Plan Review Details - Permit 09050428
Plan Review Stops For Permit 09050428
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-12 Cont ID  
Sent By rmcdouga Date 2009-06-12 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2009-06-12 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 16:01 Sent To FIRE
Notes
2009-05-29 16:16:042007 FBC
 REPAIR FIRE DAMAGE
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR SLIDING GLASS DOOR REQUIRES IMPACT PROTECTION
 DEVICES TO BE INSTALLED. SPECIFY HOW IMPACT PROTECTION
 WILL BE PROVIDED. SUBMIT 2 SETS OF PRODUCT APPROVALS
 FOR THE IMPACT PROTECTION DEVICES THAT WILL BE
 INSTALLED OR PROVIDE PROOF OF EXISTING APPROVED IMPACT
 PROTECTION. FBC 1609.1.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-27 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2009-05-27 Time 15:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-06-01 Cont ID  
Sent By mwennerg Date 2009-06-01 Time 14:32 Rev Time 0.00
Received By mwennerg Date 2009-06-01 Time 14:32 Sent To  
Notes
2009-06-01 14:33:41IN ADDITION TO APPLICABLE BUILDING CODES, WORK TO
 COMPLY WITH NFPA 101, 2006 AND NFPA 241.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 12:57 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 12:56 Sent To B
Notes
2009-06-11 12:57:06TO RMCD DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-01 Cont ID  
Sent By mwennerg Date 2009-06-01 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2009-05-21 Time 11:48 Sent To  
Notes
2009-05-21 11:48:56TO R BOX #14

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 16:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 16:17 Sent To  
Notes
***NONE***