Plan Review Details - Permit 09050332
Plan Review Stops For Permit 09050332
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By dwise Date 2009-07-09 Time 22:03 Rev Time 0.00
Received By dwise Date 2009-07-09 Time 22:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-02 Cont ID  
Sent By jwitmer Date 2009-06-02 Time 10:45 Rev Time 0.77
Received By jwitmer Date 2009-06-02 Time 10:00 Sent To  
Notes
2009-06-02 11:22:41BUILDING PLAN REVIEW
 PERMIT: 09050332
 ADD: 5841 CORPORATE WAY SUITE# 100
 CONT: LTL BUILDERS, INC.
 TEL: (561629-9753
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. PLEASE PROVIDE THE
 EXISTING FLOOR PLAN OF THIS SUITE OR LIFE SAFETY PLAN
 FOR THE FULL SUITE. 106.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS, COMMERCIAL:
 (6) LIFE SAFETY
 (7) MEANS OF EGRESS & SPECIFIC OCCUPANCY REQUIREMENTS
 PLEASE INCLUDE THE COMMON CORRIDORS OR HALLWAYS,
 1028.1.2 EXTERIOR CORRIDORS, THE MINIMUM CLEAR WIDTH OF
 SUCH CORRIDORS SHALL BE SUFFICIENT TO ACCOMMODATE THE
 OCCUPANT LOAD BUT SHALL IN NO CASE BE LESS THAN 6 FEET.
 THE CORRIDOR TO TTHE LEFT OF THE CLSSROOMS IS TO BE
 CONSIDERED AN EXTERIOR CORRIDOR. THE CORRIDOR DIRECTLY
 IN FRONT OF THE MAIN ENTRY AND CLASSROOM # 3 CAN'T BE
 DERTERMINED AT THIS TIME.
  
 THE SECOND ISSUE WITH THE CORRIDORS THAT SERVE THE
 EDUCATIONAL OCCUPANCY IS THE FIRE RATING OF THE
 CORRIDOR. TABLE 1017.1 REQUIRES THE CORRIDOR TO BE A 1
 HOUR RATING FOR BUILDINGS THAT ARE NOT FIRE
 SPRINKLERED, AND A EDUCATIONAL OCCUPANCY GREATER THAN
 30. PLANS INDICATE ONLY THE EDUCATIONAL OR CLASS ROOM
 ARE TO BE FIRE SPRINKLERED FROM THE NOTE# 3 OF SHEET
 A-1.0. AGAIN PLEASE PROVIDE CORRIDOR RATING S OUTSIDE
 OF THE TENANT UNIT.
  
 2) SHEET A-0.0 INDICATES THAT THE BUILDING TYPE TO BE A
 III-A, SPRINKLED:
 2A) IS THE TOTAL BUILDING SPRINKLERED?
 2B) THIS BUILDING TYPE IS INDICATED AS A TYPE IIIA IS
 THE BAR JOIST 1 HR PROTECTED? IT APPEARS THIS BUILDING
 COULD BE CLASSIFIED AS A III-B WITH AREA MODIFICATIONS
 506.1 & 506.2.
  
 3) SHEET A-1.0 INDICATES TWO DOORS IN SERIES LEADING
 FROM THE RECEPTION ROOM TO THE LUNCH ROOM, PLEASE
 REVIEW SECTION 11-4.13.7 AND FIGURE 26, TWO DOORS IN
 SERIES.
  
 4) SHEET A-1.0 THE SAME TWO DOORS ON THE LATCH SIDE
 WILL REQUIRE 18" CLEAR FOR MANEUVERING CLEARENCES.
 11-4.13.6.
  
 5) THE B. O. DOUG WISE WILL DETERMINE IF THE EXISTING
 SHOWER WILL REQUIRE ACCESSIBILITY, SINCE THIS IS TO BE
 USED AS A TEACHING TOOL. 11-4.21. SHOWER STALL
 REQUIREMENTS.
 MR. WISE HAS BEEN IN CONTACT WITH MR. TYLKA ALREADY FOR
 THIS PROJECT.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By dwise Date 2009-07-09 Time 22:04 Rev Time 0.00
Received By dwise Date 2009-07-09 Time 22:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By btrobaug Date 2009-06-11 Time 15:22 Rev Time 0.00
Received By btrobaug Date 2009-06-11 Time 14:35 Sent To  
Notes
2009-06-11 14:47:38 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A PANEL SCHEDULE FOR PANEL "B".
  
 2} LOCATE THE PANELS ON THE PLAN.
  
 3} INDICATE COMPLIANCE WITH CHAPTER 13, SECTION 13-415,
 ALL THAT APPLY.
  
 4} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By mawillia Date 2009-07-10 Time 15:12 Rev Time 0.00
Received By mawillia Date 2009-07-10 Time 14:39 Sent To  
Notes
2009-07-10 15:12:11*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A-1.0, A-1.2, AND E-1.0
 WERE STAMPED, INITIALED, AND DATED. THE FIRE SPRINKLER
 SHEET (1 OF 1) WAS REVIEWED FOR REFERENCE ONLY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-16 Cont ID  
Sent By mwennerg Date 2009-06-16 Time 12:11 Rev Time 0.00
Received By mwennerg Date 2009-06-16 Time 12:11 Sent To  
Notes
2009-06-16 12:19:17***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2006 AS PART OF
 THE FLORIDA FIRE PREVENTION CODE, 2007 EDITION.
  
 2) IN ADDITION TO SEPARATE SHOP DRAWINGS AND PERMITS,
 PLEASE PROVIDE THE LAYOUT OF FIRE PROTECTION EQUIPMENT.
 THE FIRE SPRINKLER LAYOUT MAY BE SHOWN ON THE REFLECTED
 CEILING PLAN.
  
 3) IS THIS CONSIDERED A FULLY FIRE SPRINKLERED
 BUILDING?
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN ILUUSTRATING THE
 MINIMUM TRAVEL DISTANCES.
  
 5) THE FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR
 CENTRAL STATION SERVICE IF NOT ALREADY PART OF AN
 EXISTING SYSTEM.
  
 6) PLEASE PROVIDE THE LOCATIONS OF REQUIRED 2A-10B,C
 RATED FIRE EXTINGUISHERS.
  
 7) PLEASE PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-16 Cont ID  
Sent By mwennerg Date 2009-06-16 Time 12:21 Rev Time 0.00
Received By mwennerg Date 2009-05-19 Time 08:34 Sent To  
Notes
2009-05-19 08:34:51TO BOB #B3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-07-10 Cont ID  
Sent By lmartine Date 2009-07-10 Time 15:55 Rev Time 0.00
Received By lmartine Date 2009-07-09 Time 22:06 Sent To  
Notes
2009-07-09 22:08:28APPLICANT MUST PROVIDE RECIEPT FROM PALM BEACH COUNTY
 FOR IMPACT FEES FOR CHANGE IN USE. DBW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By dwise Date 2009-07-09 Time 22:03 Rev Time 0.00
Received By dwise Date 2009-07-09 Time 22:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-08 Cont ID  
Sent By rregueir Date 2009-06-08 Time 14:43 Rev Time 0.00
Received By rregueir Date 2009-06-08 Time 09:38 Sent To  
Notes
2009-06-08 14:43:40REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1.0: SEVERAL DUCTS ARE MISSING SIZES. ONE SET
 OF PLANS HAS BEEN MARKED TO SHOW WHICH SIZES ARE
 MISSING. THE 7" ROUND SUPPLY IN EXISTING BATHROOM
 WITHIN CLASSROOM #2 IS MISSING CFM DESIGNATION. PLEASE
 PROVIDE ALL MISSING INFORMATION IN ACCORDANCE WITH
 FBC-M 603.1.
  
 2. PAGE M-1.0: DOES THE EXISTING BATHROOM WITHIN
 CLASSROOM #2 HAVE AXHAUST AS REQUIRED BY FBC-M TABLE
 403.3?
  
 3. PAGE M-1.0: THE VENTILATION SCHEDULE INDICATES THERE
 ARE 3 ZONES ON FLOOR PLAN. THERE IS NO INDICATION AS TO
 WHERE THESE ZONES ARE LOCATED. ALSO, THE FLOOR PLAN
 SHOWS THERE ARE 4 MECHANICAL SYSTEMS AND NOT 3. PLEASE
 PROVIDE A VENTILATION CALCULATION WITH SPACE-BY-SPACE
 OCCUPANCY CLASSIFICATIONS, OCCUPANT LOADS, VENTILATION
 RATES REQUIRED PER OCCUPANT AND TOTAL VENTILATION
 REQUIRED. ALSO PLEASE INDICATE HOW MANY CFM EACH
 INDIVIDUAL HVAC SYSTEM WILL PROVIDE TO MEETH THESE
 VENTILATION REQUIREMENTS. THIS INFORMATION IS NEEDED TO
 DEMONSTRATE COMPLIANCE WITH FBC-EB SECTION 909 FOR
 CHANGE OF OCCUPANCY AND FBC-M SECTION 403.
  
 4. SHOW BALANCED RETURN FROM BREAKOUT ROOM PER FBC-M
 601.4.
  
 5. PAGE A-1.0 SHOWS 1-HOUR FIRE RATED WALLS ON THE
 FLOOR PLAN. PAGE M-1.0 SHOWS SEVERAL DUCT PENETRATIONS
 OF THESE RATED WALLS. SHOW HOW THESE PENETRATIONS ARE
 TO BE PROTECTED IN ACCORDANCE WITH FBC-M 607.5. THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 AND/OR SMOKE DAMPER SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE DESIGNER IN
 ACCORDANCE WITH FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By dwise Date 2009-07-09 Time 22:06 Rev Time 0.00
Received By dwise Date 2009-07-09 Time 22:05 Sent To FIRE
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-29 Cont ID  
Sent By kstevens Date 2009-05-29 Time 15:55 Rev Time 0.00
Received By kstevens Date 2009-05-29 Time 15:55 Sent To  
Notes
2009-05-29 16:35:53DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
 FBC-2007 CHAPTER 1 (ADMIN)
 MUNICIPAL CODE WPB
  
 1. SUBMIT AN EXISTING FLOOR PLAN TO VERIFY THE EXTENT
 OF ALTERATION. SECTION 106.1.2 (MORE INFORMATION
 REQUIRED).
  
 2. SHT A1.0 THE DRINKING FOUNTAIN SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 3. SHT A1.0 THE LUNCH ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 4. SHT A1.0. THE SHOWER IS INDICATED AS A NEW SHOWER ON
 SHT PB-1.0. AS A NEW SHOWER IT SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.21 WITH ALL SUBSECTIONS. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED). ALSO A TURNING AREA IS REQUIRED
 IN THE SHOWER AREA PER SECTION 11-4.22.3.
  
 5. SUBMIT DETAILS SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 ___FOR W/C'S:
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 ___FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 D. 11-4.19.6 MIRRORS.
 ___FOR TOILET ROOMS
 A. 11-4.22.3 TURNING AREAS
  
 6. A WATER ISOMETRIC RISER DIAGRAM IS REQUIRED PER
 SECTION 106.3.5.1.3(3)(8)(10)(13). PLEASE SUBMIT RISER
 SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY
 SECTION 604.9) HATER HAMMER ARRESTORS. SECTION 608.
  
 7. THE SANITARY ISOMETRIC RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. BOTH WATER CLOSETS AND THE WASH
 MACHINE ARE NOT VENTED AS SHOWN. SECTION 901.2.1. --
 THE BRANCH TO THE WASH MACHINE SHALL BE 3" PER SECTION
 406.3. -- THE INDIRECT WASTE FOR THE CONDENSATE SHALL
 NOT DRAIN INTO THE SANITARY WASTE DRAIN PER ARTICLE III
 SECTION 90-125(5). CONDENSATE SHALL DRAIN TO SEPARATELY
 OUT THE BUILDING AND CONNECT TO STORM, DRAIN INTO A
 DRYWELL OR INTO A PLANTED AREA. IF CONNECTING TO STORM
 THE CONDENSATE SHALL HAVE A RELIEF VENT (GOOSENECK) AS
 THE DRAIN EXITS THE BUILDING. (SEE RED LINE EXAMPLES OF
 CORRECTIONS FOR THE VENTING ON ONE SET OF PLANS).
  
 8. SUBMIT A DETAIL FOR THE SUSPENDED WATER HEATER.
 INDICATE HOW THE WATER HEATER WILL BE SUPPORTED, WHERE
 THE P/T & PAN DRAIN DISCHARGE LINES TERMINATE, SHOW HOW
 THE THERMAL EXPANSION CONTROL IS ADDRESSED, SHUT OFF
 VALVES ETC. SECTIONS 106.1.2, 504.6,504.7.2, 606.1 &
 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-05-21 Cont ID  
Sent By kdfreema Date 2009-05-21 Time 10:32 Rev Time 0.00
Received By kdfreema Date 2009-05-21 Time 10:32 Sent To  
Notes
***NONE***