| 2009-05-21 16:28:05 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 |
| | REVISIONS. |
| | |
| | 1- REVISE INSTALLATION SCHEDULE ANCHOR SPACING FOR |
| | OPENINGS 1 AND 2 TO MATCH THE CALCULATED DESIGN |
| | PRESSURES. CALCULATED DESIGN PRESSURES ARE -57.2. |
| | THEREFORE ANCHOR SPACING FOR -57 CAN'T BE USED. NEED TO |
| | USE HIGHER DESIGN PRESSURES ANCHOR SPACING. |
| | |
| | 2- CLARIFY IF SUBSTRATE TO RECEIVE SHUTTERS IS POURED |
| | CONCRETE ON TOP AND BOTTOM. TYPICALLY THERE IS A |
| | PRECAST CONCRETE LINTEL OR POURED CONCRETE BEAM ON TOP, |
| | BUT WINDOW SILL MAY NOT BE POURED CONCRETE. PROVIDE |
| | PROOF THAT WINDOW SILL HAS MIN. 3,320 PSI CONCRETE |
| | STRENGTH AS REQUIRED BY THE PRODUCT APPROVAL OR USE THE |
| | CONCRETE BLOCK ANCHOR SPACING TO VERIFY COMPLIANCE WITH |
| | THE PRODUCT APPROVAL AND CALCULATED DESIGN PRESSURES |
| | REQUIRED BY SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | REVISE ANCHOR SPACING AS REQUIRED. |
| | |
| | 3- REVISE LENGTH OF TAPCON. 1-3/4" TAPCON DOESN'T |
| | PROVIDE THE MIN. REQUIRED EMBEDMENT OF 1-3/4" ON |
| | CONCRETE INSTALLATIONS. |
| | NOTE: MINIMUM EMBEDMENT EXCLUDES STUCCO OR ANY OTHER |
| | FINISH. ALSO, MINIMUM EMBEDMENT REQUIRED FOR CONCRETE |
| | BLOCK INSTALLATION IS 1-1/4" EXCLUDING STUCCO ALSO. |
| | |