| Plan Review Stops For Permit 09040613 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2009-08-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-08-03 |
Time |
19:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-08-03 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2009-08-03 19:02:14 | PROVISO - PROVIDE WAIVER OR DEMONSTRATE COMPLIANCE WITH | | | FBC11-4.1.6, <5 OCCUPANTS/<500 SF | | | | | | REVISION G, A-3 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-10 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-10 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2009-07-10 11:01:30 | APPLICANT HAS REQUESTED PERMISSION TO PROCEED AT THEIR | | | OWN RISK PENDING RECEIPT OF A WAIVER FROM THE FLORIDA | | | BUILDING COMMISSSION ACCESSIBILITY TECHNICAL ADVISORY | | | COMMITTEE OR THE ABILITY TO DEMONSTRATE COMPLIANCE WITH | | | THE REQUIREMENTS OF FBC SECTION 11-4.1.6(1)(F) RELATING | | | TO VERTICAL ACCESSIBILITY FOR WORK AREAS NOT CONTAINING | | | MORE THAN 5 PERSONS AND NOT OPEN TO THE PUBLIC. | | | REVISION IS BEING ISSUED UNDER THE CONDITION THAT THIS | | | ISSUE WILL BE RESOLVED PRIOR TO FINAL INSPECTION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-08 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-08 |
Time |
20:35 |
Sent To |
|
|
| Notes |
| 2009-07-08 20:47:57 | 1. APPLICANT HAS FILED FOR REVISION TO INTERIOR DEMO | | | PERMIT AND NOT INTERIOR RENOVATION PERMIT. PLEASE | | | PROVIDE A WRITTEN REQUEST AND PAY FEES ASSOCIATED WITH | | | TRANSFER OF PROJECT AND FEES ALREADY PAID TO THE | | | APPROPRIATE PERMIT. | | | 2. PROPOSED REVISION HAS INCREASED THE NET SQUARE | | | FOOTAGE OF THE CENTRAL LOFT AREA SIGNFICANTLY AND | | | COMBINED TWO ADJACENT LOFT SPACES WHICH NOW APPEARS TO | | | HAVE CREATED A VIOLATION OF FBC 11-4.1.6(1)(F) | | | (VERTICAL ACCESSIBILITY). PLEASE DEMONSTRATE COMPLIANCE | | | BY PROVIDING A NET SQUARE FOOTAGE TABULATION FOR THE | | | NEW CENTER LOFT INCLUDING THE NEW OFFICE IN ORDER TO | | | DEMONSTRATE THAT LESS 500 SQUARE FOOT OF NET AREA (5 | | | PERSONS) EXISTS OR PROVIDE A WAIVER FROM THE FLORIDA | | | BUILDING COMMISSION ACCESSIBILITY TECHNICAL ADVISORY | | | COMMITTEE. THIS INFORMATION WAS PROVIDED ON THE PLANS | | | ORIGINALLY SUBMITTED BUT HAS BEEN OMMITTED FROM THE | | | REVISED PLAN DOCUMENTS. | | | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6650 OR BY | | | EMAIL AT [email protected] IF YOU WISH TO DISCUSS THE | | | DEFICIENCIES NOTED IN THIS REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-06-04 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-06-04 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-06-04 |
Time |
15:38 |
Sent To |
PC |
|
| Notes |
| 2009-06-04 15:39:06 | IMPACT FEES PAID RECEIPT ON FILE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-06-03 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-06-03 |
Time |
16:06 |
Sent To |
FIRE |
|
| Notes |
| 2009-06-03 16:06:58 | APPROVED PENDING IMPACT REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-06 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-06 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2009-05-06 18:51:12 | 1. FBC EXISTING BUILDINGS VOLUME 2007 - 912.8 : | | | EXISTING BUILDINGS OR PORTIONS THEREOF UNDERGOING A | | | CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL | | | COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE | | | BUILDING. | | | 2. FBC 2007 11-4.1.6 ACCESIBILE BUILDINGS: ALTERATIONS: | | | (1) (F) INSUFFICIENT INFORMATION HAS BEEN PROVIDED TO | | | ESTABLISH THAT THE SECOND FLOOR AREAS IN THIS PROJECT | | | ARE EXEMPT FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY PURSUANT TO EXCEPTION (3). PROVIDE SQUARE | | | FOOTAGE TABULATIONS FOR THE GROUND FLOOR AND EACH OF | | | THE THREE (3) SECOND FLOOR AREAS. | | | 3. FBC EXISTING BUILDINGS VOLUME 2007 - 912.4.2, 805, , | | | 805.2, 805.3, 705.3, 705.3.2, DEMONSTRATE MEANS OF | | | EGRESS IS COMPLIANT WITH APPLICABLE REQUIREMENT THROUGH | | | A LIFE SAFETY PLAN, I.E., SINGLE EXIT. INCLUDE MEANS OF | | | EGRESS LIGHTING, GUARDS AND RAILS ASSESSMENT. | | | 4. PROVIDE RECORDED UNITY OF TITLE FOR UNITS BEING | | | CONNECTED. | | | 5. PROVIDE POA OR BUILDING OWNER'S CONSENT TO MODIFY | | | SEPARATION WALLS WHICH DO NOT BELONG TO INDIVIDUAL | | | PARCELS. | | | PLEASE FEEL FREE TO CONTACT ME WITH QUESTIONS REGARDING | | | THIS REVIEW. | | | DOUG WISE - 561-805-6650 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-08 |
Time |
20:33 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-08 |
Time |
20:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-06-03 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-06-03 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-05-07 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-07 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-07 |
Time |
14:35 |
Sent To |
FIRE |
|
| Notes |
| 2009-05-07 15:01:29 | 1. FBC 2007 EXISTING BUILDINGS VOLUME - 404.1, 404.2 , | | | 612.1, 711.1: PROVIDE ENERGY CALCULATIONS FOR THIS | | | RECONFIGURATION OF AN EXISTING SPACE | | | 2. FBC 2007 13-415.ABC.1.1, 13-415.ABC.1.2 - NO | | | OCCUPANCY SENSORS APPEAR TO HAVE BEEN PROVIDED FOR THE | | | SECOND FLOOR AREA. | | | 3. FBC 2007 13-415.B.1 - IT APPEARS THAT METHOD "B" HAS | | | BEEN UTILIZED TO DEMONSTRATE COMPLIANCE, HOWEVER | | | APPROXIMATELY 2000 SQUARE FEET OF AREA HAS NOT BEEN | | | INCLUDED IN THE TABULAR DATA PROVIDED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-07-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-09 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-09 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2009-07-09 11:09:25 | *****REVISION #F, DATED 6/19,29/09, APPROVED***** | | | | | | REVISED PLAN SHEETS A-2 AND E-1 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-06-03 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-06-03 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2009-06-03 16:48:04 | *****APPROVED***** | | | | | | THE COMMENTS FORM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED; PLAN SHEETS A-2, A-4, A-5, FP-1, AND | | | E-1 WERE STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-08 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-08 |
Time |
14:19 |
Sent To |
M |
|
| Notes |
| 2009-05-08 14:19:18 | *****DENIED***** | | | | | | | | | 1. THE PROJECT DATA STATES THAT SUITES #101 THRU #104 | | | WILL COMBINE TO CREATE ONE TENANT SPACE. WHAT WILL BE | | | THE SUITE DESIGNATION OF THIS TENANT SPACE? PLEASE BE | | | ADVISED THAT THE ACTUAL SITE LOCATION, INCLUDING THE | | | SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND | | | NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE | | | REFERENCED. PLEASE AMEND REFERENCE STANDARDS ON THE THE | | | TITLE SHEET. | | | | | | 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE | | | TO THE EXIT(S) AND LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S). | | | | | | 4. PLEASE BE ADVISED THAT THE STAIRS SHALL HAVE | | | HANDRAILS ON BOTH SIDES. IF HANDRAILS/GUARDRAILS ARE TO | | | BE INSTALLED, PROVIDE PRESCRIPTIVE STRENGTH FOR THE NEW | | | GUARDRAILS AND HANDRAILS. | | | | | | 5. PROVIDE A FIRE SPRINKLER HEAD LAYOUT FOR THE | | | PROPOSED FLOOR LAYOUT. THESE HEADS MAY BE SHOWN ON THE | | | REFLECTED CEILING AND/OR THE LIFE SAFETY PLAN SHEET(S). | | | | | | 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 7. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I, | | | OR CLASS II. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE/HOW THE COMMENTS WERE ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-08 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-29 |
Time |
16:35 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-08 |
Time |
20:29 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-08 |
Time |
20:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-06-03 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-06-03 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-06 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-06 |
Time |
18:52 |
Sent To |
|
|
| Notes |
| 2009-05-06 19:02:21 | 1. FBC EXISTING BUILDINGS VOLUME 2007 - 909.1 - | | | MECHANICAL SYSTEMS MUST COMPLY WITH FBC MECHANICAL DUE | | | TO INCREASED VENTILATION REQUIREMENTS. | | | 2. FMC 2007 312.1 PROVIDE EQUIPMENT LOAD CALCULATIONS | | | AND ENERGY CALCUALTIONS WHICH REFLECT THE INTENDED USE. | | | 3. FBC EXISTING BUILDINGS VOLUME 2007 - 909.1 KITCHEN | | | EXHAUST EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF | | | THE FMC 2007 FOR THE NEW OCCUPANCY. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-07-08 |
Time |
20:34 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-07-08 |
Time |
20:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-06-03 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-06-03 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-06-03 |
Time |
16:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-06 |
Time |
19:02 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-06 |
Time |
19:02 |
Sent To |
|
|
| Notes |
| 2009-05-06 19:08:24 | 1. FBC EXISTING BUIILDINGS VOLUME 2007 - 910.1 PLEASE | | | PROVIDE A PLUMBING FIXTURE TABULATION FOR THE ENTIRE | | | SPACE. | | | 2. FBC EXISTING BUILDINGS VOLUME 2007 - 906: PLEASE | | | PROVIDE ENLARGED BATHROOM FLOOR PLANS WHICH REFLECT | | | COMPLIANCE WITH CHAPTER 11 (ACCESSIBILITY) AS | | | APPLICABLE, INCLUDE CLEAR FLOOR SPACE AND TURNING | | | RADIUS OR "T" AREA. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-06-04 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2009-06-04 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2009-06-04 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2009-05-15 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2009-05-15 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2009-05-15 |
Time |
08:50 |
Sent To |
I |
|
| Notes |
|
|