Plan Review Details - Permit 09050216
Plan Review Stops For Permit 09050216
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By rmcdouga Date 2009-07-09 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2009-07-09 Time 09:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 11:47 Rev Time 0.00
Received By rmcdouga Date 2009-06-11 Time 11:47 Sent To  
Notes
2009-06-11 12:23:082007 FBC
 INSTALL LP GENERATOR
  
 DENIED BY BUILDING
  
 1) SPECIFY LARGER ANCHORS WITH MORE EMBED DEPTH OR
 PROVIDE SIGNED AND SEALED CALCULATIONS FROM A FLORIDA
 LICENSED ENGINEER WHICH SHOW THAT THE FOUR 5/16" X
 1-3/4" ANCHORS ARE ADEQUATE TO RESIST 140 MPH WINDLOAD
 FORCES FOR OVERTURNING, SLIDING AND UPLIFT AS REQUIRED
 BY FBC 1604.9.
  
 2) AS THE GENERATOR IS LOCATED AT THE CARPORT, SPECIFY
 THE PROTECTION THAT WILL BE PROVIDED. SEE FBC M303.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-05-27 Cont ID  
Sent By btrobaug Date 2009-05-27 Time 11:11 Rev Time 0.00
Received By btrobaug Date 2009-05-27 Time 10:54 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By kstevens Date 2009-07-10 Time 09:21 Rev Time 0.00
Received By kstevens Date 2009-07-10 Time 09:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-06-10 Cont ID  
Sent By kstevens Date 2009-06-10 Time 11:50 Rev Time 0.00
Received By kstevens Date 2009-06-10 Time 11:50 Sent To B
Notes
2009-06-10 11:52:51GAS PLANS APPROVED, BUT STATUS WILL REMAIN FAILED
 UNTILL THE MINIMUM 3' CLEARANCE IS SHOWN BETWEEN THE
 ONE STORY BUILDING AND THE GENERATOR. NFPA 70.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-04 Cont ID  
Sent By dpalmer Date 2009-07-04 Time 10:37 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 10:37 Sent To  
Notes
2009-07-04 10:38:27ROUTED TO RMCD.
  
 RESUBMITTED PLANS GO TO REVIEWERS SPECIFICALLY. TO BE
 ROUTED TO KS FOR P RESULT ONCE OK WITH OTHER TRADESL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-01 Cont ID  
Sent By kstevens Date 2009-07-01 Time 08:54 Rev Time 0.00
Received By kstevens Date 2009-07-01 Time 08:54 Sent To  
Notes
2009-07-01 08:55:00TO GEN-RES BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 13:23 Rev Time 0.00
Received By rmcdouga Date 2009-05-13 Time 09:13 Sent To  
Notes
2009-05-13 09:13:42INCOMING TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By rmcdouga Date 2009-07-09 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2009-07-09 Time 09:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-11 Cont ID  
Sent By rmcdouga Date 2009-06-11 Time 13:18 Rev Time 0.00
Received By rmcdouga Date 2009-06-11 Time 13:18 Sent To  
Notes
2009-06-11 13:19:492007 FBC
 INSTALL LP GENERATOR
  
 DENIED
  
 1) THE GENERATOR IS LOCATED IN A LOCATION THAT IS
 SUBJECT TO MECHANICAL DAMAGE, WHICH REQUIRES IT TO BE
 PROTECTED BY APPROVED BARRIERS. PROVIDE DETAILS OF THE
 THE PROTECTION THAT WILL BE PROVIDED. SEE FBC M303.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2009-07-09 Cont ID  
Sent By mcruz Date 2009-07-09 Time 11:59 Rev Time 0.00
Received By mcruz Date 2009-07-09 Time 11:59 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-05-19 Cont ID  
Sent By mcruz Date 2009-05-19 Time 10:56 Rev Time 0.00
Received By mcruz Date 2009-05-19 Time 10:48 Sent To E
Notes
2009-05-19 10:56:17PLACED IN ELEC BOX.