Plan Review Details - Permit 09050568
Plan Review Stops For Permit 09050568
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 19:25 Rev Time 0.00
Received By shill Date 2009-06-15 Time 19:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-16 Cont ID  
Sent By dpalmer Date 2009-10-16 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2009-10-16 Time 12:35 Sent To  
Notes
2009-10-16 12:35:36** PROVISO **
  
 PROVISO FROM PREVIOUS REVIEW NOT ADDRESSED.
  
  
 1) NOTE: CONDENSATE PUMPS ARE LABELED AS CIRCUIT L-8,
 ALTHOUGH THERE IS NO L PANEL. THE PANEL SCHEDULE
 INDICATES L-14 TYPICAL.
 408.4
  
 2) NOTE: LIGHTING CONTROLS FOR ROOMS 109,110, AND 111
 STILL REQUIRED TO MEET FBC 13-415.AB.1.1,.1.2 FOR
 MINIMUM PRESCRIPTIVE.
  
 3) NOTE: REDLINED PLANS, NO CORDS ARE PERMITTED ABOVE
 CEILING FOR CONDENSATE PUMPS. 400.8(2).
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 22:08 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 22:08 Sent To  
Notes
2009-07-21 22:08:33*** PROVISO/REDLINED PLANS.
  
 1) NOTE: ANY NEW DEVICES INSTALLED FOR ROOMS #110 AND
 #111 ARE REQUIRED TO COMPLY WITH FBC 13-415.AB.1.1,
 .1.2.
 ANY NEW DEVICE BEING INSTALLED MUST MEET SECTIONS
 ABOVE. PLEASE CALL TO GO OVER IF NEEDED. MAY NOT BE
 STANDARD SINGLE POLE SWITCHES. PLEASE SEE SECTION
 13-415.AB.1.2 FOR CONFERENCE ROOMS.
  
 2) NOTE: NL NOTE ON SYMBOL LEGEND DOES NOT INDICATE
 EMERGENCY BALLAST.
  
 ** PLEASE REVISE PLANS BEFORE ROUGH ELECTRICAL
 INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-17 Cont ID  
Sent By dpalmer Date 2009-06-17 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2009-06-17 Time 16:15 Sent To  
Notes
2009-06-17 16:15:28 
  
  
  
 ** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
 2) NOTE: PLEASE SEE 13-415.AB.5 AND 13-415.AB.5.1 FOR
 LIGHTING PERFORMANCE CALCULATIONS. THE SECTION WHICH
 USED TO ALLOW TRADE OFFS FOR OTHER AREAS IS NO LONGER
 IN THE CODE.
 AN EXAMPLE WOULD BE OFFICE 107 AS THE DESIGN ALLOWANCE
 IS OVER.
 PLEASE ALSO SEE RECEPTION AREA. THESE ARE DEFINED AS
 TWO SPACES ALTHOUGH SHOWN IN CALCULATIONS AS ONE.
 ANOTHER WOULD BE HALL AND SUPPLY WHICH ARE SHOWN
 FIGURED AS THE SAME SPACE HOWEVER THESE ARE CLEARLY
 SEPARATE SPACES ON TABLE.
 PLEASE ADJUST.
 HALLWAY SHOWS THE ADDITION OF A FIXTURE HOWEVER NO
 CIRCUIT, CONTROLS OR INFORMATION IS NOTED. PLEASE ALSO
 KNOW THAT ADDITIONAL LIGHTING MAY NOT BE ADDED IF THE
 EXISTING ALREADY EXCEEDS THE ALLOWANCE.
 ** ALLOWANCES FOR ROOMS SUCH AS ROOMS 109 AND 110 EVEN
 EXCEED ALLOWANCES UNDER THE 2001 CODE.
  
 3) NOTE: PLEASE CONFIRM THE ADDRESS LOCATION. THE
 APPLICATION NEEDS TO STATE WHETHER OR NOT THIS IS FOR
 EAST OR WEST TOWER OR CORRECT SUITE/UNIT. FOR EXAMPLE
 THE ELECTRICAL RISER SHOWS THE NEW METER AND MAIN TO
 NEW SUITE #1500 WHICH ALSO CONTAINS THE METER AND MAIN
 TO A SUITE #200. IF THIS IS BEING FED FROM SECOND FLOOR
 UP TO 15TH FLOOR HEN MORE INFORMATION IS NEED FOR
 CONDUCTOR SUPPORTS IN 300.19, VOLTAGE DROP IN 13-413 OF
 THE FBC.
 FBC 106.5
  
 4) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
  
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-23 Cont ID  
Sent By mawillia Date 2009-07-23 Time 11:29 Rev Time 0.00
Received By mawillia Date 2009-07-23 Time 11:09 Sent To I
Notes
2009-07-23 11:17:18*****APPROVAL*****
  
 PLAN SHEETS A3.1AND E2 WERE STAMPED, INITIALED, AND
 DATED; PLAN SHEETS A1.1 & A1.2 WERE PREVIOUSLY
 FIRE-STAMPED ON 6/18/2009.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By mawillia Date 2009-06-18 Time 13:06 Rev Time 0.00
Received By mawillia Date 2009-06-18 Time 12:38 Sent To  
Notes
2009-06-18 13:05:49*****PARTIAL APPROVAL*****
  
  
 PLAN SHEETS A1.1 & A1.2 WERE STAMPED, INITIALED, AND
 DATED; HOWEVER SHEET E2 IS TO BE FIRE-STAMPED WHEN THE
 ELECTRICAL EXAMINER'S COMMENT(S) HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2009-07-06 Time   Rev Time 0.00
Received By   Date 2009-07-06 Time   Sent To  
Notes
2009-07-22 18:16:39INCOMING PROCESSED BY JW, SENT TO C20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 14:39 Rev Time 0.00
Received By rregueir Date 2009-06-02 Time 14:37 Sent To PC
Notes
2009-06-17 12:48:55MOVED FROM C-18 TO B-1
2009-06-02 14:38:18C-18

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-16 Cont ID  
Sent By rregueir Date 2009-10-16 Time 14:18 Rev Time 0.00
Received By rregueir Date 2009-10-16 Time 14:18 Sent To PC
Notes
2009-10-16 14:19:48REVISED M1 DELTA 3, PAGE M2 - NO CHANGES IDENTIFIED ON
 PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-06-19 Cont ID  
Sent By rregueir Date 2009-06-19 Time 14:38 Rev Time 0.00
Received By rregueir Date 2009-06-19 Time 14:38 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-17 Cont ID  
Sent By kstevens Date 2009-06-17 Time 14:35 Rev Time 0.00
Received By kstevens Date 2009-06-17 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-05 Cont ID  
Sent By aaponte Date 2009-06-05 Time 11:08 Rev Time 0.00
Received By aaponte Date 2009-06-05 Time 11:08 Sent To  
Notes
***NONE***