Plan Review Details - Permit 09050415
Plan Review Stops For Permit 09050415
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-17 Cont ID  
Sent By rmcdouga Date 2009-07-17 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2009-07-17 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By rmcdouga Date 2009-05-28 Time 14:47 Rev Time 0.00
Received By rmcdouga Date 2009-05-28 Time 14:47 Sent To  
Notes
2009-05-28 15:47:302007 FBC
 ADDITION
  
 DENIED BY BUILDING
  
 1) THE FOUNDATION PLAN ON SHEET 5.0 SPECIFIES A 4"
 CONCRETE SLAB. THE ELEVATION AND SECTIONS SHOW A 6"
 SLAB. PLEASE CORRECT.
  
 2) THE DETAIL TAG FOR (1 ON 8.0) ON SHEET 5.0 LISTS THE
 WRONG SHEET. IT SHOULD BE 1 ON 7.0. PLEASE CORRECT.
  
 3) ON SHEET 6.0 THE FRAMING NOTES SPECIFY 19/32" (5/8")
 PLYWOOD FOR ROOF SHEATHING AND THE NOTE ON THE DRAWINGS
 ON 6.0 AND 7.0 SPECIFIES 3/4" PLYWOOD. PLEASE CORRECT.
  
 4) THE WINDLOAD PRESSURES SPECIFIED FOR THE EXTERIOR
 DOOR TO THE LAUNDRY ROOM ON SHEET 3.1 ARE TOO LOW FOR
 AN ENCLOSED STRUCTURE LOCATED IN EXPOSURE CATEGORY C
 AND AN IMPORTANCE FACTOR OF 1.00. FBC R TABLE R301.2.1
  
 5) THE WINDLOAD SCHEDULE FOR THE OPEN ATTACHED PATIO IS
 INCORRECT. THE PATIO AND LAUNDRY ROOM ARE ATTACHED TO
 THE DWELLING AND ARE NOT STRUCTURALLY INDEPENDENT. THE
 SINGLE FAMILY DWELLING IS A CATEGORY II OCCUPANCY, AS
 WELL AS, THE ATTACHED COVERED PATIO AND LAUNDRY ROOM.
 THEREFORE, THE IMPORTANCE FACTOR IS 1.00 AND NOT 0.77.
 PLEASE CORRECT AND REVISE THE ROOF WINDLOADS. FBC
 R301.2.1
  
 6) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE FOR THE
 EXTERIOR DOORS TO THE LAUNDRY ROOM AS REQUIRED BY FAC
 RULE 9B-72.
  
 7) THE DOOR SCHEDULE ON SHEET 3.1 INDICATES STORM
 PANELS FOR THE EXTERIOR DOORS TO THE LAUNDRY ROOM.
 STORM PANELS ONLY PROVIDE IMPACT PROTECTION FOR GLAZED
 AREAS. THEY ARE DO NOT PREVENT WIND PRESSURES FROM
 AFFECTING THE BUILDING ENVELOPE. THAT IS PROVIDED BY
 THE WINDOW OR DOOR THAT IS INSTALLED IN THE EXTERIOR
 OPENING. R301.2.1.2
  
 8) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE AND KEY
 PLAN SPECIFYING THE OPENINGS THAT WILL BE SHUTTERED.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE AND SPACING,
 SPAN, ETC.
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 STORM PANELS ARE MISSING SOME OF THE PAGES. SUBMIT 2
 COMPLETE COPIES OF THE PRODUCT APPROVALS.
  
 10) THE SYSTEM SELECTED FROM THE MODIFIED ROOF COVERING
 PRODUCT APPROVALS HAS A MAXIMUM DESIGN PRESSURE OF -52
 PSF, WHICH WILL REQUIRE ENHANCED FASTENING AT THE
 CORNER AND PERIMETER AREAS FOR EXPOSURE C AND 140 MPH
 WINDSPEED. SUBMIT 2 SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY LIMITATION #7 OF THE NOA.
  
 11) THE VALUATION THAT IS INDICATED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE SCOPE OF WORK SHOWN ON
 THE PLANS. THE VALUE HAS BEEN INCREASED TO $17,111.00
 BASED ON ICC VALUATION DATA. ADDITIONAL PERMIT AND
 RADON FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By btrobaug Date 2009-07-10 Time 11:45 Rev Time 0.00
Received By btrobaug Date 2009-07-10 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-27 Time 16:00 Rev Time 0.00
Received By btrobaug Date 2009-05-27 Time 15:56 Sent To  
Notes
2009-05-27 15:59:46 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-10 Cont ID  
Sent By btrobaug Date 2009-07-10 Time 11:45 Rev Time 0.00
Received By btrobaug Date 2009-07-06 Time 09:24 Sent To  
Notes
2009-07-10 11:46:32 
  
 R 11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2009-05-19 Time 14:20 Sent To  
Notes
2009-05-20 14:21:52R-6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-05-29 Cont ID  
Sent By rmcdouga Date 2009-05-29 Time 08:19 Rev Time 0.00
Received By rmcdouga Date 2009-05-29 Time 08:19 Sent To  
Notes
2009-05-29 08:20:55NO MECHANICAL PERMIT APPLIED FOR AND NO PLANS
 SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-17 Cont ID  
Sent By rmcdouga Date 2009-07-17 Time 15:11 Rev Time 0.00
Received By rmcdouga Date 2009-07-17 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-28 Cont ID  
Sent By rmcdouga Date 2009-05-28 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2009-05-28 Time 16:59 Sent To  
Notes
2009-05-28 17:01:012007 FBC
 ADDITION
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING PLAN ON SHEET 9.0 WHICH HAS A AN
 ENGINEERING COMPANY LISTED IN THE TITLE BLOCK IS
 REQUIRED BY FS 471 TO HAVE THE EMBOSSED SEAL AND
 ORIGINAL SIGNATURE OF THE ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2009-05-31 Cont ID  
Sent By mcruz Date 2009-05-31 Time 13:09 Rev Time 0.00
Received By mcruz Date 2009-05-31 Time 13:09 Sent To  
Notes
***NONE***