1ST, 2009

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 14:39 Sent To  
Notes
2009-06-19 14:39:19 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: NO LICENSED CONTRACTOR HAS APPLIED FOR THE
 SCOPE OF WORK UNDER PERMIT APPLICATION. PLANS SUBMITTED
 AS A PLAN REVIEW ONLY.
 PLEASE BE AWARE OF POSSIBLE CODE CHANGES.
  
  
 2) NOTE: PLEASE CLARIFY SCOPE OF WORK. THE PLANS
 SUBMITTED DO NOT INDICATE ANY WORK FOR ELECTRICAL
 EXCEPT FOR SOME NEW A/C UNITS AND WIRING.
 HOWEVER BASED ON THE PRESCRIPTIVE * METHOD B*
 SUBMITTED, THERE IS GOING TO BE NEW LIGHTING IN SEVERAL
 AREAS.
 PLEASE PROVIDE INFORMATION AS A REVIEW CAN NOT BE DONE
 AT THIS TIME AS NO NEW LIGHTING IS SHOWN ON PLANS.
 PLEASE ALSO BE AWARE OF LIGHTING CONTROLS IF NEW.
 13-415.AB.5, 13-415.AB.1.1,.1.2, .1.3, .1.4.
  
 3) NOTE: PLEASE SEE FAC 69A-60.003,.004 AS THE NFPA-101
 AND NFPA-1 AS OF DECEMBER 31ST 2008 IS NOW THE 2006
 EDITION. PLANS STATE 2003.
 PLEASE ALSO BE AWARE OF THE 2009 REVISIONS/GLITCH
 AMENDMENTS TO THE 2007 FBC.
 POSSIBLE 2008 NEC MAY BE ADOPTED IN THE NEAR FUTURE.
 ALL PERMIT APPLICATIONS MUST BE MADE PRIOR TO
 IMPLEMENTATION DATE OR MUST BE UNDER THE 2008 NEC.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-04-06 Cont ID  
Sent By mcarsill Date 2010-04-06 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2010-04-06 Time 09:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-02-09 Cont ID  
Sent By mawillia Date 2010-02-09 Time 13:05 Rev Time 0.00
Received By mawillia Date 2010-02-09 Time 12:13 Sent To  
Notes
2010-02-09 12:17:57*****DENIED*****
  
 THE FOLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET. ONLY NEWLY ADDED SHEET
 A-101 WAS CORRECTED
  
 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE
 SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE
 PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A
 GENERAL FIRE ALARM - IN ADDITION TO FAN SHUT DOWN.
 ADRRESS COMMENT
  
 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO
 REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101
 IS TO BE REFERENCED. ADDRESS COMMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-26 Cont ID  
Sent By mawillia Date 2009-06-26 Time 10:42 Rev Time 0.00
Received By mawillia Date 2009-06-26 Time 10:16 Sent To  
Notes
2009-06-26 10:42:35*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. PROVIDE SEQUENCE OF OPERATION UPON ACTIVATION OF THE
 SMOKE (DUCT) DETECTOR. AS PER WEST PALM BEACH FIRE
 PREVENTION, DUCT SMOKE DETECTOR(S) SHALL INITIATE A
 GENERAL FIRE ALARM - IN ADDITION TO FANN SHUT DOWN.
  
 3. ON SHEET E-2.01, AMEND GENERAL ELECTRICAL NOTE #1 TO
 REFLECT THE 2006 (INSTEAD OF 2003) EDITION OF NFPA 101
 IS TO BE REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 09:07 Rev Time 0.00
Received By shill Date 2010-03-16 Time 09:07 Sent To  
Notes
2010-03-16 09:15:20C6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-02-01 Time   Rev Time 0.00
Received By rmcdouga Date 2010-01-19 Time 08:12 Sent To  
Notes
2010-01-21 08:57:54TO C4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-26 Cont ID  
Sent By mawillia Date 2009-06-26 Time 10:44 Rev Time 0.00
Received By mawillia Date 2009-06-02 Time 10:32 Sent To  
Notes
2009-06-02 10:21:57COMM BOARD #17
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-04-16 Cont ID  
Sent By hmoser Date 2010-04-16 Time 15:31 Rev Time 0.00
Received By hmoser Date 2010-04-16 Time 15:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-02-01 Cont ID  
Sent By rregueir Date 2010-02-01 Time 11:38 Rev Time 0.00
Received By rregueir Date 2010-02-01 Time 11:38 Sent To  
Notes
2010-02-01 11:38:38WIND RESISTANCE DATA PROVIDED. THIS PROVISO HAS BEEN
 ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 08:53 Rev Time 0.00
Received By rregueir Date 2009-06-19 Time 08:52 Sent To  
Notes
2009-06-19 08:54:36REVIEW TO REMAIN IN FAIL STATUS PENDING RECEIPT OF
 PERMIT APPLICATION FROM CONTRACTOR.
  
 **PROVISO**
 PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE OF
 CONDENSING UNIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-09 Cont ID  
Sent By aaponte Date 2009-06-09 Time 15:16 Rev Time 0.00
Received By aaponte Date 2009-06-09 Time 15:16 Sent To  
Notes
***NONE***