Plan Review Details - Permit 09050005
Plan Review Stops For Permit 09050005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By jwitmer Date 2009-07-24 Time 10:45 Rev Time 1.25
Received By jwitmer Date 2009-07-24 Time 09:30 Sent To  
Notes
2009-07-24 10:27:18BUILDING PROVISOS:
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) R703.3 WOOD, HARDBOARD AND WOOD STRUCTURAL PANEL
 SIDING.
  
 R703.3.1 PANEL SIDING. JOINTS IN WOOD, HARDBOARD OR
 WOOD STRUCTURAL PANEL SIDING SHALL BE MADE AS FOLLOWS
 UNLESS OTHERWISE APPROVED. HORIZONTAL JOINTS IN PANEL
 SIDING SHALL BE LAPPED A MINIMUM OF 1 INCH (25 MM) OR
 SHALL BE SHIPLAPPED OR SHALL BE FLASHED WITH Z-FLASHING
 AND OCCUR OVER SOLID BLOCKING, WOOD OR WOOD STRUCTURAL
 PANEL SHEATHING.
  
 3) R 806 ROOF VENTILATION
 R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING
 AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE
 SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL
 AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50
 PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED
 VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN
 THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT
 LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS
 WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED
 BY EAVE OR CORNICE VENTS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-18 Cont ID  
Sent By jwitmer Date 2009-05-18 Time 11:15 Rev Time 4.00
Received By jwitmer Date 2009-05-18 Time 8:00 Sent To  
Notes
2009-05-18 12:01:27BUILDING PLAN REVIEW
 PERMIT: 09050005
 ADD: 308 COLONIAL RD
 CONT: UNDERHILL BLDG & ROOFING
 TEL: (561)379-3665
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009, 2007 FLORIDA EXISTING BUILDING CODE
 WITH 2009 SUPPLEMENTS, CHAPTER 10 ADDITIONS, PLEASE
 UPDATE PLANS, A2 & S2.
  
 2) FEES, STATE RADON FEES OF $4.62 ARE OWED.
  
 3) SHEET A-2 TYPICAL WALL SECTION IS MISSLABELED,
 INDICATES A TYPICAL GARAGE WALL SECTION, PLEASE CORRECT
 WITH TRAY CEILING AS INDICATED IN THE MASTER BEDROOM.
 PLANS ARE LACKING DETAILS FOR EAVE VENTING AND 1/2 HALF
 OF THE REQUIRED ROOF VENTING TO BE A MINIMUM OF 3'-0"
 ABOVE THE EAVE VENTS. R806.2.
  
 4) SHEET A-2 TYPICAL WALL SECTION, PLANS DO NOT
 INDICATE TTHE TYPICAL GABLE END WALL DETAILS. PLANS DO
 NOT INDICATE THE REQUIRED BRACING FOR THE GABLE END
 WALL TRUSS.
 BUILDING PROVISO; R502.1.3.2 BRACING. TRUSSES SHALL BE
 BRACED TO PREVENT ROTATION AND PROVIDE LATERAL
 STABILITY IN ACCORDANCE WITH THE REQUIREMENTS SPECIFIED
 IN THE CONSTRUCTION DOCUMENTS FOR THE BUILDING AND ON
 THE INDIVIDUAL TRUSS DESIGN DRAWINGS. IN THE ABSENCE OF
 SPECIFIC BRACING REQUIREMENTS, TRUSSES SHALL BE BRACED
 IN ACCORDANCE WITH TPI/WTCA BCSI.
  
 5) THE GABLE END WALL DOES NOT PROVIDE HOW THE
 HORIZONTAL JOINT IN THE T-111 SHEATHING WILL OCCUR,
 PLEASE PROVIDE COMPLIANCE WITH: R703.3.1 PANEL SIDING.
 JOINTS IN WOOD, HARDBOARD OR WOOD STRUCTURAL PANEL
 SIDING SHALL BE MADE AS FOLLOWS UNLESS OTHERWISE
 APPROVED. HORIZONTAL JOINTS IN PANEL SIDING SHALL BE
 LAPPED A MINIMUM OF 1 INCH (25 MM) OR SHALL BE
 SHIPLAPPED OR SHALL BE FLASHED WITH Z-FLASHING AND
 OCCUR OVER SOLID BLOCKING, WOOD OR WOOD STRUCTURAL
 PANEL SHEATHING.
  
 6) THE MEP SHEETS DO NOT INDICATE SMOKE DETECTORS IN
 THE NEW MASTER BEDROOM, PLEASE PROVIDE COMPLIANCE WITH:
 R313.1 SMOKE DETECTION AND NOTIFICATION. ALL SMOKE
 ALARMS SHALL BE LISTED IN ACCORDANCE WITH UL 217 AND
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CODE AND THE HOUSEHOLD FIRE WARNING EQUIPMENT
 PROVISIONS OF NFPA 72.
  
 HOUSEHOLD FIRE ALARM SYSTEMS INSTALLED IN ACCORDANCE
 WITH NFPA 72 THAT INCLUDE SMOKE ALARMS, OR A
 COMBINATION OF SMOKE DETECTOR AND AUDIBLE NOTIFICATION
 DEVICE INSTALLED AS REQUIRED BY THIS SECTION FOR SMOKE
 ALARMS, SHALL BE PERMITTED. THE HOUSEHOLD FIRE ALARM
 SYSTEM SHALL PROVIDE THE SAME LEVEL OF SMOKE DETECTION
 AND ALARM AS REQUIRED BY THIS SECTION FOR SMOKE ALARMS
 IN THE EVENT THE FIRE ALARM PANEL IS REMOVED OR THE
 SYSTEM IS NOT CONNECTED TO A CENTRAL STATION.
  
 R313.2 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-08-28 Cont ID  
Sent By dpalmer Date 2009-08-28 Time 08:46 Rev Time 0.00
Received By dpalmer Date 2009-08-27 Time 16:59 Sent To P
Notes
2009-08-28 08:47:52NEEDS RE-STAMPS FOR MECH AND PLUMBING AS SHEETS WERE
 CHANGED OUT AND THESE ARE ON THE SAME NEW SHEETS WITH
 ELECTRICAL.
2009-08-28 08:46:44 
 ** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. MAKE
 ADJUSTMENTS BEFORE INSPECTIONS
  
 1) NOTE: THE CONDENSING UNIT LOAD OVER CURRENT
 PROTECTION/BREAKER ON LOAD CALCULATIONS IS SHOWN AT
 2-25AMP HOWEVER PANEL SCHEDULE FOR THE SAME CU IS SHOWN
 AS 30AMP.
 THE AHU ON THE LOAD CALCULATIONS INDICATES A 30AMP
 BREAKER WHICH IS THE MINIMUM REQUIRED PER 424.3B.
 HOWEVER THE PANEL SCHEDULE FOR THE NEW AHU INDICATES A
 2-25AMP BREAKER. THESE SEEM TO HAVE BEEN REVERSED.
 LOADS ARE TO BE SHOWN PER 220.83B. NO DE-RATING IS
 PERMITTING WHEN ADDING TO AN EXISTING SERVICE.
  
 2) NOTE: THE RISER STILL INDICATES AN *EQUIPMENT
 GROUNDING CONDUCTOR* AHEAD OF 150AMP MAIN. THIS IS TO
 BE VIF AS IT SHOULD NOT BE INSTALLED. THIS CREATES
 OBJECTIONABLE CURRENTS PER 250.6, 250.24.
 THE RISER IS MISSING AN *EQUIPMENT GROUNDING CONDUCTOR
 FROM NEW 100AMP MAIN TO SUB PANEL *B*. AS REQUIRED PER
 250.24,250.110,250.122.
  
 3) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER LOAD
 NEEDS TO BE SHOWN AT 125%. ( SEE HANDBOOK AS THIS IS A
 CONTINUOUS LOAD FOR FEEDERS AND SERVICES UNDER THE 2005
 NEC.
  
 **** IMPORTANT:
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-31 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 15:45 Sent To  
Notes
2009-07-31 15:45:43** DENIED 2ND REVIEW **
  
 *** SOME COMMENTS FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING ALONG WITH SOME NEW NOTES BASED ON
 REVISED INFORMATION NOW SHOWN ON PLANS.
 ** IT IS RECOMMENDED A MEETING BE SET UP TO GO OVER
 COMMENTS.
  
 1) NOTE: PLANS NOW MENTIONS CARBON MONOXIDE DETECTORS
 INSIDE ALL NEW AND EXISTING SLEEPING ROOMS. PREVIOUS
 REVIEW DID NOT COMMENT ON THIS. THE COMMENT HAD TO DO
 WITH SMOKE ALARMS PER R313.1 AND NFPA-72. PLEASE SEE FS
 553.885 FOR LOCATION OF REQUIRED CARBON MONOXIDE
 DETECTOR WHICH IS ACTUALLY WITHIN 10FT LOCATED OUTSIDE
 THE SLEEPING ROOM.
  
 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS, PANEL
 SCHEDULES, BREAKERS AND CONDUCTORS FOR A/C EQUIPMENT IS
 STILL NOT COORDINATING. LOAD CALCULATIONS FOR EXAMPLE
 INDICATE 50AMP BREAKERS WITH #8 AWG CONDUCTORS FOR
 CONDENSING UNITS, YET THE ONE NEW CU ON PANEL SCHEDULE
 INDICATES #12 AWG WITH A 2-POLE 20AMP BREAKER. PLEASE
 LOOK UP THE MANUFACTURES RECOMMENDED OCP AND CIRCUIT
 SIZE.
 PLEASE SEE ANOTHER CONFLICT WITH MINIMUM AND MAXIMUM
 OVER CURRENT PROTECTION, AND CONDUCTORS IS WITH THE TWO
 HEAT STRIPS INDICATED ON THE LOAD
 CALCULATIONS/SCHEDULE.
 BOTH THE 7.5 KW AND 4KW HEAT ON LOAD/SCHEDULE STATES #6
 AWG AND 60AMP BREAKER. THIS IS NOT POSSIBLE FOR EITHER
 ONE. THE PANEL SCHEDULE FOR THE NEW AHU STATES 40AMP
 WITH #8 AWG WHICH DOES NOT COORDINATE. IN EITHER CASE
 PLEASE SEE 424.3B AND 422.11E3. THE TYPICAL MINIMUM
 OVER CURRENT PROTECTION SIZING IS 125% AND THE MAXIMUM
 IS 150%.
 ** PLEASE ALSO VERIFY THE FACT ONE UNIT IS INDICATING A
 4KW HEAT STRIP, THIS IS NOT KNOWN TO BE TYPICAL.
 ***** PLEASE ALSO SEE 422.12,220.60 ETC
 A/C LOADS FOR LOAD CALCULATIONS MAY BE DE-RATED HOWEVER
 WHEN FIGURING THE LARGER OF THE TWO LOADS, YOU USE THE
 ACTUAL LOAD BEFORE DE-RATING NOT THE LOAD AFTER
 DE-RATING.
 ** PLEASE ALSO CHECK THE KW LOADS SHOWN FOR THE
 CONDENSING UNITS, THESE SEEM TO BE HIGH.
  
  
 3) NOTE: THE PREVIOUS REVIEW MADE NOTE TO 210.52D FOR
 THE LOCATION OF THE GFI RECEPTACLE IN THE BATHROOM. AN
 OCCUPANT IS NOT PERMITTED TO CROSS OVER ONE SINK TO
 PLUG IN AN APPLIANCE ON THE OTHER SIDE OF ANOTHER SINK.
 THE OPTION IS TO RELOCATE THE ONE GFI TO THE MIDDLE OF
 THE TWO SINKS OR TO ADD AND ADDITIONAL GFI RECEPTACLE.
 NO RELOCATION WAS DONE AND NO DEVICE WAS ADDED.
  
 4) NOTE: PREVIOUS REVIEW MENTIONED THAT THE RISER DID
 NOT INDICATE ANY EQUIPMENT GROUNDING CONDUCTORS AFTER
 THE FIRST MEANS OF DISCONNECT. NO CONDUCTORS PER
 250.122, 250.110,250.24 ETC WERE ADDED.
 THIS IS ONLY AFTER THE FIRST MEANS OF DISCONNECT.
  
 5) NOTE: PREVIOUS REVIEW MENTIONED 210.12 FOR ARC FAULT
 PROTECTION REQUIRED FOR ALL CIRCUITS/OUTLETS IN
 BEDROOMS. THIS WAS REVISED IN THE 2002 NEC. THE PANEL
 SCHEDULE ONLY INDICATES AFCI PROTECTION ON ONE OF THE
 TWO MASTER BEDROOM CIRCUITS.
  
 6) NOTE: PREVIOUS REVIEW MENTIONED TO IDENTIFY THE
 3-WAY SWITCH LOCATED ON THE REAR WALL OF THE NEW MASTER
 BEDROOM. THE 3-WAY SWITCH ON PLANS DOES NOT GO TO
 ANYTHING??
 220,210,300,310 ETC,
 FBC 106.1.1
 SECTIONS GIVEN IN GENERAL AS IT IS NOT CLEAR WHAT THIS
 IS FOR.
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED FOR
 ALL SERVICE EQUIPMENT LOCATIONS TO BE IDENTIFIED ON
 PLANS. THE PLANS WERE REVISED TO SHOW THE NEW METER AND
 ONE NEW MAIN DISCONNECT HOWEVER THE SECOND DISCONNECT
 IS NOT SHOWN. PLEASE SEE 230.72 AS THIS REQUIRES ALL
 MAINS TO BE GROUPED.
 ALSO 110.26 FOR MINIMUM CLEARANCES.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO NEW
 OR EXISTING SMOKE ALARMS IN DWELLING BEING BROUGHT UP
 TO THE CURRENT NFPA-72 11.8.3 REQUIREMENTS. THE PLANS
 CONTAINS A NOTE HOWEVER AT SOME POINT A BASIC LAYOUT
 FOR THE EXISTING DWELLING SHOWING THE LOCATIONS WILL BE
 NEEDED. THIS CAN BE PART OF A PROVISO AT A LATER DATE
 IF LOCATIONS ARE NOT KNOWN AT THIS TIME.
  
 ** PER NEW BUILDING OFFICIAL, PLANS ARE NO LONGER
 RELEASE HOWEVER PER THE IMPACT REVIEW STOP, ONE SET
 WILL BE REQUIRED TO BE SIGNED OUT FOR REVIEW AND
 STAMPING BY PAL BEACH COUNTY.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 15:29 Sent To  
Notes
2009-05-15 15:29:58**DENIED REVIEW **
  
 1) NOTE: PLANS SHALL STATE MINIMUM CODE UNDER PERMIT
 APPLICATION MADE.
 ALL PLANS AFTER MARCH 1ST, 2009 SHALL CONTAIN THE
 FOLLOWING AT A MINIMUM FOR THIS SCOPE.
 2007 FBC W/ 2009 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE R313 FOR REQUIRED SMOKE ALARMS.
 THIS REQUIRES NEW/EXISTING TO MEET CURRENT CODE
 REQUIREMENTS. PLEASE ALSO SEE NFPA-72 11.5.1 AND
 11.8.3.
 THIS REQUIRES NEW SMOKE ALARM DEVICES INSIDE AND OUT
 NEW SLEEPING ROOM. SECTION 118.3 REQUIRED UNIT TO BE
 WITHIN 3FT OF THE HIGHEST POINT ON A SLOPED CEILING.
 ** KEEP IN MIND UNDER THE REVISED CODE IN 2002 AND 2005
 ALL OUTLETS IN BEDROOM REQUIRE AFCI PROTECTION
 INCLUDING SMOKE ALARM DEVICES.
  
 3) NOTE: PLANS NEED TO SHOW LOCATION OF NEW SERVICE
 MAINS AND DISCONNECTS.
 240.24, 110.26.
 BASED ON THE PLANS THE EXISTING PANEL DOES NOT MEET
 110.26 AND POWER WILL NOT BE RELEASED BACK TO DWELLING
 UNLESS RE-LOCATED.
  
 4) NOTE: PLEASE SEE 210.52D FOR BATH COUNTER GFI
 RECEPTACLE. THE GFI AS SHOWN NEEDS TO BE RELOCATED OR A
 NEW ONE ADDED. THIS IS TO PREVENT THE OCCUPANT FROM
 CROSSING OVER THE SINK AREA TO PLUG IN ANY APPLIANCE.
 THIS IS A SAFETY ISSUE.
  
 5) NOTE: PLEASE SEE THE RISER DOES NOT INDICATE ANY
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT FROM THE NEW MAIN TO THE EXISTING PANEL *A*.
 250.122,250.110,250.24.
  
 6) NOTE: PLEASE SEE RISER AS IT DOES INDICATE THE AIC
 RATING FOR THE OTHER NEW MAIN FEEDING EXISTING PANEL.
 110.9
  
 7) NOTE: *** PLEASE VERIFY WITH THE SERVICE PROVIDER
 THAT THEY ARE ACTUALLY GOING TO BE INSTALLING THE
 CONDUCTORS UNDERGROUND FROM THE POLE TO THE NEW
 SERVICE. THE RISER SHOWS TWO RUNS OF CONDUITS. MOST
 LIKELY FPL WILL NOT BE RUNNING PARALLEL SERVICE
 ENTRANCE CONDUCTORS. PLEASE ALSO VERIFY THEY WILL NOT
 BE INSTALLING A NEW HAND HOLE AT THE BASE OF POLE
 REQUIRING OWNER TO RUN FROM THAT LOCATION TO THE
 DWELLING. THIS IS BEING DONE IN MANY LOCATIONS FOR NEW
 SERVICES IN WHICH FPL IS NOT INSTALLING CONDUCTORS UP
 TO THE DWELLING. IF THIS IS THE CASE THE CONDUITS AND
 CONDUCTORS WOULD FALL UNDER NEC AND 310.16, 310.15B6 AT
 A MINIMUM.
  
 8) NOTE: PLEASE SEE CLOSET AREA WHICH INDICATES A NEW
 220V RECEPTACLE PER THE SYMBOL LEGEND. BASED ON THE
 PLANS THIS APPEARS THIS IS BEING SHOWN FOR THE AHU.
 PLEASE SEE 440.11, 440.12, 422.31, 424.19AS A
 RECEPTACLE FOR CORD AND PLUG CONNECTION MAY NOT BE USED
 OR INSTALLED.
 THIS REQUIRES A DISCONNECT.
  
 9) NOTE: PLEASE SEE LOAD CALCULATIONS WHICH ARE NOT
 CLEAR ON ACTUAL KW OF AHU/ HEAT. SEE 10KW LOAD NOTED AT
 100% WHICH IS SHOWN IN THE CALCULATIONS AS 7.5KW?
 PLEASE SEE 220.83 AND 424.3B
  
 10) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON THE PANEL SCHEDULE FOR NEW BEDROOM
 CIRCUITS. 210.12
  
 11) NOTE: PLEASE SEE 408.4 WHICH WAS REVISED IN THE
 2005 NEC WHICH REQUIRES THE PANEL SCHEDULE TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE USE OF * GENERAL LTS, OR GENERAL
 RECEPTACLES* IS NOT PERMITTED. THESE WOULD BE NOTED AS
 * MASTER BEDRM LTS PR MASTER BEDRM RECEPTS* OR WORDS TO
 THAT AFFECT.
  
 12) NOTE: PLEASE SEE 220.52 AS THE LAUNDRY/WASHER LOADS
 ARE REQUIRED TO BE FIGURED AT 1500VA MINIMUM. PLANS
 INDICATE 800VA.
  
 13) NOTE: PLEASE IDENTIFY THE THREE-WAY SWITCH AT THE
 MASTER BEDROOM BACK DOOR WHICH IS NOT SHOWN GOING TO
 ANYTHING.
 NEC 2005, FBC 106.1.1 FOR CLARITY.
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 14:12 Rev Time 0.00
Received By shill Date 2009-07-15 Time 14:12 Sent To  
Notes
2009-07-15 14:12:38R1
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-18 Cont ID  
Sent By jwitmer Date 2009-05-18 Time 10:48 Rev Time 0.00
Received By jwitmer Date 2009-05-01 Time 15:24 Sent To  
Notes
2009-05-18 11:13:19BUILDING PLAN REVIEW
 PERMIT: 09050005
 ADD: 308 COLONIEL RD
 CONT: UNDERHILL BLDG & ROOFING
 TEL: (561)379-3665
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009, 2007 FLORIDA EXISTING BUILDING CODE
 WITH 2009 SUPPLEMENTS, CHAPTER 10 ADDITIONS. PLEASE
 UPDATE PLANS.
  
 2) SHEET A-2 INDICATES THE WIND DESIGN BUT NOT THE
 REFRENECE STANDARD USED? SEE DESIGN CRITERIA R301.2.1.1
  
 3) SHEET A-2 DOES NOT INDICATE ROOF VENTING EAVE NOT
 THE REQUIRED 50% A MINIMUM OF 3'-0" ABOVE THE EAVE
 VENTS. R806.2
  
 4) PLANS DO NOT PROVIDE A TRUE SECTION THROUGH THE WALL
 SECTION, WALL SECTION INDICATES IT TO BE A TYPICAL
 GARAGE WALL WHEREAS THIS IS A BEDROOM WITH TRAY
 CEILING. THE SECOND ISSUE IS THERE IS NO SECTION
 INDICATING A SECTION THROUGH THE GABLE END WALL, HOW
 THIS WALL WILL BE FRAMED? BRACING FOR THE GABLE END
 WALL, NOR HOW THE HORIZONTAL END JOINTS OF THE T-111
 SIDING WILL BE TREATED. R 703..3.1.
  
 5) BUILDING PROVISO: PROVIDE TRUSS BRACING FOR GABLE
 END WALL. R502.1.3.2 BRACING. TRUSSES SHALL BE BRACED
 TO PREVENT ROTATION AND PROVIDE LATERAL STABILITY IN
 ACCORDANCE WITH THE REQUIREMENTS SPECIFIED IN THE
 CONSTRUCTION DOCUMENTS FOR THE BUILDING AND ON THE
 INDIVIDUAL TRUSS DESIGN DRAWINGS. IN THE ABSENCE OF
 SPECIFIC BRACING REQUIREMENTS, TRUSSES SHALL BE BRACED
 IN ACCORDANCE WITH TPI/WTCA BCSI.
  
 6) MEP-1 SMOKE ALRMS DUE NOT APPEAR IN THIS SHEET,
 R313.2 LOCATION. SMOKE ALARMS SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
  
 1. IN EACH SLEEPING ROOM.
  
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND
 UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS
 WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR
 BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON
 THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
  
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 R313.2.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A PERMIT
 OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE ADDED OR
 CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL DWELLING
 UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS LOCATED AS
 REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS SHALL BE
 INTERCONNECTED AND HARD WIRED.
  
 EXCEPTIONS:
  
 1. INTERCONNECTION AND HARD-WIRING OF SMOKE ALARMS IN
 EXISTING AREAS SHALL NOT BE REQUIRED WHERE THE
 ALTERATIONS OR REPAIRS DO NOT RESULT IN THE REMOVAL OF
 INTERIOR WALL OR CEILING FINISHES EXPOSING THE
 STRUCTURE, UNLESS THERE IS AN ATTIC, CRAWL SPACE OR
 BASEMENT AVAILABLE WHICH COULD PROVIDE ACCESS FOR HARD
 WIRING AND INTERCONNECTION WITHOUT THE REMOVAL OF
 INTERIOR FINISHES.
  
 2. WORK INVOLVING THE EXTERIOR SURFACES OF DWELLINGS,
 SUCH AS THE REPLACEMENT OF ROOFING OR SIDING, OR THE
 ADDITION OR REPLACEMENT OF WINDOWS OR DOORS, OR THE
 ADDITION OF A PORCH OR DECK, ARE EXEMPT FROM THE
 REQUIREMENTS OF THIS SECTION.
  
 R313.3 POWER SOURCE. IN NEW CONSTRUCTION, THE REQUIRED
 SMOKE ALARMS SHALL RECEIVE THEIR PRIMARY POWER FROM THE
 BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM A
 COMMERCIAL SOURCE, AND WHEN PRIMARY POWER IS
 INTERRUPTED, SHALL RECEIVE POWER FROM A BATTERY. WIRING
 SHALL BE PERMANENT AND WITHOUT A DISCONNECTING SWITCH
 OTHER THAN THOSE REQUIRED FOR OVERCURRENT PROTECTION.
 SMOKE ALARMS SHALL BE PERMITTED TO BE BATTERY OPERATED
 WHEN INSTALLED IN BUILDINGS WITHOUT COMMERCIAL POWER OR
 IN BUILDINGS THAT UNDERGO ALTERATIONS, REPAIRS OR
 ADDITIONS REGULATED BY SECTION R313.2.1.
  
 7)
2009-05-01 15:27:51R5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2009-10-21 Cont ID  
Sent By jwitmer Date 2009-10-21 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2009-10-21 Time 07:57 Sent To  
Notes
2009-10-21 09:28:24PR# 09 017230 AMOUNT: $1,093.12 /VERIFIED FEES WERE
 PAID TO P B COUNTY, JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2009-08-28 Cont ID  
Sent By dpalmer Date 2009-08-28 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2009-08-28 Time 08:21 Sent To  
Notes
2009-08-28 08:23:50CALLED AND SPOKE TO CONRACTOR HE WILL TAKE TO PBC FOR
 IMPACT FEE REVIEW ONCE ALL REVIEWS ARE COMPLETED.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-07-31 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2009-10-21 Time 07:57 Sent To  
Notes
2009-07-31 15:07:23HAS NOT GONE TO PBC FOR IMPACT FEE REVIEW/STAMPS.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-07-24 Cont ID  
Sent By rkussner Date 2009-07-24 Time 17:08 Rev Time 0.00
Received By rkussner Date 2009-07-24 Time 17:08 Sent To  
Notes
2009-07-24 17:13:18***LANDSCAPE PASSED WITH 'PROVISO'***
  
 1. LANDSCAPE PLAN WITH LANDSCAPE CALULATIONS SHALL BE
 SUBMITTED AND APPROVED PRIOR TO C/O.
  
 2. SUBMIT A COST ESTIMATE WITH THE LANDSCAPE PLAN THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST.
  
 3. AN IRRIGATION PERMIT IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-05-14 Cont ID  
Sent By rkussner Date 2009-05-14 Time 15:12 Rev Time 0.00
Received By rkussner Date 2009-05-14 Time 15:12 Sent To  
Notes
2009-05-14 15:26:17***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. PURSUANT TO SECTION 94-441 (B), THE LANDSCAPING,
 TREE PROTECTION AND SCREENING REQUIREMENTS OF THIS
 SECTION SHALL APPLY TO ALL DEVELOPMENT WITHIN THE CITY,
 PROVIDED THAT THE RENOVATIONS, REPAIR, ALTERATION OR
 REDEVELOPMENT EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE. THE ENTIRE SITE SHALL BE BROUGHT UP TO
 CURRENT LANDSCAPE STANDARDS.
  
 2. PURSUANT TO SECTION 94-448 (D)(2), SUBMIT A
 LANDSCAPE PLAN THAT CONTAINS ALL OF THE REQUIRED
 INFORMATION LISTED IN THIS SECTION.
  
 3. SUBMIT A COMPLETE LANDSCAPE COST ESTIMATE BROKEN
 DOWN INTO UNIT COST THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR.
  
 4. AN IRRIGATION PERMIT IS REQUIRED. ALL LANDSCAPE
 AREAS SHALL BE PROVIDED WITH 120% IRRIGATION COVERAGE,
 INCLUDING THE RIGHTS-OF-WAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-08 Cont ID  
Sent By rregueir Date 2009-09-08 Time 10:23 Rev Time 0.00
Received By rregueir Date 2009-09-08 Time 10:23 Sent To  
Notes
2009-09-08 10:24:03RE-STAMPED REPLACED PAGES.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-28 Cont ID  
Sent By rregueir Date 2009-07-28 Time 08:25 Rev Time 0.00
Received By rregueir Date 2009-07-28 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-11 Cont ID  
Sent By rregueir Date 2009-05-11 Time 15:10 Rev Time 0.00
Received By rregueir Date 2009-05-11 Time 14:28 Sent To  
Notes
2009-05-11 15:10:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE REFERENCE THE CURRENT CODE IN EFFECT AT TIME
 OF PERMIT APPLICATION. THE 2007 FLORIDA BUILDING CODE
 WITH 2009 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009.
  
 2. ENERGY CALCULATIONS: FORM 600C-04 WAS SUBMITTED FOR
 ENERGY CODE COMPLIANCE. THIS FORM IS NO LONGER
 APPLICABLE AS OF MARCH 1, 2009. ADDITIONS TO EXISTING
 RESIDENTIAL BUILDINGS SHALL BE CONSIDERED NEW BUILDING
 CONSTRUCTION AND SHALL COMPLY WITH THE REQUIREMENTS OF
 EITHER METHOD A OR B AS APPLICABLE IN ACCORDANCE WITH
 FBC-R SECTION N1100.0.3. PLEASE SUBMIT FORM 100A-08 OR
 FORM 1100B-08 TO DEMONSTRATE ENERGY CODE COMPLIANCE.
  
 3. A COOLING AND HEATING LOAD CALCULATION SHALL BE
 PERFORMED ON THE BUILDING AND SHALL BE ATTACHED TO THE
 FORM 1100 SUBMITTED WHEN APPLICATION IS MADE FOR A
 BUILDING PERMIT IN ACCORDANCE WITH FBC-R SECTION
 N1107.AB.1.
  
 4. PLEASE PROVIDE ALL FLEXIBLE AND RECTANGULAR DUCT
 SIZES ON PLANS. DUCT SYSTEMS SERVING HEATING, COOLING
 AND VENTILATION EQUIPMENT SHALL BE FABRICATED IN
 ACCORDANCE WITH THE PROVISIONS OF ACCA MANUAL D OR
 OTHER APPROVED METHODS PER FBC-R SECTION M1601.1.
  
 5. PAGE MEP-1 SHOWS NEW BATH EXHAUST TERMINATING AT THE
 SOFFIT. THE AIR REMOVED BY THE MECHANICAL EXHAUST
 SYSTEM SHALL BE DISCHARGED TO THE OUTDOORS AND SHALL
 NOT BE EXHAUSTED INTO A SOFFIT IN ACCORDANCE WITH FBC-R
 SECTION M1501.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-01 Cont ID  
Sent By jwitmer Date 2009-09-01 Time 08:25 Rev Time 0.50
Received By jwitmer Date 2009-09-01 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 14:35 Rev Time 0.50
Received By jwitmer Date 2009-08-04 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-08 Cont ID  
Sent By kstevens Date 2009-05-08 Time 10:27 Rev Time 0.00
Received By kstevens Date 2009-05-08 Time 10:27 Sent To  
Notes
2009-05-08 10:39:18DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. SHTS A-2 & MEP-1 CODES REFERENCED ARE FBC-2004
 W/2006 REVISIONS & THE STANDARD PLUMBING CODE. FOR ALL
 APPLICATIONS FOR PERMIT SUBMITTED ON OR AFTER MARCH 1,
 2009, PLANS SHALL BE DESIGNED AND REFERENCED TO THE
 FBC-2007 WITH 2009 SUPPLEMENTS. PLEASE DESIGN PLANS AND
 CHANGE CODE REFERENCES TO THE CORRECT CODE CYCLE.
 SECTION 106.1.1.
  
 2. SHT MEP-1 SANITARY RISER DIAGRAM. FITTINGS SHALL BE
 INSTALLED TO GUIDE SEWAGE & WASTE IN THE DIRECTION OF
 FLOW. SECTION 706.3. THE TUB CONNECTION TO THE BRANCH
 LINE AT THE LAVS IS INCORRECT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-07-23 Cont ID  
Sent By mcruz Date 2009-07-23 Time 14:25 Rev Time 0.00
Received By mcruz Date 2009-07-23 Time 14:15 Sent To  
Notes
2009-07-23 14:25:10PASSED W/PROVISO:
 THE LANDSCAPE/IRRIGATION PLANS SHALL BE APPROVED PRIOR
 TO FINAL C.O.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED BACK ON R1

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By mcruz Date 2009-05-15 Time 11:49 Rev Time 0.00
Received By mcruz Date 2009-05-15 Time 11:46 Sent To  
Notes
2009-05-15 11:49:33PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 4. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE ZLDR, SECTION 94-305(B):
 OVERHANGS SHALL NOT PROJECT MORE THAN THREE (3) FEET
 INTO A REQUIRED SETBACK.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED BACK ON RES RACK R5