| 2009-05-27 12:50:56 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS471. |
| | |
| | 2. SOUTH ENTRANCE RAMP, SEE FBC11-4.6.2(1), PARKING |
| | SPACES TO BE LOCATED ON AN ACCESSIBLE ROUTE NO LESS |
| | THAN 44". THE DETAIL SHOWS THE RAMP AS 3'. |
| | |
| | 3. SOUTH ENTRANCE RAMP IS SHOWN AS 36"; SEE FBC11-4.8.3 |
| | (EXCEPTION), FBC1010.5.1, 44" REQUIRED AS THIS IS A |
| | REQUIRED MEANS OF EGRESS. |
| | |
| | 4. IT APPEARS THAT HANDRAILS ARE REQUIRED AND ARE SHOWN |
| | ON THE PLAN, FBC11-4.8.5. A PERMIT IS REQUIRED FOR |
| | HANDRAIL INSTALLATION. WHEN RESUBMITTING, PROIVIDE AN |
| | APPLICATION FOR HANDRAIL INSTALLATION OR ADVISE AS TO |
| | HOW THIS ISSUE WILL BE ADDRESSED (THIS DOES NOT APPEAR |
| | TO BE WITHIN THE SCOPE OF A CONCRETE CONTRACTOR'S |
| | LICENSE). |
| | |
| | 5. FBC11-4.8.4(2), SHOW 72" STRAIGHT AND LEVEL |
| | CLEARANCE REQUIRED AT THE BOTTOM OF EACH RAMP. |
| | |
| | 6. SOUTH ENTRANCE RAMP, MIDDLE OF ACCESS AISLE |
| | TERMINATES AT THE RAMP. THE RAMP IS REQUIRED TO HAVE |
| | HANDRAILS AND HANDRAIL EXTENSIONS FBC 11-4.8.5, SHOW |
| | ACCESSIBLE ROUTE. FBC11-4.6.2. |
| | |
| | 7. PROVIDE A DETAIL FOR THE EDGE PROTECTION, |
| | FBC11-4.8.7, FBC1010.9. |
| | |
| | 8. LANDING AT DOORS SHALL COMPLY WITH FBC11-13.6 (PER |
| | FBC11-4.8.4(4)), FBC FIGURE 11-25. SOUTH ENTRANCE, |
| | NORTHEAST ENTRANCE, SHOW 18" MINIMUM PULL SIDE AT THE |
| | DOOR. |
| | |
| | 9. EXIT DISCHARGE HAS BEEN REDUCED FROM 5' TO 3' AT THE |
| | SOUTH ENTRANCE; MEANS OF EGRESS CAPACITY SHALL NOT BE |
| | DIMINISHED FBC1003.6. |
| | |
| | 10. CLARIFY LOCATION OF ACCESSIBLE PARKING SIGNAGE. |
| | C-1D SHOWS SIGN 2' MIN AWAY FROM OVERHANG EDGE, BUT |
| | THAT WOULD PUT THE SIGN IN THE MIDDLE OF THE SOUTH |
| | ENTRANCE RAMP. |
| | |
| | 11. ENGINEER'S PLAN CONFLICTS WITH THE DETAIL PROVIDED |
| | BY G & H CONCRETE; FOR INSTANCE, SOUTH RAMP, ENGINEER'S |
| | PLAN SHOWS A 3' RAMP, OTHER SHOWS 4' WIDE RAMP, AND |
| | ENGINEER'S PLAN DOES NOT SHOW WIDTH OF RAMP SECTION |
| | BETWEEN LANDING AND DOOR. HAVE THE ENGINEER INCORPORATE |
| | ALL CHANGES AND DIMENSIONS INTO HIS OR HER PLAN. |
| | |
| | |
| | |
| | |