| 2009-06-17 12:55:47 | ** DENIED PLANS * |
| | |
| | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE |
| | FOLLOWING MINIMUM CODES. STATING THE *LATEST EDITION* |
| | IS NOT ACCEPTABLE. |
| | FOR EXAMPLE, THE LATEST EDITION OF NFPA-70 NEC WHICH IS |
| | THE 2008 HAS NOT BEEN ADOPTED AS OF YET ALTHOUGH IT IS |
| | ALREADY OUT AND AVAILABLE. THE PLANS NEED TO STATE THE |
| | CODES IN THE DESIGN. SOME ARE SHOWN HOWEVER BE SURE ALL |
| | ARE SHOWN AS BELOW. |
| | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL |
| | PLANS. |
| | 2007 FBC W/ 2009 AMENDMENTS. |
| | 2006 NFPA-101 ( PLANS STATE 2005 FOR THIS CODE) |
| | 2002 NFPA-72 |
| | 2006 NFPA-1 |
| | |
| | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 |
| | |
| | 2) NOTE: A *METHOD A* *WHOLE* BUILDING ENERGY |
| | CALCULATION WAS SUBMITTED. THE USE OF A WHOLE BUILDING |
| | CALCULATION WOULD BE JUST THAT, THE WHOLE BUILDING. |
| | THE CALCULATIONS AS SUBMITTED ARE NOT COMPLETE FOR |
| | WHOLE BUILDING. |
| | IN ANY CASE, ONLY NEW BEING INSTALLED NEEDS TO MEET |
| | PRESCRIPTIVE REQUIREMENTS. |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER |
| | 13-415.AB.5 |
| | |
| | 3) NOTE: PLEASE SEE 422.13 AS ALL WATER HEATER LOADS |
| | SHALL BE FIGURED AT 125%. PLEASE SEE THE 2005 NEC AS |
| | THIS WAS A CHANGE WHICH WENT INTO AFFECT DECEMBER 8TH |
| | 2006. |
| | |
| | 4) NOTE: PLEASE LABEL ALL MAINS AS REQUIRED PER 230.2E. |
| | FOR EXAMPLE: MAIN 1 OF X, 2 OF X ETC. |
| | |
| | 5) NOTE: PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THEY FEED. 408.4. PLEASE SEE |
| | COMMENTARY UNDER 2005 NEC HANDBOOK. |
| | ** IF THIS WAS THE ONLY COMMENT THIS COULD HAVE BEEN |
| | REDLINED. |
| | |
| | 6) NOTE: PLEASE SHOW CODE COMPLIANCE FOR COMPLETE LOAD |
| | CALCULATIONS FOR PANEL LA. PANEL LA LOADS DO NOT SEEM |
| | TO INCLUDE LOADS FROM LB. BASED ON THE SHEETS SUBMITTED |
| | THE LOADS ARE ALL SHOWN SEPARATE AND THE LOADS AS SHOWN |
| | EXCEED THE 400AMP SERVICE ENTRANCE CONDUCTORS RATING |
| | PER 310.16. |
| | PLEASE SUBMIT AND SHOW COMPLETE LOAD CALCULATIONS FOR |
| | LA/LC. ( LB IS SHOWN FED FROM LA THEREFORE LB LOAD AS |
| | SHOWN FOR PANEL SHOULD BE FIGURED INTO THE LA LOAD. |
| | 240.4,310.16, 220.12,220.14,220.42,220.44,ETC |
| | *** PLEASE KEEP IN MIND COMMENTS #3 ABOVE AS WELL AS |
| | ALL CONTINUOUS LOADS AT 125% ALONG WITH ANY LARGEST |
| | MOTOR LOADS. |
| | 215.3,230.42 |
| | |
| | 7) NOTE: PLEASE SEE NOTE #4 ON PLANS WHICH STATES ALL |
| | LIGHTING CONTROLS SHALL BE PER 13-415.1.ABC.1.1, .1.2. |
| | THESE CODE SECTIONS HAVE BEEN REVISED UNDER THE NEW |
| | CODE. PLEASE SEE 13-415.AB.1.1,.1.2, .1.3. |
| | |
| | 8) NOTE: PLEASE SEE FBC 13-413.AB.2.1, .2.2. PLEASE |
| | PLACE NOTES ON PLANS ACCORDINGLY. IT WAS CONFIRMED WITH |
| | THE STATE THAT THE VERBIAGE IN THE CODE IS THE INTENDED |
| | WORDING TO BE ON PLANS. |
| | |
| | 9) NOTE: PLEASE PLACE NOTE FOR FIRE ALARM PANEL BRANCH |
| | CIRCUIT. THE BREAKER SHALL BE OF A LOCK ON/OFF TYPE |
| | BREAKER WHICH MEANS THE DEVICE SHALL BE AN INTEGRAL |
| | PART OF THE BREAKER. THE SNAP/CLICK ON TYPE DEVICES IS |
| | NOT ACCEPTABLE OR LISTED FOR THE PURPOSE. 110.3 |
| | NFPA-72 4.4.1.4.2.1 THE DEDICATED BRANCH CIRCUIT(S) AND |
| | CONNECTIONS SHALL BE MECHANICALLY PROTECTED. |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | 10) NOTE: PLEASE SEE FBC 11-4.28.1, .2, .3 FOR MINIMUM |
| | DEVICES WHICH NEED TO BE SHOWN FOR ADA COMPLIANCE. |
| | PLEASE BE SURE TO ALSO SEE THE MINIMUM DEVICE HEIGHTS, |
| | LEVELS AND LOCATIONS NEED TO BE SHOWN ON PLANS. |
| | FS633. |
| | IF EXISTING, PLEASE SHOW LOCATIONS. THIS SPACE IS BEING |
| | RECONFIGURED FOR NEW TENANT SO THE LOCATIONS NEED TO BE |
| | VERIFIED. |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |