Plan Review Details - Permit 09050234
Plan Review Stops For Permit 09050234
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By rmcdouga Date 2009-06-25 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2009-06-25 Time 16:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By rmcdouga Date 2009-05-20 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2009-05-20 Time 15:45 Sent To  
Notes
2009-05-20 15:45:522007 FBC R
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND EVALUATION REPORTS FOR THE SPRAY
 FOAM INSULATION. PROVIDE FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE FOAM INSULATION. PROVIDE TWO SETS OF
 PLANS WITH WALL SECTIONS INDICATING THE LOCATION AND
 R-VALUE OF THE NEW INSULATION. FBC R314.5.3
  
 2) SUBMIT TWO SETS OF PLANS SHOWING THE LOCATION, SIZES
 AND TYPES OF WINDOWS AND DOORS THAT ARE BEING REPLACED.
 R301.2.1
  
 3) SUBMIT TWO SETS OF PLANS SHOWING THE LOCATION, TYPE
 AND THE AMOUNT OF SIDING THAT IS BEING REPLACED. IF THE
 SIDING IS BEING REPLACED WITH CEMENT BOARD TYPE SIDING
 SUCH AS HARDI-BOARD, SUBMIT TWO COPIES OF PRODUCT
 APPROVALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2009-05-13 08:19:02INCOMING TO R-11

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-06-15 Cont ID  
Sent By dpalmer Date 2009-06-15 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2009-06-15 Time 16:38 Sent To  
Notes
2009-06-15 16:38:53 
  
  
 ** REDLINED PLANS *
  
 1) NOTE: RECEPT AND CIRCUIT REQUIRED FOR WASHER/LAUNDRY
 PER 210.52F,210.11C2. THIS MUST BE IN ADDITION TO THE
 STACK WASHER/DRYER CIRCUIT/RECEPT.
  
 2) NOTE: ANY LOW VOLTAGE SYSTEM SUCH AS PHONE, CATV,
 SPEAKERS ETC SHALL BE UNDER SEPARATE PERMIT(S). LOW
 VOLTAGE FOR ANY SECURITY IS ALSO UNDER SEPARATE PERMIT.
  
 REDLINED THE FOLLOWING.
 210.52,210.8A6,410.8, 408.4 ETC SEE PLANS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-18 Cont ID  
Sent By dpalmer Date 2009-05-18 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2009-05-18 Time 13:28 Sent To  
Notes
2009-05-18 13:28:56**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE
 DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES.
 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE
 DETECTORS.
 SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO
 NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY
 THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED
 SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS.
  
  
 2) NOTE: THE RECEPTACLE SPACING ALONG KITCHEN COUNTER
 SPACE DOES NOT MEET 210.52C1. WITHIN 2FT OF THE END OF
 A COUNTER EDGE, AND 4FT THERE AFTER. SEE WALL/COUNTER
 SPACE IN WHICH THIS DOE NOT MEET SECTION GIVEN.
  
 3) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES IN
 KITCHEN SHALL BE GFI/GFI PROTECTED. PLEASE SHOW.
  
 4) NOTE: PLEASE SEE 210.52F FOR MISSING WASHER/LAUNDRY
 CIRCUIT. PLEASE ALSO SEE 220.52 FOR REQUIRED VA TO BE
 FIGURED.
  
 5) NOTE: PLEASE SEE NEC 220 FOR LOAD CALCULATIONS. THE
 SUBMITTED CALCULATIONS DO NOT DEPICT ANY LOAD
 CALCULATIONS OUT OF THE NEC.
 PLEASE ALSO SEE 4220.13 FOR WATER HEATERS AS LOADS ARE
 FIGURED AT 125%.
  
 5) NOTE: THE RISER INDICATES THE UNDERGROUND TO A
 HAND-HOLE. BEING THE CASE THIS WOULD REQUIRE THE
 CONDUCTORS TO FALL UNDER THE NEC AND 310.16, 310.15B6.
 PLEASE INCLUDE CONDUCTORS.
  
 6) NOTE: PLEASE INCLUDE AIC RATING FOR NEW SERVICE
 EQUIPMENT. 110.9
  
 7) NOTE: PLEASE SEE 210.52E AND 210.8A3 FOR THE
 REQUIRED MISSING FRONT AND REAR GFI RECEPTACLES.
  
 8) NOTE: PLEASE SEE FS 481.229 AND 471.003 WHEN MEETING
 THE EXCEPTIONS IN THE STATUTES FOR DESIGN PROFESSIONAL,
 THE DESIGNER OF RECORD SHALL PRINT AND SIGN NAME TAKING
 RESPONSIBILITY OF SAID PLANS.
  
 9) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL
 LOCATIONS IN WHICH THE RECEPTACLE SPACE FOR WALL AREAS
 NEEDS TO BE ADJUSTED.
  
 10) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER/DISPOSAL
 WHEN BEING FED TO THE SAME YOKE SHALL BE ON A 2-POLE
 BREAKER.
  
 11) NOTE: PLEASE SHOW LOCATION OF MISSING DISCONNECT
 FOR THE AHU. 440.12 AND 440.14
  
 12) NOTE: PLEASE SEE 210.63 FOR MISSING ATTIC SPACE
 LIGHT REQUIRED.
  
 13) NOTE: PLEASE LIST ANY RECESSED TYPE LIGHT FIXTURES
 TO MEET FBC 13-606.AB.1.2.3.4
  
 14) NOTE: PLEASE SUBMIT TWO COPIES OF PLANS. FBC 106.1,
 106.1.1
  
 15) NOTE: PLEASE COORDINATE ELECTRICAL WITH MECHANICAL
 PLANS. ONE SHOWS 10KW AND THE OTHER 8KW. PLEASE KNOW
 THAT THIS WILL AFFECT THE OVER CURRENT PROTECTION IF
 THIS IS 8KW AS THE OCP ON PANEL IS SHOWN AS 60AMP WHICH
 MAY BE TOO HIGH. SEE 424.3B.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-11 Cont ID  
Sent By rregueir Date 2009-06-11 Time 13:09 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 13:09 Sent To  
Notes
2009-06-11 13:11:58TO R-11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-05-27 Time   Rev Time 0.00
Received By jwitmer Date 2009-05-13 Time 08:17 Sent To  
Notes
2009-05-13 08:18:11INCOMING TO :R-11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-01 Cont ID  
Sent By rmcdouga Date 2009-07-01 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2009-07-01 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By rmcdouga Date 2009-05-20 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2009-05-20 Time 14:35 Sent To  
Notes
2009-05-20 14:46:592007 FBC R
  
 MECHANICAL DENIED
  
 1) SPECIFY THE SIZE OF THE RETURN AIR DUCTS. M1602.4
  
 2) SHOW COMPLIANCE WITH M1305.1.3 APPLIANCES IN ATTICS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By rmcdouga Date 2009-06-25 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2009-06-25 Time 16:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By rmcdouga Date 2009-05-20 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2009-05-20 Time 15:07 Sent To  
Notes
2009-05-20 15:19:282007 FBC R
  
 PLUMBING DENIED
  
 1) SPECIFY THE SCOPE OF PLUMBING WORK THAT WILL BE
 DONE.
  
 2) IF KITCHEN OR BATHROOMS ARE BEING RECONFIGURED AND
 LOCATIONS OF PLUMBING FIXTURES ARE BEING CHANGED,
 SUBMIT TWO COPIES OF FLOOR PLANS WITH DIMENSIONS AND
 SANITARY RISER DIAGRAMS. FBC R CHAPTERS 25-33.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By mcruz Date 2009-06-22 Time 13:20 Rev Time 0.00
Received By mcruz Date 2009-06-22 Time 12:57 Sent To  
Notes
2009-06-22 13:21:03PLACED BACK IN R11

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-27 Cont ID  
Sent By mcruz Date 2009-05-27 Time 12:47 Rev Time 0.00
Received By mcruz Date 2009-05-27 Time 12:33 Sent To  
Notes
2009-05-27 12:47:19PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. BASED ON THE ELECTRICAL DETAIL, IT APPEARS THE
 PROPOSED CONDENSOR UNIT IS GOING TO BE PLACED ON THE
 EAST SIDE OF THE PROPERTY.
  
 PLEASE INDICATE ON THE SURVEY THE SETBACK DIMENSIONS
 FROM PROPOSED A/C EQUIPMENT TO ALL ADJACENT PROPERTY
 LINES. PURSUANT THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  