Plan Review Details - Permit 09040649
Plan Review Stops For Permit 09040649
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-04-30 Cont ID  
Sent By jnguyen Date 2009-04-30 Time 15:23 Rev Time 0.00
Received By jnguyen Date 2009-04-30 Time 14:48 Sent To  
Notes
2009-05-15 09:58:45UPDATE ON 5-15-2009: I AGREE WITH DEWEY'S ASSESSMENT
 THAT ADDRESSES SHOULD NOT BE ASSIGNED TO COMMON AREA
 RESTROOMS. THEREFORE, I HAVE CHANGED SEQUENTIAL UNIT
 RECORDS 0028 & 0029 IN COMMUNITYPLUS UNDER PCN#
 74434317050030060 - 1601 FORUM PL FROM PH-1 & PH-2 TO
 14TH FLOOR & 15TH FLOOR. "PENTHOUSE" IS WHAT THE
 CONTRACTOR MAY HAVE JUST UNOFFICIALLY REFERRED TO THE
 RESTROOMS AS SUCH. PLEASE MAKE THE ADJUSTMENT ON THE
 ORIGINAL PERMIT APPLICATION.
2009-04-30 15:13:41 
 4-30-2009: I RESEARCHED THE ISSUE & TALKED TO A
 REPRESENTATIVE FROM KAST CONSTRUCTION COMPANY, LLC. I
 WAS ABLE TO CONFIRM THE PCN# 74434317050030060, AND
 THAT THE UNITS WERE PENTHOUSE 1 (PH-1) ON THE 14TH
 FLOOR & PENTHOUSE 2 (PH-2) ON THE 15TH FLOOR. IN
 COMMUNITYPLUS UNDER PCN# 74434317050030060, I CREATED
 SEQUENTIAL UNIT RECORDS 0028 - 1601 FORUM PL # PH-1 &
 0029 - 1601 FORUM PL # PH-2. PLEASE MOVE & ATTACH THIS
 PERMIT TO EITHER ONE OF THOSE SEQUENTIAL UNIT RECORDS
 0028 OR 0029, AS I DO NOT HAVE AUTHORIZATION TO
 IMPLEMENT THIS PROCEDURE IN COMMUNITYPLUS.
2009-04-30 13:44:20PER J NGUYEN..HE WILL RESEARCH UNIT INFO ON P1 & P2

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-25 Cont ID  
Sent By jwitmer Date 2009-06-25 Time 16:49 Rev Time 0.55
Received By jwitmer Date 2009-06-25 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-14 Cont ID  
Sent By jwitmer Date 2009-05-14 Time 11:20 Rev Time 0.77
Received By jwitmer Date 2009-05-14 Time 10:30 Sent To  
Notes
2009-05-14 11:09:13BUILDING PLAN REVIEW
 PERMIT: 09040649
 ADD: 1601 FORUM PL (P1 & P2)
 CONT: KAST CONSTRUCTION
 TEL: (561)689-2910 #266 BARRY CRAFT
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
 1B) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
 NEITHER SHEET A-1 NOR A-2 PROVIDE DIMENSIONS FOR THE
 CONTRACTOR TOBE ABLE TO CONSTRUCT OR INSTALL.
  
 2) LOW VALUE FOR THE REMOVAL OF AND REPLACEMENT. CALLED
 KAST CONSTRUCTION UNABLE TO SPEAK TO A PERSON, LEFT
 MESSAGE WITH BARRY CRAFT. W P B ADMINISTRTIVE CODE
 108.2 SCHEDULE OF PERMIT FEES. ON BUILDINGS,
 STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND PLUMBING
 SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A FEE FOR
 EACH PERMIT SHALL BE PAID AS REQUIRED, IN ACCORDANCE
 WITH THE SCHEDULE ESTABLISHED BY THE APPLICABLE
 GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 14:44 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 14:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 09:45 Sent To  
Notes
2009-07-03 09:47:17*** TEMP FAILED, UNTIL ORIGINAL APPLICATION IS
 SUBMITTED. ONLY A COLOR COPY OF THE FRONT OF THE
 ORIGINAL APPLICATION WAS BROUGHT BACK. CALLED AND LEFT
 MESSAGE FOR MIKE FROM KAST CONSTRUCTION.
2009-07-03 09:45:50NOTE: PLEASE SHOW LIGHTING PER NFPA-101 7.8,
 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN FOR
 MINIMUM EGRESS LIGHTING.
 ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE
 OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER
 EMERGENCY POWER IF THE GENERATOR BREAKER IS TRIPPED OR
 LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS
 COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS.
 PLEASE BE SURE TO GO OVER THIS WITH BUILDING
 OWNER/MANAGEMENT.
 OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED
 UNDER EMERGENCY POWER OR PROVIDE THE TWO FIXTURES ON EM
 CIRCUIT WITH BATTERY BACK UP.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-15 Cont ID  
Sent By dpalmer Date 2009-05-15 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2009-05-15 Time 09:28 Sent To  
Notes
2009-05-15 09:28:20**DENIED REVIEW **
  
 1) NOTE: THE MINIMUM CODES UNDER DESIGN AS ADOPTED
 MARCH 1ST 2009 SHALL BE AS FOLLOWS. THE ELECTRICAL CODE
 NFPA-70 WAS REVISED ON DECEMBER 8TH, 2006. THE PLANS
 STILL INDICATE THE 2002 NEC. PLEASE ALSO SEE FAC
 69A-60.004 WHICH ADOPTED THE NEW NFPA-101 2006 EDITION
 AS OF DECEMBER 31, 2008.
 PLEASE ADJUST AND DESIGN TO THESE CODES.
  
 2007 FBC W/ 2009 SUPPLEMENTS.
 2005 NFPA-70
 2006 NFPA-101
  
 2) NOTE: PLEASE SEE THE LIGHTING POWER DENSITIES NEED
 TO BE DONE UNDER THE NEW CODE. PLEASE SEE 2007 FBC WITH
 2009 REVISIONS. THE CODE SECTION IS MINOR AS THE TABLE
 DID CHANGE.
 THE LPD AS SHOWN LOOKS LIKE IT EXCEEDS ALLOWANCES BASED
 ON ACTUAL SQ FOOTAGE ON PLANS FOR SPACE. IT IS NOT
 PERMITTED TO INCLUDE WALL AREAS WHERE SHAFTS ETC ARE
 LOCATED.
 APPLICATION HAS THE SQ FT CLOSER TO ACTUAL WHICH STATES
 595.
  
 ** SOME OF THESE ITEMS COULD HAVE BEEN REDLINED HOWEVER
 WE DO NOT HAVE THE AUTHORITY TO REVISE DESIGNS ON
 PLANS.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 13:49 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 13:37 Sent To  
Notes
2009-06-29 13:49:23*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-20 Cont ID  
Sent By mawillia Date 2009-05-20 Time 13:37 Rev Time 0.00
Received By mawillia Date 2009-05-20 Time 13:08 Sent To  
Notes
2009-05-20 13:36:47*****DENIED*****
  
 1. INCONSISTENCY IN THE ACTUAL PROJECT SITE FLOOR
 LOCATION. THE FLOOR SITE LISTED IN THE TITLE BLOCK OF
 THE SUBMITTED PLAN SHEETS AND IN THE PROJECT DATA
 ADDRESS ON SHEET T ARE REFLECTED AS P1 AND P2, WHEREAS
 THE RECORDED FLOOR IN OUR SYSTEM IS FOR THE 14TH FLOOR.
 PLEASE CORRELATE.
  
 2. AS OF 12/31/2009, THE 2007 EDITION OF FLORIDA FIRE
 PREVENTION CODE (BASED ON NFPA 101 - LIFE SAFETY CODE -
 2006 EDITION AND NFPA 1 - UNIFORM FIRE CODE - 2006
 EDITION) SHALL BE REFERENCED. AMEND REFERENCE STANDARDS
 ON SHEET T TO REFLECT CURRENT CODE.
  
 3. ON SHEET E-1, ELECTRICAL NOTE #2, AMEND CODE EDITION
 TO REFLECT 2005 NFPA 70 AND 2006 NFPA 101.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPORPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW A-1, E-1
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-19 Cont ID  
Sent By btrobaug Date 2009-06-19 Time 15:37 Rev Time 0.00
Received By btrobaug Date 2009-06-19 Time 15:37 Sent To  
Notes
2009-06-19 15:37:38 
 B-12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-20 Cont ID  
Sent By mawillia Date 2009-05-20 Time 13:09 Rev Time 0.00
Received By mawillia Date 2009-05-01 Time 16:42 Sent To  
Notes
2009-05-01 16:42:45C-20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 14:41 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 14:41 Sent To  
Notes
2009-07-08 14:41:32RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 10:23 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 10:21 Sent To  
Notes
2009-05-15 10:23:41**PROVISO**
  
 REVISE FRONT PAGE TO REFERENCE THE CURRENT CODES IN
 EFFECT AT TIME OF PERMIT APLICATION. THE 2007 FLORIDA
 BUILDING CODE W/ 2009 SUPPLEMENT IS IN EFFECT AS OF
 MARCH 1, 2009.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-05-11 Cont ID  
Sent By kstevens Date 2009-05-11 Time 09:14 Rev Time 0.00
Received By kstevens Date 2009-05-11 Time 09:14 Sent To  
Notes
2009-05-11 09:15:43PLUMBING FIXTURES TO BE REMOVED AND REINSTALLED IN THE
 SAME LOCATION. NO PLUMBING PLANS SUBMITTED/REQUIRED.