Plan Review Details - Permit 09050339
Plan Review Stops For Permit 09050339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By rmcdouga Date 2009-07-09 Time 13:00 Rev Time 0.00
Received By rmcdouga Date 2009-07-09 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 14:17 Rev Time 0.00
Received By rmcdouga Date 2009-06-11 Time 14:17 Sent To  
Notes
2009-06-11 14:27:342007 FBC
 INSTALL LP GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE
 SLAB TO RESIST WINDLOADS OF 140 MPH IN REGARD TO
 OVERTURNING, SLIDING AND UPLIFT. SEE FBC 1604.9.
  
 2) ADJUST THE DECLARED VALUE TO REFLECT THE ENTIRE
 SCOPE OF WORK INCLUDING ALL LABOR AND ALL MATERIALS.
 FBC 108.3* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By btrobaug Date 2009-07-08 Time 14:32 Rev Time 0.00
Received By btrobaug Date 2009-07-08 Time 14:08 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By btrobaug Date 2009-06-11 Time 11:14 Rev Time 0.00
Received By btrobaug Date 2009-06-11 Time 09:25 Sent To B
Notes
2009-06-11 11:14:53 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE PERMIT CLERK.
  
 2} PROVIDE A RISER DIAGRAM PER 215.5 INCLUDING
 GENERATOR AND RELATED EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2009-06-10 Cont ID  
Sent By kstevens Date 2009-06-10 Time 14:17 Rev Time 0.00
Received By kstevens Date 2009-06-10 Time 14:17 Sent To B
Notes
2009-06-10 14:18:31SEE PERMIT # 09050466

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 10:32 Sent To  
Notes
2009-07-01 10:32:54SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2009-05-18 Time 16:21 Sent To  
Notes
2009-05-18 16:21:47TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By rmcdouga Date 2009-07-09 Time 13:01 Rev Time 0.00
Received By rmcdouga Date 2009-07-09 Time 13:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2009-06-11 Time 15:09 Sent To  
Notes
2009-06-11 16:03:342007 FBC
 INSTALL LP GENERATOR
  
 DENIED BY MECHANICAL
  
 1) THE CONCRETE SLAB SUPPORTING THE GENERATOR IS
 REQUIRED TO BE A MINIMUM OF 3-1/2" THICK. SEE FBC
 M304.9
  
 2) THE GENERATOR IS REQUIRED TO BE LOCATED AT LEAST 5
 FEET FROM OPENINGS IN WALLS AND AT LEAST 5 FEET FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS PER NFPA 37 SECTION
 4.1.4 SHOW COMPLIANCE. FBC M 915.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-07-06 Cont ID  
Sent By mcruz Date 2009-07-06 Time 10:55 Rev Time 0.00
Received By mcruz Date 2009-07-06 Time 10:51 Sent To E
Notes
2009-07-06 10:55:06ROUTED TO BT

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-31 Cont ID  
Sent By mcruz Date 2009-05-31 Time 11:30 Rev Time 0.00
Received By mcruz Date 2009-05-31 Time 11:25 Sent To E
Notes
2009-05-31 11:29:59PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. INDICATE SETBACK DIMENSIONS FROM THE PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  