| 2009-05-26 13:00:58 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | ONLY ONE COPY PROVIDED (TWO REQUIRED) AND ONE COLUMN |
| | WAS LEFT BLANK. THE "SHUTTER CONNECTION MOUNTING TYPE" |
| | SHOULD CORRELATE WITH THE ANCHOR CHARTS; IN THIS CASE, |
| | THEY ARE NAMED SECTION 1 THROUGH SECTION 13, TOP AND |
| | BOTTOM, FOR CONCRETE AND BLOCK (SEE SHEET 10). IT |
| | APPEARS THAT YOU MAY BE PROPOSING TO USE SECTION 7 |
| | (BOTH TOP AND BOTTOM). |
| | |
| | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, |
| | FAC9B72, WWW.FLORIDABUILDING.ORG. PLEASE PRINT COVER |
| | SHEET FROM THE WEBSITE. |
| | |
| | 3. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| | |
| | 4. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS WILL |
| | BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH THE |
| | INSTALLATION SCHEDULE, ITEM 1 ABOVE. FBC R301, FBC1609, |
| | FBC*106. |
| | |
| | 5. SEE FBC R 301 OR FBC1609, ASCE7-05, THIS JOB IS IN |
| | EXPOSURE C. PLEASE REVISE DESIGN PRESSURES ACCORDINGLY. |
| | |
| | |
| | |