Plan Review Details - Permit 09050056
Plan Review Stops For Permit 09050056
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-10-21 Cont ID  
Sent By jwitmer Date 2009-10-21 Time 10:48 Rev Time 0.45
Received By jwitmer Date 2009-10-21 Time 10:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-18 Cont ID  
Sent By jwitmer Date 2009-08-18 Time 10:52 Rev Time 0.36
Received By jwitmer Date 2009-08-18 Time 10:40 Sent To  
Notes
2009-08-18 10:56:50BUILDING PLAN REVIEW
 PERMIT: 09050056
 ADD: 205 N DIXIE HWY
 CONT: M.A.C. CONSTRUCTION, INC
 TEL: (786) 236-1006
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 AUGUST 18/2009
  
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED THREE OR
 MORE TIMES FOR REPEATED FAILURE TO CORRECT A CODE
 VIOLATION.
 SAME SHEETS SUBMITTED UNDER THE FIRST REVIEW< NO
 CHANGES!
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 & 2007 FLORIDA EXISTING BUILDING
 CODE WITH
 2009 SUPPLEMENTS. PLEASE PROVIDE LEVEL OF ALTERATION.
 2007 EXISTING BUILDING CODE 401.4 A DESIGN PROFESSIONAL
 OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE. PLEASE UPDATE YOUR CODE REFRENECES.
  
 2) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503, CHAPTER 6,& TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 3) PLANS FAIL TO PROVIDE MANUFACTURERS INFORMATION FOR
 FLOOR LOADING, TABLE 1607.1 COMPUTER ROOMS SHALL BE
 DESIGNED FOR HEAVIER LOADS BASED ON THE ANTICIPATED
 OCCUPANCY.
 PLEASE PROVIDE FLOOR LOADING FOR THE RAISED FLOOR
 LOADING AS WELL AS THE STRUCTURAL SLAB.
  
 4) PLANS INDICATE THE USAGE OF THIS ROOM TO BE A IT
 ROOM, NFPA 75 AND NEC 645.2 BOTH REQUIRE RATED WALLS.
 PLANS DO NOT INDICATE ANY RATING OF THE WALLS OR
 THROUGH PENETRATIONS. 712.3.1 THROUGH PENRTRATIONS.
  
 5) SHEET A-1 INDICATES A PAIR OF NEW DOORS BUT NO
 RATING INFORMATION, OPENING PROTECTIVES TABLE 715.3.
  
 NEW COMMENT:
 6) BRIDGE DESIGN CONSULTING ENGINEERS- ONE SET OF FLOOR
 LOADING DOCUMENTS IS A COPY NOT ORIGINAL SIGNATUE NOR
 SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE: NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING (471.025 F.S.
 AND 471.023 F.S.).
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 13:21 Rev Time 1.11
Received By jwitmer Date 2009-05-14 Time 12:41 Sent To  
Notes
2009-05-14 14:18:05BUILDING PLAN REVIEW
 PERMIT: 09050056
 ADD: 205 N DIXIE HWY
 CONT: M.A.C. CONSTRUCTION, INC
 TEL: (786) 236-1006
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 & 2007 FLORIDA EXISTING BUILDING
 CODE WITH
 2009 SUPPLEMENTS. PLEASE PROVIDE LEVEL OF ALTERATION.
 2007 EXISTING BUILDING CODE 401.4 A DESIGN PROFESSIONAL
 OR AN OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS
 OF ALTERATION PURSUANT TO SECTIONS 403, 404 AND 405 OF
 THIS CODE. PLEASE UPDATE YOUR CODE REFRENECES.
  
 2) 10.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503, CHAPTER 6,& TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
  
 3) PLANS FAIL TO PROVIDE MANUFACTURERS INFORMATION FOR
 FLOOR LOADING, TABLE 1607.1 COMPUTER ROOMS SHALL BE
 DESIGNED FOR HEAVIER LOADS BASED ON THE ANTICIPATED
 OCCUPANCY.
 PLEASE PROVIDE FLOOR LOADING FOR THE RAISED FLOOR
 LOADING AS WELL AS THE STRUCTURAL SLAB.
  
 4) PLANS INDICATE THE USAGE OF THIS ROOM TO BE A IT
 ROOM, NFPA 75 AND NEC 645.2 BOTH REQUIRE RATED WALLS.
 PLANS DO NOT INDICATE ANY RATING OF THE WALLS OR
 THROUGH PENETRATIONS. 712.3.1 THROUGH PENRTRATIONS.
  
 5) SHEET A-1 INDICATES A PAIR OF NEW DOORS BUT NO
 RATING INFORMATION, OPENING PROTECTIVES TABLE 715.3.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 13:34 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 13:34 Sent To  
Notes
2009-10-10 13:36:20STAMPED PLANS,
  
 ALL LV, FS, FA ARE UNDER SEPARATE PERMITS.
 NO LOW VOLTAGE INCLUDED IN ON THIS PERMIT. MUST HAVE
 SEPARATE PERMIT HOWEVER MAY REFERENCE THESE PLANS FOR
 LOW VOLTAGE SCOPE AS SHOWN.
 FS AND FA REQUIRES SEPARATE PLANS SEE FIRE MARSHAL
 REVIEW/STAMPS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 14:10 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 14:10 Sent To  
Notes
2009-08-21 14:13:02** DENIED 2ND REVIEW.
  
 1) NOTE: SAME PLANS SUBMITTED BACK FOR REVIEW WITHOUT
 ANY CHANGES. SEE FS 553.80(2)(B).
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 12:09 Sent To  
Notes
2009-05-15 12:09:52**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FS 553.73 AS ALL PROJECTS SUBMITTED
 FOR PERMIT AFTER MARCH 1ST, 2009 SHALL BE UNDER THE
 FOLLOWING CODES.
 PLEASE SEE FAC 69A-60.004 AS NFPA-101 AND NFPA-1 2006
 EDITIONS WERE REVISED AND ADOPTED AS OF DECEMBER 31,
 2009.
 E101 INDICATES SOME OF THE OLDER CODES.
 PLEASE BE SURE PLANS STATE THE FOLLOWING:
  
 2007 FBC W/2009 REVISIONS.
 2006 NFPA-101
  
 SOME OTHERS SUCH AS 2005 NFPA-70 ARE OK ALONG WITH 2003
 NFPA-75 AND 2002 NFPA-72
  
 2) NOTE: PLEASE SEE BUILDING REVIEW NOTES FOR RATINGS
 FOR WALLS NEED TO BE INDICATED. IN ORDER TO USE THE
 WIRING METHODS IN NEC 645, THE LOCATION SHALL MEET ALL
 ITEMS LISTED IN NEC 645.4 (1-5). IF ALL ITEMS ARE NOT
 PROVIDED THEN NO WIRING METHODS IN 645 ARE PERMITTED TO
 BE USED. THEN ALL WIRING SHALL BE DONE PER CHAPTERS
 1-4.
 PLEASE CONFIRM RATINGS.
  
 3) NOTE: PLEASE SEE FBC 13-415.AB.1.1, .1.2 AN D.1.3 AS
 ANY NEW LIGHTING CONTROLS SHALL MEET THE PRESCRIPTIVE
 REQUIREMENTS FOR NEW BEING INSTALLED.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B.5.1,
 13-415.B.1 FOR LIGHTING PERFORMANCE CALCULATIONS FOR
 PRESCRIPTIVE SPACE REQUIREMENTS.
  
 5) NOTE: PLEASE SHOW ALL LISTED WALL AND PENETRATION
 DETAILS PER 300.21.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-10-23 Cont ID  
Sent By mawillia Date 2009-10-23 Time 13:29 Rev Time 0.00
Received By mawillia Date 2009-10-23 Time 13:09 Sent To  
Notes
2009-10-23 13:25:09*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; PLAN SHEETS A-1, F/A-101, AND F-1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-08-21 Cont ID  
Sent By mawillia Date 2009-08-21 Time 11:45 Rev Time 0.00
Received By mawillia Date 2009-08-21 Time 10:50 Sent To  
Notes
2009-08-21 10:54:30*****DENIED*****
  
 IT APPEARS THAT THE SAME SHEETS FROM THE PREVIOUS
 REVIEW WERE SUBMITTED; THEREFORE THE FOLLOWING COMMENTS
 NOT ADDRESSED:
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED. ON SHEET E-101 IN SECTION F (CODES &
 STANDARDS), AMEND NFPA 101 TO REFLECT THE CURRENT
 EDITION.
  
 2. ON SHEET F/A-101, EXPLAIN VERBAGE " USE THOSE THAN
 APPLY" IN THE FIRE ALARM SYSTEM LEGEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By mawillia Date 2009-05-20 Time 15:16 Rev Time 0.00
Received By mawillia Date 2009-05-20 Time 14:45 Sent To  
Notes
2009-05-20 15:14:00*****DENIED*****
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED. ON SHEET E-101 IN SECTION F (CODES &
 STANDARDS), AMEND NFPA 101 TO REFLECT THE CURRENT
 EDITION.
  
 2. ON SHEET F/A-101, EXPLAIN VERBAGE " USE THOSE THAN
 APPLY" IN THE FIRE ALARM SYSTEM LEGEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-01-11 Cont ID  
Sent By dpalmer Date 2010-01-11 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2010-01-11 Time 14:54 Sent To P
Notes
2010-01-11 14:55:14PLUMB REV TO P IN BOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-11-10 Cont ID  
Sent By shill Date 2009-11-10 Time 11:24 Rev Time 0.00
Received By shill Date 2009-11-10 Time 11:24 Sent To  
Notes
2009-11-10 11:28:24TO KS DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-30 Cont ID  
Sent By jgomez Date 2009-09-30 Time 09:44 Rev Time 0.00
Received By jgomez Date 2009-09-30 Time 09:44 Sent To  
Notes
2009-09-30 09:44:53SENT TO COMMERCIAL BOX #38.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-10 Cont ID  
Sent By lmartine Date 2009-08-10 Time 14:04 Rev Time 0.00
Received By lmartine Date 2009-08-10 Time 14:04 Sent To  
Notes
2009-08-10 14:07:37C-5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By mawillia Date 2009-05-20 Time 14:45 Rev Time 0.00
Received By mawillia Date 2009-05-05 Time 17:09 Sent To  
Notes
2009-05-05 17:09:55TO C26

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-10-23 Cont ID  
Sent By rregueir Date 2009-10-23 Time 12:59 Rev Time 0.00
Received By rregueir Date 2009-10-23 Time 12:58 Sent To  
Notes
2009-10-23 12:59:51**PROVISO**
  
 1. PROVIDE CONDENSER MANUFACTURER'S WIND RESISTANCE
 DATA TO THE DEPARTMENT FOR PLAN REVIEW IN ACCORDANCE
 WITH FBC-M 301.12.
  
 2. PROVIDE FULL PRODUCT APPROVAL DOCUMENTATION TO FIELD
 INSPECTOR AT TIME OF INSPECTION PER FBC-B 106.3.3 AND
 FAC RULE 9B-72.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-08-14 Cont ID  
Sent By rregueir Date 2009-08-14 Time 15:19 Rev Time 0.00
Received By rregueir Date 2009-08-14 Time 15:04 Sent To  
Notes
2009-08-14 15:19:22SAME SHEETS SUBMITTED FROM PREVIOUS REVIEW. COMMENTS
 NOT ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 14:23 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 14:15 Sent To  
Notes
2009-05-15 14:23:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-4 SHOWS AN ALUMINUM STAND TO BE USED ON ROOF
 FOR NEW CONDENSING UNIT. PROVIDE ENGINEERING AND
 STRUCTURAL DETAIL FOR FIELD FABRICATED STAND SHOWING
 WIND RESISTANCE CAPABILITIES AND MEANS OF ATTACHMENT TO
 STRUCTURE IN ACCORDANCE WITH FBC-M 301.12. IF A
 PRE-ENGINEERED A/C STAND IS USED, PROVIDE PRODUCT
 APPROVAL WITH INSTALLATION INSTRUCTIONS PER FAC RULE
 9B-72.
  
 2. PROVIDE APPLIANCE MANUFACTURER'S DATA SHOWING THE
 CONDENSING UNIT IS DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 3. AIR HANDLER SHALL BE PROVIDED WITH AUXILIARY DRAIN
 PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3.
  
 4. AHU MOUNTED SMOKE DETECTOR SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM IN ACCORDANCE WITH FBC-M
 606.4.1.
  
 5. ALL NEW PIPING WHICH PENETRATES A RATED FLOOR OR
 WALL ASSEMBLY SHALL BE PROTECTED AS A
 THROUGH-PENETRATION IN ACCORANCE WITH FBC-B 712.3.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-11-16 Cont ID  
Sent By kstevens Date 2009-11-16 Time 10:41 Rev Time 0.00
Received By kstevens Date 2009-11-16 Time 10:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 16:13 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 16:13 Sent To  
Notes
2009-09-30 16:38:41DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 MUNICIPAL CODE CITY WPB
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN
 DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3
 DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO
 THE SANITARY DRAINAGE SYSTEM.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RESPONSE THAT THE FLOOR
 DRAIN IS CONNECTED TO THE SANITARY SYSTEM IS NOT WHAT
 IS SHOWN ON THE PLANS. THE PLAN SHOW ALL THE AHU & A/C
 UNITS DRAINING INTO THE EXISTING 2 INCH CONDENSATE
 LINE. CONDENSATE SHALL NOT DRAIN INTO THE SANITARY PER
 THE WEST PALM BEACH CITY CODE ARTICLE III SECTION
 90-125(5). PLEASE CLARIFY. IS THIS A CONDENSATE SYSTEM
 AS INDICATED OR A SANITARY SYSTEM IN WHICH CASE THE
 CONDENSATE SHALL NOT DRAIN INTO PER CITY CODE.
  
 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC
 UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION
 608. PLEASE INDICATE METHOD.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED. THE BACKFLOW SHALL BE INSTALLED A
 MAXIMUM 4 FEET ABOVE THE FLOOR FOR TESTING AND
 CERTIFICATION AND SHALL HAVE DRAIN LINE AND AN AIR GAP
 TO AN APPROVED INDIRECT WASTE RECEPTOR. MANUF
 INSTALLATION INSTRUCTIONS.SECTION 301.2.
  
 3. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-08-14 Cont ID  
Sent By kstevens Date 2009-08-14 Time 15:45 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 15:45 Sent To  
Notes
2009-08-14 15:47:04DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 MUNICIPAL CODE CITY WPB
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN
 DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3
 DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO
 THE SANITARY DRAINAGE SYSTEM.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC
 UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION
 608. PLEASE INDICATE METHOD.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 3. PLANS SHALL BE DESIGNED PER THE CURRENT CODE CYCLE
 WHICH IS FBC-2007 W/2009 SUPPLEMENTS. PLEASE INDICATE
 ON PLANS. SECTION 106.1.1.
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 16:08 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 16:08 Sent To  
Notes
2009-05-11 16:20:00DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 MUNICIPAL CODE CITY WPB
  
 1. SHT P-1 SHOWS EXISTING FIRE PROTECTION DRAIN
 DRAINING INTO THE CONDENSATE SYSTEM. PER SECTION 301.3
 DISCHARGE OF LIQUID WASTE OR SEWAGE SHALL CONNECT TO
 THE SANITARY DRAINAGE SYSTEM.
  
 2. SHT P-1 INDICATES NEW COLD WATER PIPING TO NEW AC
 UNIT CRU-3. BACKFLOW PROTECTION IS REQUIRED. SECTION
 608. PLEASE INDICATE METHOD.
  
 3. PLANS SHALL BE DESIGNED PER THE CURRENT CODE CYCLE
 WHICH IS FBC-2007 W/2009 SUPPLEMENTS. PLEASE INDICATE
 ON PLANS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  