Plan Review Details - Permit 09060009
Plan Review Stops For Permit 09060009
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-11-16 Cont ID  
Sent By jgomez Date 2009-11-16 Time 11:25 Rev Time 0.00
Received By jgomez Date 2009-11-16 Time 11:25 Sent To  
Notes
2009-11-16 11:25:42ENERGY CALCS AND LINTEL PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-09-21 Cont ID  
Sent By jgomez Date 2009-09-21 Time 14:20 Rev Time 0.00
Received By jgomez Date 2009-09-21 Time 14:20 Sent To  
Notes
2009-09-21 14:21:40MET WITH MICHAEL PANCZAK. NEED TO RESUBMIT THE ENERGY
 CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-09-16 Cont ID  
Sent By jgomez Date 2009-09-16 Time 11:57 Rev Time 0.00
Received By jgomez Date 2009-09-16 Time 11:56 Sent To  
Notes
2009-09-16 12:02:49REVISION PACKAGE CHECKLIST:
  
 1- PRECAST LINTEL PRODUCT APPROVAL NOA 08-0320.09
 SUBMITTED IS FOR 4", 6" AND 12" PRECAST LINTELS. NEED
 TO PROVIDE PRODUCT APPROVAL FOR 8" PRECAST LINTELS AS
 SHOWN ON PLANS. (REPEAT COMMENT).
 ***REMAINDER: ENGINER OF RECORD TO REVIEW AND APPROVE
 IN WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) ENERGY CALCULATIONS PREPARER TO SIGN AND DATE BOTTOM
 OF FORM.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-08-19 Cont ID  
Sent By jgomez Date 2009-08-19 Time 15:27 Rev Time 0.00
Received By jgomez Date 2009-08-19 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-07-30 Cont ID  
Sent By jgomez Date 2009-07-30 Time 11:04 Rev Time 0.00
Received By jgomez Date 2009-07-30 Time 11:03 Sent To  
Notes
2009-07-30 11:18:02RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT
 COMMENT. NOT ADDRESSED AT ALL. THIS IS REQUIRED PRIOR
 TO RECEIVE THE PERMIT. SEE SEC. N1100.2.2 OF 2007
 FLORIDA RESIDENTIAL CODE).
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) PRECAST LINTELS AS SHOWN ON PLANS. (REPEAT COMMENT.
 NOT ADDRESSED AT ALL).
  
 B) ) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON
 PLANS AND DETAILS. (REPEAT COMMENT. NOT ADDRESSED AT
 ALL).
  
 4- SHEET 3.1:
 A) REVISE EGRESS WINDOWS NOTE: SEE SEC. R310 OF 2007
 FLORIDA RESIDENTIAL CODE FOR CORRECT MIN. OPENING
 HEIGHT AND CORRECT MIN. NET CLEAR OPENING. (REPEAT
 COMMENT. NOT PROPERLY ADDRESSED. EGRESS WINDOW OPENING
 IS NOT MEASURED BY THE MIN. TOTAL GLASS AREA BUT BY THE
 MIN. TOTAL OPENING AREA. ALSO, CLARIFY WHERE IS THE
 MIN. CLEAR OPENING HEIGHT OF 31" AND MIN. CLEAR OPENING
 WIDTH OF 36" TAKEN FROM. ALSO, THE LAST SENTENCE THAT
 "THE NET CLEAR OPENING SHALL IN NO CASE BE LESS THAN 5
 SQ.FT" . IS INCORRECT. THIS OPENING APPLIES TO GROUND
 UNITS ONLY. SEE SEC R310 OF 2007 FLORIDA RESIDENTIAL
 CODE AND REVISE INFORMATION AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-16 Cont ID  
Sent By jgomez Date 2009-06-16 Time 11:51 Rev Time 0.00
Received By jgomez Date 2009-06-16 Time 11:51 Sent To  
Notes
2009-06-16 11:52:52RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.0 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FRENCH DOORS INCLUDING FRENCH DOORS WITH SIDELITES
 AS SHOWN ON PLANS.
  
 B) FIXED WINDOWS AS SHOWN ON PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 ON DRAWINGS SPECIFIC MULLION SIZE AND ANCHORS TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES. SEC.
 R301.
  
 E) SHUTTERS IF DOORS AND WINDOWS DON'T HAVE IMPACT
 GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE ATTACHED SAMPLE. IN ADDITION MARK ON DRAWINGS
 SHUTTERS MOUNTING CONDITIONS AND ANCHOR TYPE AND
 SPACING TO BE USED.
  
 F) PRECAST LINTELS AS SHOWN ON PLANS.
  
 G) SIMPSON STRUCTURAL CONNECTORS AS SPECIFIED ON PLANS
 AND DETAILS.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 5- SHEET 3.1:
 A) SPECIFY SAFETY GLASS FOR WINDOW ON SHOWER OF MASTER
 BATHROOM AND WINDOWS NEXT TO SWING DOOR IN MASTER
 BEDROOM. SEC. R308.4 2007 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE EGRESS WINDOWS NOTE: SEE SEC. R310 OF 2007
 FLORIDA RESIDENTIAL CODE FOR CORRECT MIN. OPENING
 HEIGHT AND CORRECT MIN. NET CLEAR OPENING.
  
 C) INFORMATION ON WIND DESIGN INFORMATION AND DESIGN
 PARAMETERS DON'T CORRESPOND TO EACH OTHER. ONE CALLS
 FOR BUILDING EXPOSURE "C", WHILE THE OTHER ONE CALLS
 FOR BUILDING EXPOSURE "B". REVISE AS REQUIRED TO MATCH.
 (NOTE: ACCORDING TO 2009 REVISIONS, BUILDING IS LOCATED
 ON EXPOSURE "C").
  
 D) REVISE CODE SECTIONS SPECIFIED ON WIND DESIGN
 INFORMATION AND DESIGN PARAMETERS INFORMATION. SEE FBC
 2007 FOR CORRECT SECTION TO BE REFERENCED AND REVISE AS
 REQUIRED.
  
 E) FRAMED WALLS REQUIRES TWO LAYERS OF WATER RESISTANT
 BARRIERS AS REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE GENERAL WALL LEGEND AS
 REQUIRED.
  
 F) SPECIFY MIN. STUCCO THICKNESS (7/8") AS REQUIRED BY
 TABLE R702.1(1) OF 2007 FLORIDA RESIDENTIAL CODE.
 REVISE GENERAL WALL LEGEND AS REQUIRED.
  
 G) CLARIFY WHY THERE IS A NOTE THAT IMPACT RESISTANT
 WINDOWS REQUIRE 2X BUCKS. SEE WINDOW PRODUCT APPROVAL
 AND REVISE/CLARIFY AS REQUIRED.
  
 6- SHEET 4.1:
 A) REVISE TYPICAL DOOR JAMB DETAIL. 2X4 STRUCTURAL BUCK
 SIZE DOESN'T PROVIDE FULL SUPPORT TO THE DOOR FRAME AS
 REQUIRED BY SEC. R613.6 OF 2007 FLORIDA RESIDENTIAL
 CODE. SEE DOOR PRODUCT APPROVAL FOR SIZE OF FRAME AND
 SPECIFIED CORRECT STRUCTURAL BUCK SIZE.
  
 B) TYP. WOOD WALL SECTION: SPECIFY 2 LAYERS OF WATER
 RESISTANT BARRIER (SEC. R703.6.3) AND MIN. STUCCO
 THICKNESS (TABLE R702.1(1).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2009-11-16 Cont ID  
Sent By btrobaug Date 2009-11-16 Time 09:22 Rev Time 0.00
Received By btrobaug Date 2009-11-16 Time 09:02 Sent To P
Notes
2009-11-16 09:23:13TO KEN STEVENS./WRT.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-09-17 Cont ID  
Sent By dpalmer Date 2009-09-17 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2009-09-17 Time 14:17 Sent To  
Notes
2009-09-17 14:17:47PLANS SIGNED,
  
 REDLINED 13-606.AB.1.2.4 FOR TYPES OF RECESSED LIGHTS

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-09-17 Cont ID  
Sent By dpalmer Date 2009-09-17 Time 09:05 Rev Time 0.00
Received By dpalmer Date 2009-09-17 Time 09:05 Sent To  
Notes
2009-09-17 09:05:52 
 ** DENIED PLANS TEMPORARILY**
  
  
 1) NOTE: PLEASE SEE FS 471.003,481.229, WHEN MEETING
 EXCEPTIONS, DESIGN PROFESSIONAL LICENSED UNDER FS 489
 SHALL PRINT NAME AND SIGN PLANS.
 ** A CALLED WAS PLACED TO GC AND LEFT MESSAGE FOR
 ELECTRICAL CONTRACTOR TO COME IN AND ADDRESS THE ABOVE.
  
  
 ** AS STATED ABOVE. PLEASE CALL TO GO OVER ANY
 COMMENTS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-20 Cont ID  
Sent By dpalmer Date 2009-08-20 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2009-08-20 Time 16:55 Sent To  
Notes
2009-08-20 16:55:48*** REDLINED
  
  
 1) NOTE: RISER NOW REVISED TO REMOVE MAIN. EQUIPMENT
 GROUNDING CONDUCTOR STILL SHOWN BEFORE FIRST MEANS OF
 DISCONNECT. THIS IS NOT PERMITTED. 250.6, 250.24
  
 2) NOTE: VIF RECESSED LIGHTING MEETING FBC
 13-606.AB.1.2.4
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By dpalmer Date 2009-08-03 Time 11:17 Rev Time 0.00
Received By dpalmer Date 2009-08-03 Time 11:17 Sent To  
Notes
2009-08-03 11:17:27** DENIED 2ND REVIEW **
  
 *** THERE ARE SEVERAL ITEMS ON PLANS NOW SHOWN WHICH
 WERE NOT ON PREVIOUS SUBMITTED PLANS. SOME OF THESE
 HAVE CREATED NEW COMMENTS WHICH COULD NOT HAVE BEEN
 PREVIOUSLY MADE.
 PANEL SCHEDULE AND EQUIPMENT ON PANEL HAS BEEN
 COMPLETELY REVISED.
  
 1) NOTE: ELECTRICAL RISER INDICATES A MAIN DISCONNECT
 AFTER METER, YET THIS IS NOT SHOWN ON THE PLANS. THE
 PLANS ONLY INDICATE THE PANEL AND THE METER.
 PANEL SCHEDULE INDICATES PANEL AS MLO. A MAIN WOULD BE
 REQUIRED EITHER AHEAD OF PANEL OR IN PANEL IF LOCATED
 PER 230.70,230.71,
 240.24,110.26 ETC
  
 2) NOTE: PREVIOUS PANEL SCHEDULE INDICATED A STORAGE
 TYPE WATER HEATER AND THE REVIEW COMMENT WAS TO SHOW
 LOAD AT 125%. THE PLANS ALSO INDICATED A INSTA-HOT.
 HOWEVER THE NEW PLANS ONLY INDICATES ONE *INSTA-HOT*
 LOCATED UNDER THE COUNTER IN THE BATHROOM AND PER THE
 PANEL SCHEDULE THIS IS NOW A GAS APPLIANCE.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR LOCATION.
 PLEASE ALSO EXPLAIN WHERE THE REMAINDER OF THE HOT
 WATER IS BEING FED FROM. IS THERE GOING TO BE ANOTHER
 GAS OR ELECTRIC WATER HEATING SOURCE?
 THERE ARE UNANSWERED QUESTIONS ON THIS AT THIS TIME.
 SEE 422.13, 220.87 ETC
  
 3) NOTE: PLEASE PREVIOUS PLANS WHICH PANEL SCHEDULE
 INDICATED A 101KW AHU WITH 2-60 ON #6AWG WHICH WAS OK.
 HOWEVER THE PANEL SCHEDULE NOW INDICATES THIS SAME AHU
 INDICATES AN EVEN HIGHER LOAD AT 12KW. THE OVER CURRENT
 PROTECTION IS LESS AND SMALLER BRANCH CIRCUIT
 CONDUCTORS ARE ALSO SHOWN. THESE DO NOT MEET 424.3B FOR
 MINIMUM OCP AND 310.16, 240.4 FOR BRANCH CIRCUIT
 CONDUCTORS.
 PLEASE SEE NEW AHU #2 AND #3 WHICH BOTH SHOW 40AMP OCP
 FOR TWO DIFFERENT HEAT LOADS. THIS DOES NOT SEEM
 POSSIBLE.
 MECHANICAL PLANS DO NOT GIVE ANY INFORMATION.
  
 4) NOTE: SAME AS PREVIOUS REVIEW: PLEASE IDENTIFY THE
 LIGHTING CONTROL SWITCHES WITH THE RESPECTIVE 3-WAY OR
 4-WAY DESIGNATION. THERE ARE MORE THAN ONE LOCATION
 STILL SHOWN. 210.70
  
 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING
 ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF
 INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE)
  
 6) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED
 TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE
 SURE TO UPDATE TYPE OF FIXTURES ON PLANS.
  
 7) NOTE: PLEASE SHOW LOCATION FOR THE NEW 30AMP
 RECEPTACLE FOR MICROWAVE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By dpalmer Date 2009-06-18 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2009-06-18 Time 15:57 Sent To  
Notes
2009-06-18 15:57:37 
 ** DENIED PLANS *
  
 1) NOTE: PLEASE SEE FS 481.229, 471.003 AND 489 FOR
 REQUIRED DESIGN PROFESSIONAL. NO DESIGN PROFESSIONAL
 SHOWN. PLANS MUST BE DONE BY ONE OF THE SECTIONS GIVEN.
  
 2) NOTE: PLEASE CLARIFY SHEETS SUBMITTED. NOTE THE FACT
 THAT THE ELECTRICAL SHEET 5.1 CLEARLY STATES *SHEET 8
 OF 7* HOW IS THIS POSSIBLE? PLEASE COORDINATE ALL PLANS
 AND DOCUMENTS.
  
 3) NOTE: PLEASE PROVIDE LAYOUT OF EXISTING DWELLING
 SHOWING NEW OR EXISTING SMOKE ALARMS MEETING CURRENT
 NFPA-72. PLEASE KNOW THAT PER FS 553.885 IF THE HOUSE
 HAS AN ATTACHED GARAGE OR GAS APPLIANCES ONE CARBON
 MONOXIDE DETECTOR IS REQUIRED. A SMOKE ALARM DEVICE CAN
 BE A COMBINATION DEVICE WITH THE CARBON MONOXIDE
 DETECTORS.
 IF EXISTING DOES NOT MEET CURRENT NFPA-72, THEN ALL
 MUST BE BROUGHT UP TO CODE. PLEASE KEEP IN MIND THE ARC
 FAULT PROTECTION PER 210.12 OF THE 2005 NEC.
 11.8.3, 11.5.1.1, FBC R313.1
 SMOKE ALARM TOO CLOSE TO BATHROOM DOOR 11.8.3
  
 4) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD
 SHALL BE FIGURED AT 125% AS A CONTINUOUS LOAD. ( SEE
 NEC HANDBOOK).
  
 5) NOTE: PLEASE COORDINATE THE PLANS WITH THE
 ELECTRICAL RISER AS SHOWN. PLANS ONLY INDICATE A METER
 LOCATED OUTSIDE WHEREAS THE RISER CLEARLY SHOWS A MAIN
 TO BE INSTALLED.
 RISER IS CONFUSING AS THE RISER INDICATES A NEW MAIN TO
 BE INSTALLED YET THE RISER IS ALSO NOTED AT *EXISTING*.
 WHICH IS IT?
 110.26, 240.24, 230.70/71
 FBC 106.1.1 FOR CLARITY AND COORDINATION OF PLANS.
  
 6) NOTE: PLANS INDICATE THERE IS GOING TO BE A NEW
 INSTA-HOT HOWEVER THE PANEL SCHEDULE/LOAD CALCULATIONS
 AND PLUMBING PLANS DO NOT INDICATE ANY OF THIS?
 408.4,240.4,310.16,220 ETC
  
 7) NOTE: PLEASE IDENTIFY THE LIGHTING CONTROL SWITCHES
 WITH THE RESPECTIVE 3-WAY OR 4-WAY DESIGNATION.
 PLEASE ALSO SEE DOOR AREA OFF DINING ROOM WHICH THERE
 IS NO LIGHT ILLUMINATING THE EGRESS AREA. THERE ARE
 SEVERAL WAYS OF DOING THIS. PLEASE SHOW ONE *MINIMUM
 CODE REQUIRED* METHOD.
 210.70
  
 8) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING
 ALONG AREAS IN WHICH THERE IS MORE THAN 2FT OF
 INDIVIDUAL WALL SPACE. ( BEDRM #3 FOR EXAMPLE)
  
 9) NOTE: PLEASE SEE FBC 13-606.AB1.2.4 AS ALL RECESSED
 TYPE LIGHT FIXTURES SHALL MEET SECTION GIVEN. PLEASE BE
 SURE TO UPDATE TYPE OF FIXTURES ON PLANS.
  
 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS
 ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS SHALL BE
 FIGURED AT 1500VA FOR EACH. PLANS SHOW THE TWO MINIMUM
 KITCHEN SMALL APPLIANCES HOWEVER THE 1500VA IS FOR EACH
 INCLUDING AND ABOVE THE TWO. FOR EXAMPLE: DINING ROOM,
 AND AREAS OF THE LIKE.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 14:28 Sent To  
Notes
2009-09-08 14:28:59INCOMING TO R-11

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-12 Cont ID  
Sent By rmcdouga Date 2009-08-12 Time 09:08 Rev Time 0.00
Received By rmcdouga Date 2009-08-12 Time 09:08 Sent To  
Notes
2009-08-12 09:10:16TO R11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-17 Cont ID  
Sent By kstevens Date 2009-07-17 Time 12:17 Rev Time 0.00
Received By kstevens Date 2009-07-17 Time 12:16 Sent To  
Notes
2009-07-17 12:20:41SENT TO R-25.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date 2009-06-22 Time   Rev Time 0.00
Received By shill Date 2009-06-02 Time 10:44 Sent To  
Notes
2009-06-02 10:45:26TO R4
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-09-21 Cont ID  
Sent By rregueir Date 2009-09-21 Time 10:39 Rev Time 0.00
Received By rregueir Date 2009-09-21 Time 10:39 Sent To  
Notes
2009-09-21 10:39:48REVISED AD.1 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-08-24 Cont ID  
Sent By rregueir Date 2009-08-24 Time 12:06 Rev Time 0.00
Received By rregueir Date 2009-08-24 Time 10:48 Sent To  
Notes
2009-08-24 12:08:17**PROVISO**
 1. PROVIDE COMBUSTION OR MAKEUP AIR FOR NEW GAS DRYER
 PER FBC-R G2407.1 OR FBC-R G2439.4
  
 2. PROVIDE BALANCED RETURN IN MASTER SUITE PER FBC-R
 M1602.4
  
 3. PROVIDE NEW ENERGY CODE COMPLIANCE FORM PER BUILDING
 PLAN REVIEW COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 11:37 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 11:06 Sent To  
Notes
2009-07-28 11:37:22REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NOT ADDRESSED: PLANS SHOW THE GARAGE BEING CONVERTED
 TO A BEDROOM. ANY EXPANSION OF THE CONDITIONED SPACE IS
 DEFINED AS AN ADDITION PER FBC-R SECTION N1100.7.3.
 ADDITIONS TO EXISTING RESIDENTIAL BUILDINGS SHALL BE
 CONSIDERED NEW BUILDING CONSTRUCTION AND SHALL COMPLY
 WITH THE REQUIREMENTS OF EITHER METHOD A OR B AS
 APPLICABLE PER FBC-R SECTION N1100.0.3. ADDITIONS THAT
 ARE UNABLE TO COMPLY WITH CODE REQUIREMENTS FOR THE
 ADDITION ALONE MAY COMPLY WITH THE CODE BY BRINGING THE
 ENTIRE BUILDING INTO COMPLIANCE WITH SECTION
 N1100.A.5.2.
  
 2. PARTIALLY ADDRESSED: NO MECHANICAL INFORMATION IS
 PROVIDED ON PLANS. PLEASE SHOW HOW EXISTING A/C SYSTEM
 IS TO BE MODIFIED OR WHAT NEW SYSTEM IS BEING INSTALLED
 FOR THE NEWLY CONDITIONED SPACE. AT A MINIMUM,
 COMPLIANCE WITH FBC-R303.8 MUST BE SHOWN ON PLANS.
 PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO ENERGY
 CALCULATIONS SHOWING EXISTING EQUIPMENT CAPABLE OF
 ADDITIONAL COOLING LOADS.
  
 3. PARTIALLY ADDRESSED: LOCATION OF BATH EXHAUST
 TERMINATION STILL NOT SHOWN ON PLANS.
  
 4. NEW PLANS NOW SHOW NEW GAS APPLIANCES BEING
 INSTALLED. THE FOLLOWING SHALL BE ADDRESSED:
 A. GAS DRYER: PROVIDE COMBUSTION AIR IN ACCORDANCE WITH
 FBC-R SECTION G2407.1 OR MAKEUP AIR IN ACCORDANCE WITH
 FBC-R SECTION G2439.4.
 B. PAGE 5.1 SHOWS ONE CARBON MONOXIDE DETECTOR LOCATED
 IN THE SITTING AREA. CARBON MONOXIDE ALARMS SHALL BE
 LOACTED WITHIN 10 FEET OF SLEEPING ROOMS IN ACCORDANCE
 WITH FBC-R313.4.
  
 5. PAGE AD.1 SHOWS A DETAIL FOR ROOF MOUNTED DUCT. THE
 PROPOSED DETAIL IS NOT CLEAR. IS THE DUCT SHOWN ON
 PLANS TO BE RUN ON THE ROOF? IF SO, WHY IS THE DUCT
 SHOWN ON THE PLANS ROUND WHILE THE SUPPORT DETAIL IS
 FOR RECTANGULAR DUCT? HOW CAN THERE BE EXISTING
 SLEEPERS ON A SECTION OF THE BUILDING WHICH WAS
 PREVIOUSLY UNCONDITIONED? PLEASE CLARIFY AND SHOW
 COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS OF
 FBC-R SECTION M1307.3.
  
 6. RETURN TRANSFER DUCTS ARE NOT SIZED TO MEET THE
 EXCEPTIONS UNDER FBC-R SECTION M1602.4. DESIGN RETURNS
 TO MEET THESE EXCEPTIONS OR A FIELD TEST WILL BE
 REQUIRED AT FINAL INSPECTION TO VERIFY MAXIMUM PRESSURE
 DIFFERENTIAL IN ACCORDANCE WITH THIS SECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 11:03 Rev Time 0.00
Received By rregueir Date 2009-06-19 Time 10:18 Sent To  
Notes
2009-06-19 11:03:28REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLANS SHOW THE GARAGE BEING CONVERTED TO A BEDROOM.
 ANY EXPANSION OF THE CONDITIONED SPACE IS DEFINED AS AN
 ADDITION PER FBC-R SECTION N1100.7.3. ADDITIONS TO
 EXISTING RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW
 BUILDING CONSTRUCTION AND SHALL COMPLY WITH THE
 REQUIREMENTS OF EITHER METHOD A OR B AS APPLICABLE PER
 FBC-R SECTION N1100.0.3. ADDITIONS THAT ARE UNABLE TO
 COMPLY WITH CODE REQUIREMENTS FOR THE ADDITION ALONE
 MAY COMPLY WITH THE CODE BY BRINGING THE ENTIRE
 BUILDING INTO COMPLIANCE WITH SECTION N1100.A.5.2.
  
 2. NO MECHANICAL INFORMATION IS PROVIDED ON PLANS.
 PLEASE SHOW HOW EXISTING A/C SYSTEM IS TO BE MODIFIED
 OR WHAT NEW SYSTEM IS BEING INSTALLED FOR THE NEWLY
 CONDITIONED SPACE. AT A MINIMUM, COMPLIANCE WITH
 FBC-R303.8 MUST BE SHOWN ON PLANS.
  
 3. SHOW LOCATION OF DRYER AND BATH EXHAUST TERMINATIONS
 IN ACCORDANCE WITH FBC-R303.4, FBC-R303.5 AND FBC-R
 SECTION M1501.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-11-16 Cont ID  
Sent By kstevens Date 2009-11-16 Time 10:04 Rev Time 0.00
Received By kstevens Date 2009-11-16 Time 10:04 Sent To B
Notes
2009-11-16 10:05:29REVISION OK -- SHT 4.2 -- SANT. RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-14 Cont ID  
Sent By kstevens Date 2009-09-14 Time 13:54 Rev Time 0.00
Received By kstevens Date 2009-09-14 Time 13:54 Sent To  
Notes
2009-09-14 13:55:09REVISION OK -- SHT 4.2 -- SANT RISER DIAGRAM. -- NOTE
 CONCERNING GAS PERMIT BY INSTALLATION CONTRACTOR.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-06 Cont ID  
Sent By kstevens Date 2009-08-06 Time 15:44 Rev Time 0.00
Received By kstevens Date 2009-08-06 Time 15:44 Sent To  
Notes
2009-08-06 15:47:40 
  
  
  
 PASSED/PROVISO:
 A REVISION IS REQUIRED FOR THE SANITARY ISOMETRIC RISER
 DIAGRAM SHOWING THE CONNECTION OF THE BUILDING DRAIN TO
 THE BUILDING SEWER.
  
 SHT 5.1 PANEL BOARD SCHEDULE INDICATES A GAS RANGE &
 GAS INSTA-HOT WATER HEATER. A SEPARATE GAS PERMIT IS
 REQUIRED WITH GAS PLANS.
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-15 Cont ID  
Sent By kstevens Date 2009-06-15 Time 15:52 Rev Time 0.00
Received By kstevens Date 2009-06-15 Time 15:52 Sent To  
Notes
2009-06-15 15:53:28PASSED/PROVISO:
  
 REVISION REQUIRED SHOWING THE CONNECTION TO THE
 BUILDING DRAIN/BUILDING SEWER AND SHOW THE TRAP TO THE
 SHOWER.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-22 Cont ID  
Sent By mcruz Date 2009-06-22 Time 11:50 Rev Time 0.00
Received By mcruz Date 2009-06-22 Time 11:48 Sent To  
Notes
2009-06-22 11:50:01*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  