| Plan Review Stops For Permit 09050339 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-09 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-09 |
Time |
13:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-11 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-11 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2009-06-11 14:27:34 | 2007 FBC | | | INSTALL LP GENERATOR | | | | | | DENIED BY BUILDING | | | | | | 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE | | | SLAB TO RESIST WINDLOADS OF 140 MPH IN REGARD TO | | | OVERTURNING, SLIDING AND UPLIFT. SEE FBC 1604.9. | | | | | | 2) ADJUST THE DECLARED VALUE TO REFLECT THE ENTIRE | | | SCOPE OF WORK INCLUDING ALL LABOR AND ALL MATERIALS. | | | FBC 108.3* CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-08 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-07-08 |
Time |
14:08 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-06-11 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-06-11 |
Time |
09:25 |
Sent To |
B |
|
| Notes |
| 2009-06-11 11:14:53 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL FOR THE GENERATOR, | | | EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER | | | 108.3 FBC AS AMENDED. | | | INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING, | | | AND GET A RECEIPT FROM THE PERMIT CLERK. | | | | | | 2} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING | | | GENERATOR AND RELATED EQUIPMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2009-06-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-10 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-10 |
Time |
14:17 |
Sent To |
B |
|
| Notes |
| 2009-06-10 14:18:31 | SEE PERMIT # 09050466 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-07-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-01 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-01 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2009-07-01 10:32:54 | SENT TO ZONING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-11 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-05-18 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2009-05-18 16:21:47 | TO ZONING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-07-09 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-09 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-06-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-06-11 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-11 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2009-06-11 16:03:34 | 2007 FBC | | | INSTALL LP GENERATOR | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE CONCRETE SLAB SUPPORTING THE GENERATOR IS | | | REQUIRED TO BE A MINIMUM OF 3-1/2" THICK. SEE FBC | | | M304.9 | | | | | | 2) THE GENERATOR IS REQUIRED TO BE LOCATED AT LEAST 5 | | | FEET FROM OPENINGS IN WALLS AND AT LEAST 5 FEET FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS PER NFPA 37 SECTION | | | 4.1.4 SHOW COMPLIANCE. FBC M 915.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-07-06 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-07-06 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-07-06 |
Time |
10:51 |
Sent To |
E |
|
| Notes |
| 2009-07-06 10:55:06 | ROUTED TO BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-31 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-05-31 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-05-31 |
Time |
11:25 |
Sent To |
E |
|
| Notes |
| 2009-05-31 11:29:59 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED | | | GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE | | | CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT | | | REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL | | | EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A | | | REQUIRED SETBACK. | | | | | | PURSUANT TO THE ZLDR, SECTION 94-72(A)(2): | | | SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT - | | | MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS: | | | | | | A. FRONT: 25 FEET; | | | | | | B. CORNER: 12.5 FEET; | | | | | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | | IS LESS; | | | | | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|