Plan Review Details - Permit 09060020
Plan Review Stops For Permit 09060020
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-09-28 Cont ID  
Sent By jnguyen Date 2009-09-28 Time 10:51 Rev Time 0.00
Received By jnguyen Date 2009-09-28 Time 9:47 Sent To  
Notes
2009-09-28 10:44:38I WAS NOT PROVIDED WITH A COPY OF THIS PERMIT NOR THE
 SITE PLAN, BUT CLAY KOHLMEYER (561) 719-3429 CALLED ME
 ON BEHALF OF THE PROPERTY OWNER ON PCN#
 74434306010000160 AT 5601 CORPORATE WAY. HE STATED THAT
 SUITE # 400 IN THE SOUTHWEST STRUCTURE WAS BEING SPLIT
 INTO TWO SEPARATE UNITS & THAT SUITE # 402 NEEDED TO BE
 ASSIGNED. ACCORDING TO THE CITY OF WPB'S ADDRESSING
 POLICY SECTION 1.3:
  
 ONE PRIMARY NUMBER SHALL BE ASSIGNED TO EACH STRUCTURE
 WITH MULTIPLE UNITS EACH UNIT WITHIN THE STRUCTURE
 SHALL BE ASSIGNED A UNIT DESIGNATOR SUCH AS "SUITE".
 ALLOWED UNIT DESIGNATORS INCLUDE APARTMENT (APT)
 NUMBERS FOR APARTMENTS, AND SUITE, BAY, UNIT (STE, OR
 BAY, OR UNIT) NUMBERS FOR COMMERCIAL BUILDINGS. THE
 UNIT DESIGNATOR SHALL BE NUMERIC AND SHALL NOT INCLUDE
 ALPHA OR FRACTIONAL CHARACTERS (I.E., # A OR # 1/2).
 IT WILL BE THE DEVELOPER RESPONSIBILITY TO ASSIGN UNIT
 (DESIGNATORS) ADDRESSES TO ALL UNITS INSIDE THE
 STRUCTURE .THE LIST OF ADDRESSES MUST BE APPROVED BY
 THE SUPPORT SERVICES DEPARTMENT IN CHARGE OF ADDRESSING
 PRIOR TO RELEASE THE CERTIFICATE OF OCCUPANCY.
 EXAMPLES TO ASSIGN UNIT NUMBERS ARE:
 GROUND/FIRST FLOOR: UNIT NUMBERS FROM 100 TO 199, (100
 MAIN ST. # 101, INDICATES THE UNIT ON THE FIRST FLOOR)
 SECOND FLOOR: UNIT NUMBERS FROM 200 TO 299, (100 MAIN
 ST. # 201, INDICATES THE FIRST UNIT ON THE SECOND
 FLOOR)
  
 *THEREFORE, THE DEVELOPER ALSO RESERVES THE RIGHT TO
 CHANGE THE SUITE/UNIT ADDRESSES, AS LONG AS IT CONFORMS
 WITH OUR ADDRESSING POLICIES & GUIDELINES.
  
 AS A RESULT, I NOTIFIED ALL OF THE RELEVANT PARTIES VIA
 (PALM BEACH COUNTY, PAPA, FPL, USPS, ETC.) OF THE NEW
 SUITE ADDRESS OF 5601 CORPORATE WAY # 402. IN
 COMMUNITYPLUS UNDER PCN# 74434306010000160, I CREATED
 THE SEQUENTIAL UNIT RECORD 0022 - 5601 CORPORATE WAY #
 402 & REATTACHED THIS PERMIT RECORD TO IT (PREVIOUSLY
 TIED TO # 400). MR. KOHLMEYER ALSO INFORMED ME THAT THE
 NUMERICAL SUITE ADDRESS LABELS FOR THE SOUTHWEST OFFICE
 BUILDING WAS BEING REARRANGED ACCORDING TO THE PROPERTY
 OWNER'S PREFERENCE. SINCE I WAS NOT PROVIDED WITH THE
 ORIGINAL PERMIT APPLICATION & SITE PLAN, PLEASE MAKE
 THE ADJUSTMENT ON THEM FROM 5601 CORPORATE WAY # 400 TO
 # 402.
  
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-30 Cont ID  
Sent By jwitmer Date 2009-07-30 Time 16:10 Rev Time 0.55
Received By jwitmer Date 2009-07-30 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By jwitmer Date 2009-06-19 Time 14:55 Rev Time 0.55
Received By jwitmer Date 2009-06-19 Time 14:18 Sent To  
Notes
2009-06-19 14:50:06BUILDING PLAN REVIEW
 PERMIT: 09060020
 ADD: 5601 CORPORATE WAY # 400
 CONT: CLAY KOHLMEYER
 TEL: (561)719-3429
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1 NOTES FOR BUILDING TYPE INDICATES TWO
 BUILDING TYPES A II AND V UNPROTECTED/ UNSPRINKLERED
 PLEASE PROVIDE BUILDING TYPE TABLE 503.
  
 2) SHEET A-1 TENANT DEMISSING WALL EXISTING WALL SYMBOL
 INDICATES TO HAVE FIRE WALL RATING OVER EXISTING WALL
 WITH 2 LAYERS OF TYPE X BOARD ON ONE SIDE, PLEASE
 PROVIDE AN ASSEMBLY NUMBER FOR THIS CONFIGURATION.
 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
  
 3) PROVIDE TYPE OF FLEXIBLE FIRE PROOFING TO OCCUR AT
 THE ONE-HOURTENANT SEPERATION WALL AT ROOF DECK LEVEL.
 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE
 TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW
 TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB
 OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED
 FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL
 BE SECURELY ATTACHED THERETO. IF THE PARTITIONS ARE NOT
 CONTINUOUS TO THE SHEATHING, DECK OR SLAB, AND WHERE
 CONSTRUCTED OF COMBUSTIBLE CONSTRUCTION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-13 Cont ID  
Sent By dpalmer Date 2009-08-13 Time 08:08 Rev Time 0.00
Received By dpalmer Date 2009-08-13 Time 08:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-31 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 12:06 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 12:06 Sent To  
Notes
2009-07-31 12:07:22 
  
 ** DENIED 2ND REVIEW **
  
  
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW. PLEASE SUBMIT
 LIGHTING PERFORMANCE CALCULATIONS MEETING MINIMUM
 PRESCRIPTIVE REQUIREMENTS. THE ORIGINAL SUBMITTED
 CALCULATIONS WERE BASED ON METHOD *A* (WHOLE BUILDING)
 WHICH COULD NOT BE USED. THE NOTES STATED FOR NEW
 LIGHTING IN AREAS PER 13-415.AB.5. THERE ARE ONLY TWO
 METHODS OF CALCULATIONS NOW IN THE 2007 FBC W/2009
 REVISIONS. PREVIOUS REVIEW STATED METHOD *A* COULD NOT
 BE USED THIS WOULD LEAVE ONLY METHOD B.
 IT WAS STATED ON PREVIOUS REVIEW THAT IF THERE WERE ANY
 QUESTIONS TO PLEASE CALL THIS REVIEWER. THE RESPONSE
 FROM ARCHITECT STATES TO SEE MECHANICAL CONTRACTOR'S
 RESPONSE TO MECHANICAL REVIEW #4.
 THIS NOTES A CONVERSATION WITH RONALD REGUERIO
 MECHANICAL REVIEWER AND THAT *ENERGY CALCULATIONS* ARE
 NOT REQUIRED. ENERGY CALCULATIONS FOR MECHANICAL AND
 OTHER SYSTEMS MAY NOT BE REQUIRED HOWEVER MINIMUM
 LIGHTING PERFORMANCE CALCULATIONS ARE REQUIRED.
 13-400.0.B.4, 13-415.B, 13-415.B.1.
  
 ** A CALLED WAS PLACED TO ARCHITECT BY THIS REVIEWER TO
 TRY AND GO OVER COMMENT HOWEVER IT WAS NOT RECEIVED AS
 BEING PROACTIVE.
  
 2) NOTE: PLEASE SEE COMMENT #10 FROM PREVIOUS REVIEW.
 NO DEVICES, LOCATIONS, MINIMUMS FOR HEIGHTS OR ANY
 INFORMATION WAS SHOWN ON PLANS. PLEASE SHOW THE MINIMUM
 DEVICES MEETING ADA COMPLIANCE. PLACING A NOTE ON PLANS
 STATING DEVICES MUST MEET THE CODE SECTIONS IS NOT
 SHOWING ANY MINIMUM DESIGN.
 ** PLEASE CALL TO GO OVER. DOES THIS BUILDING CONTAIN
 AN EXISTING FIRE ALARM SYSTEM? IS ONE BEING INSTALLED?
 IF NO SYSTEM IS BEING INSTALLED OR REQUIRED THEN THIS
 NOTE CAN BE REMOVED.
 PLEASE ALSO CONTACT FIRE MARSHAL TO SEE IF REQUIRED.
  
 3) NOTE: MAINS WILL STILL BE REQUIRED TO BE LABLED PER
 230.2E. IE, MAIN ONE OF TWO ETC. THIS COULD BE
 REDLINED.
  
 *** PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER NEW
 BUILDING OFFICIAL.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By dpalmer Date 2009-06-17 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2009-06-17 Time 12:55 Sent To  
Notes
2009-06-17 12:55:47** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES. STATING THE *LATEST EDITION*
 IS NOT ACCEPTABLE.
 FOR EXAMPLE, THE LATEST EDITION OF NFPA-70 NEC WHICH IS
 THE 2008 HAS NOT BEEN ADOPTED AS OF YET ALTHOUGH IT IS
 ALREADY OUT AND AVAILABLE. THE PLANS NEED TO STATE THE
 CODES IN THE DESIGN. SOME ARE SHOWN HOWEVER BE SURE ALL
 ARE SHOWN AS BELOW.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2005 FOR THIS CODE)
 2002 NFPA-72
 2006 NFPA-1
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: A *METHOD A* *WHOLE* BUILDING ENERGY
 CALCULATION WAS SUBMITTED. THE USE OF A WHOLE BUILDING
 CALCULATION WOULD BE JUST THAT, THE WHOLE BUILDING.
 THE CALCULATIONS AS SUBMITTED ARE NOT COMPLETE FOR
 WHOLE BUILDING.
 IN ANY CASE, ONLY NEW BEING INSTALLED NEEDS TO MEET
 PRESCRIPTIVE REQUIREMENTS.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.AB.5
  
 3) NOTE: PLEASE SEE 422.13 AS ALL WATER HEATER LOADS
 SHALL BE FIGURED AT 125%. PLEASE SEE THE 2005 NEC AS
 THIS WAS A CHANGE WHICH WENT INTO AFFECT DECEMBER 8TH
 2006.
  
 4) NOTE: PLEASE LABEL ALL MAINS AS REQUIRED PER 230.2E.
 FOR EXAMPLE: MAIN 1 OF X, 2 OF X ETC.
  
 5) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO
 ROOMS AND AREAS IN WHICH THEY FEED. 408.4. PLEASE SEE
 COMMENTARY UNDER 2005 NEC HANDBOOK.
 ** IF THIS WAS THE ONLY COMMENT THIS COULD HAVE BEEN
 REDLINED.
  
 6) NOTE: PLEASE SHOW CODE COMPLIANCE FOR COMPLETE LOAD
 CALCULATIONS FOR PANEL LA. PANEL LA LOADS DO NOT SEEM
 TO INCLUDE LOADS FROM LB. BASED ON THE SHEETS SUBMITTED
 THE LOADS ARE ALL SHOWN SEPARATE AND THE LOADS AS SHOWN
 EXCEED THE 400AMP SERVICE ENTRANCE CONDUCTORS RATING
 PER 310.16.
 PLEASE SUBMIT AND SHOW COMPLETE LOAD CALCULATIONS FOR
 LA/LC. ( LB IS SHOWN FED FROM LA THEREFORE LB LOAD AS
 SHOWN FOR PANEL SHOULD BE FIGURED INTO THE LA LOAD.
 240.4,310.16, 220.12,220.14,220.42,220.44,ETC
 *** PLEASE KEEP IN MIND COMMENTS #3 ABOVE AS WELL AS
 ALL CONTINUOUS LOADS AT 125% ALONG WITH ANY LARGEST
 MOTOR LOADS.
 215.3,230.42
  
 7) NOTE: PLEASE SEE NOTE #4 ON PLANS WHICH STATES ALL
 LIGHTING CONTROLS SHALL BE PER 13-415.1.ABC.1.1, .1.2.
 THESE CODE SECTIONS HAVE BEEN REVISED UNDER THE NEW
 CODE. PLEASE SEE 13-415.AB.1.1,.1.2, .1.3.
  
 8) NOTE: PLEASE SEE FBC 13-413.AB.2.1, .2.2. PLEASE
 PLACE NOTES ON PLANS ACCORDINGLY. IT WAS CONFIRMED WITH
 THE STATE THAT THE VERBIAGE IN THE CODE IS THE INTENDED
 WORDING TO BE ON PLANS.
  
 9) NOTE: PLEASE PLACE NOTE FOR FIRE ALARM PANEL BRANCH
 CIRCUIT. THE BREAKER SHALL BE OF A LOCK ON/OFF TYPE
 BREAKER WHICH MEANS THE DEVICE SHALL BE AN INTEGRAL
 PART OF THE BREAKER. THE SNAP/CLICK ON TYPE DEVICES IS
 NOT ACCEPTABLE OR LISTED FOR THE PURPOSE. 110.3
 NFPA-72 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND
 CONNECTIONS SHALL BE MECHANICALLY PROTECTED.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 10) NOTE: PLEASE SEE FBC 11-4.28.1, .2, .3 FOR MINIMUM
 DEVICES WHICH NEED TO BE SHOWN FOR ADA COMPLIANCE.
 PLEASE BE SURE TO ALSO SEE THE MINIMUM DEVICE HEIGHTS,
 LEVELS AND LOCATIONS NEED TO BE SHOWN ON PLANS.
 FS633.
 IF EXISTING, PLEASE SHOW LOCATIONS. THIS SPACE IS BEING
 RECONFIGURED FOR NEW TENANT SO THE LOCATIONS NEED TO BE
 VERIFIED.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-08-04 Cont ID  
Sent By mawillia Date 2009-08-04 Time 11:22 Rev Time 0.00
Received By mawillia Date 2009-08-04 Time 11:07 Sent To  
Notes
2009-08-04 11:21:29****PARTIAL APPROVAL*****
  
  
 PLAN SHEETS D-1 AND A-1 WERE STAMPED, INITIALED AND
 DATED; HOWEVER SHEET E-1 IS TO BE FIRE-STAMPED WHEN THE
 ELECTRICAL PLAN EXAMINERS' COMMENTS HAVE BEEN
 SATISFIED. BE ADVISED, EFFECTIVE 12/31/2008, THE 2006
 EDITION OF NFPA 101 (LIFE SAFETY CODE) SHALL BE
 REFERENCED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-06-18 Cont ID  
Sent By mawillia Date 2009-06-18 Time 14:18 Rev Time 0.00
Received By mawillia Date 2009-06-18 Time 13:56 Sent To  
Notes
2009-06-18 14:17:41*****FIRE STAMPING NEEDED*****
  
  
 PLAN SHEETS A-1 AND E-1 TO BE FIRE-STAMPED WHEN THE
 OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN SATISFIED. BE
 ADVISED, EFFECTIVE 12/31/2008, THE 2006 EDITION OF NFPA
 101 (LIFE SAFETY CODE) SHALL BE REFERENCED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-10-16 Cont ID  
Sent By rregueir Date 2009-10-16 Time 11:15 Rev Time 0.00
Received By rregueir Date 2009-10-16 Time 11:14 Sent To M
Notes
2009-10-16 11:15:20PLUMB AND MECH REVISION HAND ROUTED FOR EXPEDITED
 REQUEST. MECH REVIEW COMPLETE, SENT TO KSTEVENS DESK
 FOR REVIEW. RJR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-23 Cont ID  
Sent By lmartine Date 2009-07-23 Time 08:33 Rev Time 0.00
Received By lmartine Date 2009-07-23 Time 08:28 Sent To  
Notes
2009-07-23 08:33:57B-14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By shill Date 2009-06-02 Time 10:57 Sent To PC
Notes
2009-06-02 10:58:08TO B13
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-10-16 Cont ID  
Sent By rregueir Date 2009-10-16 Time 11:13 Rev Time 0.00
Received By rregueir Date 2009-10-16 Time 11:12 Sent To P
Notes
2009-10-16 11:12:58REVISED M-1 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 16:24 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 16:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-06 Cont ID  
Sent By rregueir Date 2009-07-06 Time 15:01 Rev Time 0.00
Received By rregueir Date 2009-07-06 Time 14:47 Sent To PC
Notes
2009-07-06 15:01:04REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE SYSTEM SHALL BE PROVIDED WITH DUCT SMOKE
 DETECTOR IN ACCORDANCE WITH FBC-M 606.2.2.1. CONTROLS
 AND OPERATION SHALL COMPLY WITH FBC-M 606.3 AND 606.4.
  
 2. SHOW LOCATION OF BATHROOM EXHAUST TERMINATIONS IN
 ACCORDANCE WITH FBC-M 401.4 AND FBC-M 501.2.
  
 3. THE SPACE APPEARS TO BE DESIGNED WITH THE CEILING TO
 SERVE AS A RETURN AIR PLENUM. CEILING MOUNTED EXHAUST
 FANS WOULD RESULT IN POSITIVE PRESSURE EXHAUST DUCTS
 PASSING THROUGH THE RETURN AIR PLENUM. EXHAUST DUCTS
 UNDER POSITIVE PRESSURE SHALL NOT PASS THROUGH THE
 PLENUM IN ACCORDANCE WITH FBC-M 601.5.
  
 4. THE VENTILATION SCHEDULE INCLUDED IN THE COOLING
 LOAD CALCULATIONS CALL FOR A MINIMUM OF 50 CFM OF
 EXHAUST IN THE COPY ROOM. NO SUCH EXHAUST IS SHOWN ON
 THE PLANS. PLEASE COORDINATE PLANS WITH THE VENTILATION
 SCHEDULE.
  
 5. THE MECHANICAL PLANS SUBMITTED WERE DESIGNED BY AN
 AIR CONDITIONING CONTRACTOR. THE CONTRACTOR MAY ONLY
 ACT AS THE DESIGNER OF THIS SYSTEM IF THEY ARE ALSO THE
 INSTALLING CONTRACTOR. THIS REVIEW WILL REMAIN IN FAIL
 STATUS PENDING RECEIPT OF A PERMIT APPLICATION FOR THIS
 SCOPE OF WORK FROM NORTH COUNTY COOLING IN ACCORDANCE
 WITH FS 471.003
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-10-19 Cont ID  
Sent By kstevens Date 2009-10-19 Time 17:39 Rev Time 0.00
Received By kstevens Date 2009-10-19 Time 17:39 Sent To  
Notes
2009-10-19 17:40:12REVISION OK -- SHTS A-1 & A-2.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-07 Cont ID  
Sent By kstevens Date 2009-08-07 Time 12:59 Rev Time 0.00
Received By kstevens Date 2009-08-07 Time 12:59 Sent To  
Notes
2009-08-07 13:01:17PASSED/PROVISO:
  
 REVISION REQUIRED.
  
 TOILET ROOM 108 SHALL BE ACCESSIBLE. SECTION
 11-4.1.3(11). -- FLUSH CONTROLS SHALL BE ON THE WIDE
 SIDE OF THE W/C. 11-4.16.5. -- LAV FAUCET SHALL COMPLY
 WITH SECTION 11-4.19.5.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 10:12 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 10:12 Sent To  
Notes
2009-06-17 10:34:19DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-1 SUBMIT A DETAIL FOR THE LOUNGE SINK (113).
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH REQD)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 2. SHT A-1 TOILET ROOM (108) SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.22
 WITH ALL SUBSECTIONS. SECTIONS 11-4.1.3(11) &
 11-4.1.6(1)(B). SHOW CLEAR FLOOR SPACE ON FLOOR PLAN AS
 WELL AS GRAB BARS.
  
 3. SHT A-2 DETAIL 6/A-2 SHOW COMPLIANCE FOR THE
 FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
  
 4. SHT A-2 THE SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN IN TOILET ROOM 108. PLEASE CORRELATE.
 SECTIONS 106.1.1 & 701.1.
  
 5. SHT A-2 PLUMBING NOTES #7 AIR CHAMBERS ARE NOT
 APPROVED. PDI-WH 201.
  
 6. SUBMIT A WATER ISOMETRIC RISER DIAGRAM. SHOW ALL
 PIPE SIZES, VALVES, WATER HAMMER ARRESTORS ETC. SECTION
 106.3.5.1.3(3)(8)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-25 Cont ID  
Sent By kdfreema Date 2009-06-25 Time 09:18 Rev Time 0.00
Received By kdfreema Date 2009-06-25 Time 09:18 Sent To  
Notes
***NONE***