| 2009-05-08 10:40:19 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. RETURN TRANSFER DUCTS AT BACK LEFT AND BACK RIGHT |
| | BEDROOMS US TOO SMALL TO MEET THE BALANCED RETURN AIR |
| | REQUIREMENTS. TRANSFER DUCTS SHALL INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE SQUARE |
| | INCHES OF THE SUPPLY DUCT ENTERING THE ROOM IT'S |
| | SERVING AND THE DOOR HAVING AT LEAST AN UNRESTRICTED 1 |
| | INCH UNDERCUT TO ACHIEVE PROPER RETURN AIR BALANCE IN |
| | ACCORDANCE WITH FBC-R SECTION M1602.4 EXCEPTION 1. |
| | |
| | 2. RETURN AIR TRANSFER DUCT FOR MASTER BEDROOM HAS NO |
| | SIZE SHOWN ON PLANS. PLEASE SHOW DUCT SIZE ON PLANS TO |
| | DEMONSTRATE COMPLIANCE WITH FBC-R SECTION M1602.4 |
| | EXCEPTIONS 1 AND 3. |
| | |
| | 3. AHU DETAIL CALLS FOR THE PRIMARY DRAIN LINE TO BE |
| | ROUTED TO AN "OVERFLOW DRAIN." PLEASE CLARIFY THIS |
| | DESIGN. CONDENSATE FROM THE COOLING COIL SHALL BE |
| | CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE |
| | OF DISPOSAL (OUTDOORS, PERVIOUS AREA, MIN. 12" FROM THE |
| | HOUSE AND 6" ABOVE GRADE). CONDENSATE SHALL NOT |
| | DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS WHERE IT |
| | WOULD CAUSE A NUISANCE IN ACCORDANCE WITH FBC-R SECTION |
| | M1411.3. |
| | |
| | 4. A FORM 1100C-07 ENERGY CALCULATION WAS SUBMITTED. |
| | THIS FORM IS NOT VALID. THE 2009 SUPPLEMENT TO THE 2007 |
| | FLORIDA BUILDING CODE IS IN EFFECT AS OF MARCH 1, 2009. |
| | THE CORRECT FORM IS 1100B-08 IN ACCORDANCE WITH THE |
| | 2009 SUPPLEMENT. PLEASE SUBMIT THE CORRECT FORM. FOR |
| | MORE INFORMATION ON THE 2009 SUPPLEMENT TO THE 2007 |
| | FLORIDA BUILDING CODE, PLEASE VISIT: |
| | WWW.FLORIDABUILDING.ORG |
| | |