| 2009-05-29 13:43:03 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 |
| | REVISIONS. |
| | |
| | 1- FLAT ROOF: |
| | A) SELECTED ASSEMBLY ON SHEET 17 OF NOA 07-1219.09 |
| | SUBMITTED IS GOOD FOR -52.5PSF MAXIMUM DESIGN |
| | PRESSURES. THIS BUILDING IS LOCATED IN AN AREA THAT |
| | REQUIRES HIGHER DESIGN PRESSURES FOR PERIMETER AND |
| | CORNER AREAS. THEREFORE, NAIL ENHANCING AS REQUIRED BY |
| | GENERAL LIMITATION #7 ARE REQUIRED. |
| | |
| | B) GENERAL LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED |
| | REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED |
| | BY ANY OF THE DESIGN PROFESSIONAL LISTED. SEE GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA AND PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS. |
| | ***NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION |
| | THAT ACCORDING TO THE 2009 REVISIONS TO THE 2007 |
| | FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED ON |
| | EXPOSURE C, NOT B. SEE REVISIONS TO BUILDING EXPOSURE |
| | ON SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- SHINGLES PRODUCT APPROVAL 07-1120.14 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE COUNTY. SEE ATTACHED COPY FROM |
| | MIAMI-DADE COUNTY WEBSITE. NEED TO PROVIDE CURRENT NOA |
| | 08-1110.09 WHICH SUPERSEDES NOA 07-1120.14. |
| | |
| | 3- COBRA VENTILATION NOA 08-0826.02 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE COUNTY ALSO. SEE ATTACHED |
| | COPY. PROVIDE CURRENT NOA 09-0105.08. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |