Plan Review Details - Permit 09050318
Plan Review Stops For Permit 09050318
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By dwise Date 2009-06-25 Time 20:56 Rev Time 0.00
Received By dwise Date 2009-06-25 Time 20:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 09:40 Rev Time 0.00
Received By shill Date 2009-06-15 Time 09:40 Sent To  
Notes
2009-06-15 09:47:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DECLARE WIND DESIGN CRITERIA, FBC1603.
  
 2. PROVIDE ATTACHMENT DETAILS TO SHOW HOW EXTERIOR
 EQUIPMENT AND DUCTS WILL RESIST WIND LOADS FBC1609.
  
 3. PROVIDE CALCULATIONS TO SHOW THAT THE EXISTING
 FLOOR/CEILING CAN SUPPORT THE LOADS CREATED BY THE NEW
 EQUIPMENT/DUCTS IN ADDITION TO OTHER DEAD AND LIVE
 LOADS. WHAT OCCUPANCY IS ON THE SECOND FLOOR (FBC
 CHAPTER 3)?
  
 4. PLEASE CLARIFY EXISTING CONDITONS. HOOD HANGING
 DETAIL (SHEET 3) SHOWS TRUSSES; SECTIONS SHOW "2X10
 WOOD STUDS;" DO YOU MEAN JOISTS? "STUDS" ARE INSTALLED
 VERTICALLY (COMPONENT OF A FRAME WALL). IT IS NOT CLEAR
 IF FLOOR JOISTS OR FLOOR TRUSSES ARE EXISTING.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-06-30 Cont ID  
Sent By mawillia Date 2009-06-30 Time 12:33 Rev Time 0.00
Received By mawillia Date 2009-06-30 Time 12:14 Sent To  
Notes
2009-06-30 12:33:32*****APPROVED*****
  
  
 PLAN SHEETS 1 THRU 3 (OF 6) WERE STAMPED, INITIALED,
 AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-19 Cont ID  
Sent By btrobaug Date 2009-06-19 Time 15:07 Rev Time 0.00
Received By btrobaug Date 2009-06-19 Time 15:07 Sent To B
Notes
2009-06-19 15:08:27TO DOUG'S DESK./WRT,

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-15 Cont ID  
Sent By shill Date 2009-06-15 Time 09:53 Rev Time 0.00
Received By shill Date 2009-05-15 Time 11:34 Sent To  
Notes
2009-05-15 11:35:10SENT TO MECH

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By dwise Date 2009-06-25 Time 20:55 Rev Time 0.00
Received By dwise Date 2009-06-25 Time 20:55 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-29 Cont ID  
Sent By rregueir Date 2009-05-29 Time 14:23 Rev Time 0.00
Received By rregueir Date 2009-05-29 Time 13:02 Sent To  
Notes
2009-05-29 14:23:39REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. GREASE EXHAUST DUCTS SHALL BE FLANGED, GASKETED AND
 BOLTED TO THE INLET AND OUTLET OF THE FAN FOR IN-LINE
 FANS IN ACCORDANCE WITH FBC-M 506.3.2.3.
  
 2. DUCTS EXPOSED TO THE OUTSIDE ATMOSPHERE OR SUBJECT
 TO A CORROSIVE ENVIRONMENT SHALL BE PROTECTED AGAINST
 CORROSION IN AN APPROVED MANNER IN ACCORDANCE WITH
 FBC-M 506.2.
  
 3. A GREASE DUCT TEST IS REQUIRED FOR ALL JOINTS AND
 SEAMS IN THE PRESENCE OF THE CODE OFFICIAL IN
 ACCORDANCE WITH FBC-M 506.3.2.5. THE PROPOSED LOCATION
 OF THE DUCT WILL REQUIRE INSPECTION OF THE EXTERIOR
 DUCT PRIOR TO INSTALLATION. COORDINATE WITH FIELD
 INSPECTOR.
  
 4. PROVIDE STRUCTURAL CALCULATIONS FOR BUILDING PLAN
 REVIEW SHOWING THE EXISTING FLOOR/CEILING ASSEMBLY IS
 CAPABLE OF SUPPORTING ADDITIONAL LOADS ASSOCIATED WITH
 THE PROPOSED HOOD, DUCTWORK, WRAP AND PERSONNEL WORKING
 ON THE HOOD IN ACCORDANCE WITH FBC-M 506.3.3 AND 507.6.
  
 5. PROVIDE MANUFACTURERS OR OTHER SUPPORTING DATA
 SHOWING SUPPLY AND EXHAUST FANS ARE DESIGNED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. SEPARATE
 BUILDING PLAN REVIEW ALSO REQUIRED FOR THE WIND
 RESISTANCE CAPABILITIES OF FAN AND DUCT SUPPORTS.
  
 6. SUPPLY FAN APPEARS TO BE FACING THE REAR PARKING LOT
 OF THE BUILDING. MAKEUP AIR INTAKE OPENING LOCATIONS
 SHALL COMPLY WITH FBC-M SECTIONS 401.4 AND 401.4.1
  
 NOTE: SEPARATE PERMIT FOR FIRE SUPPRESSION SYSTEM
 REQUIRED PER FBC-M 509.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-30 Cont ID  
Sent By aaponte Date 2009-06-30 Time 17:12 Rev Time 0.00
Received By aaponte Date 2009-06-30 Time 17:12 Sent To  
Notes
2009-06-30 17:13:27PROVISO: DUCTS EXPOSED TO THE OUTSIDE SHALL BE PAINTED
 IN THE SAME COLOR THAN THE REAR FACADE.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-06-03 Cont ID  
Sent By aaponte Date 2009-06-03 Time 17:26 Rev Time 0.00
Received By aaponte Date 2009-06-03 Time 17:26 Sent To  
Notes
***NONE***