Plan Review Details - Permit 09050222
Plan Review Stops For Permit 09050222
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-08-19 Cont ID  
Sent By kstevens Date 2009-08-17 Time 09:20 Rev Time 0.00
Received By kstevens Date 2009-08-17 Time 09:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-07-22 Cont ID  
Sent By kstevens Date 2009-07-22 Time 18:05 Rev Time 0.00
Received By kstevens Date 2009-07-22 Time 18:05 Sent To  
Notes
2009-07-22 18:19:20DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 FUEL GAS
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE. - THE DRAWING IS NOT IN ISOMETRIC FORM
 AND DOES NOT SHOW THE LENGTHS OF EACH CUT SECTION. THE
 DRAWING DOES NOT REFLECT THE PIPING SHOWN ON THE FLAT
 DRAWING.
 ****NO RESPONSE, COMMENT NOT ADDRESSED. NOT ALL LENGHTS
 SHOWN. -- SEE EXAMPLE OF RISER DIAGRAM IN ISOMETRIC
 FORM.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - PIPING
 MATERIAL IS NOT INDICATED ON THE RISER DIAGRAM AND NOT
 ALL PIPING IS INDICATED ON THE FLAT DRAWING.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1/G2412.8 THRU G2413.6.1. AND TABLES
 402.4(1) THRU
 402.4(35)/G2413.4(1) THRU G2413.4(8). - THE BTU LOAD
 FOR THE FUTURE GENERATOR IS NOT SHOWN OR ADDED TO THE
 TOTAL BTU LOAD.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.-- THE MANUF.
 SHEET FOR THE RANGE INDICATES THE LOAD AT 140,000
 BTU'S, (6 BURNERS @ 18,000 EACH, 1 GRIDDLE @ 18,000 & 1
 GRILL @ 14,000), BUT THE PLANS INDICATE ONLY 100,000
 BTU'S . THERE IS NO BTU LOAD INDICATED FOR THE
 GENERATOR. PLEASE CORRELATE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN
 COMMENT 1 IS ADDRESSED.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & G2407.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 & G2413.2.
 ****RESPONSE NOTED, ALL FUTURE APPLIANCES SHALL BE
 INDICATED AS SUCH ON THE ISOMETRIC. A SEPARATE PERMIT
 WILL BE REQUIRED WHEN THE APPLIANCES ARE INSTALLED.
  
 B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-05-13 Cont ID  
Sent By kstevens Date 2009-05-13 Time 08:21 Rev Time 0.00
Received By kstevens Date 2009-05-12 Time 16:54 Sent To  
Notes
2009-05-13 08:43:38DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 FUEL GAS
 FBC-2007 RESIDENTIAL
 FBC-2007 CHAPTER 1
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE. - THE DRAWING IS NOT IN ISOMETRIC FORM
 AND DOES NOT SHOW THE LENGTHS OF EACH CUT SECTION. THE
 DRAWING DOES NOT REFLECT THE PIPING SHOWN ON THE FLAT
 DRAWING.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. - PIPING
 MATERIAL IS NOT INDICATED ON THE RISER DIAGRAM AND NOT
 ALL PIPING IS INDICATED ON THE FLAT DRAWING.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1/G2412.8 THRU G2413.6.1. AND TABLES
 402.4(1) THRU
 402.4(35)/G2413.4(1) THRU G2413.4(8). - THE BTU LOAD
 FOR THE FUTURE GENERATOR IS NOT SHOWN OR ADDED TO THE
 TOTAL BTU LOAD.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED WHEN
 COMMENT 1 IS ADDRESSED.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & G2407.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 & G2413.2.
  
 B. 108.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION
 OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. - THE VALUATION OF $2,200.00 FOR ALL THE
 APPLIANCES, THE PIPING & LABOR APPEARS TO BE LOW.
 PLEASE INDICATE THE TOTAL COAST OF THE JOB.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved