Plan Review Details - Permit 09040613
Plan Review Stops For Permit 09040613
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-08-03 Cont ID  
Sent By shill Date 2009-08-03 Time 19:00 Rev Time 0.00
Received By shill Date 2009-08-03 Time 19:00 Sent To  
Notes
2009-08-03 19:02:14PROVISO - PROVIDE WAIVER OR DEMONSTRATE COMPLIANCE WITH
 FBC11-4.1.6, <5 OCCUPANTS/<500 SF
  
 REVISION G, A-3
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-07-10 Cont ID  
Sent By dwise Date 2009-07-10 Time 10:56 Rev Time 0.00
Received By dwise Date 2009-07-10 Time 10:56 Sent To  
Notes
2009-07-10 11:01:30APPLICANT HAS REQUESTED PERMISSION TO PROCEED AT THEIR
 OWN RISK PENDING RECEIPT OF A WAIVER FROM THE FLORIDA
 BUILDING COMMISSSION ACCESSIBILITY TECHNICAL ADVISORY
 COMMITTEE OR THE ABILITY TO DEMONSTRATE COMPLIANCE WITH
 THE REQUIREMENTS OF FBC SECTION 11-4.1.6(1)(F) RELATING
 TO VERTICAL ACCESSIBILITY FOR WORK AREAS NOT CONTAINING
 MORE THAN 5 PERSONS AND NOT OPEN TO THE PUBLIC.
 REVISION IS BEING ISSUED UNDER THE CONDITION THAT THIS
 ISSUE WILL BE RESOLVED PRIOR TO FINAL INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2009-07-10 Cont ID  
Sent By dwise Date 2009-07-08 Time 10:55 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 20:35 Sent To  
Notes
2009-07-08 20:47:571. APPLICANT HAS FILED FOR REVISION TO INTERIOR DEMO
 PERMIT AND NOT INTERIOR RENOVATION PERMIT. PLEASE
 PROVIDE A WRITTEN REQUEST AND PAY FEES ASSOCIATED WITH
 TRANSFER OF PROJECT AND FEES ALREADY PAID TO THE
 APPROPRIATE PERMIT.
 2. PROPOSED REVISION HAS INCREASED THE NET SQUARE
 FOOTAGE OF THE CENTRAL LOFT AREA SIGNFICANTLY AND
 COMBINED TWO ADJACENT LOFT SPACES WHICH NOW APPEARS TO
 HAVE CREATED A VIOLATION OF FBC 11-4.1.6(1)(F)
 (VERTICAL ACCESSIBILITY). PLEASE DEMONSTRATE COMPLIANCE
 BY PROVIDING A NET SQUARE FOOTAGE TABULATION FOR THE
 NEW CENTER LOFT INCLUDING THE NEW OFFICE IN ORDER TO
 DEMONSTRATE THAT LESS 500 SQUARE FOOT OF NET AREA (5
 PERSONS) EXISTS OR PROVIDE A WAIVER FROM THE FLORIDA
 BUILDING COMMISSION ACCESSIBILITY TECHNICAL ADVISORY
 COMMITTEE. THIS INFORMATION WAS PROVIDED ON THE PLANS
 ORIGINALLY SUBMITTED BUT HAS BEEN OMMITTED FROM THE
 REVISED PLAN DOCUMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6650 OR BY
 EMAIL AT [email protected] IF YOU WISH TO DISCUSS THE
 DEFICIENCIES NOTED IN THIS REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-04 Cont ID  
Sent By dwise Date 2009-06-04 Time 15:38 Rev Time 0.00
Received By dwise Date 2009-06-04 Time 15:38 Sent To PC
Notes
2009-06-04 15:39:06IMPACT FEES PAID RECEIPT ON FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-03 Cont ID  
Sent By dwise Date 2009-06-03 Time 16:06 Rev Time 0.00
Received By dwise Date 2009-06-03 Time 16:06 Sent To FIRE
Notes
2009-06-03 16:06:58APPROVED PENDING IMPACT REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dwise Date 2009-05-06 Time 18:19 Rev Time 0.00
Received By dwise Date 2009-05-06 Time 18:19 Sent To  
Notes
2009-05-06 18:51:121. FBC EXISTING BUILDINGS VOLUME 2007 - 912.8 :
 EXISTING BUILDINGS OR PORTIONS THEREOF UNDERGOING A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE
 BUILDING.
 2. FBC 2007 11-4.1.6 ACCESIBILE BUILDINGS: ALTERATIONS:
 (1) (F) INSUFFICIENT INFORMATION HAS BEEN PROVIDED TO
 ESTABLISH THAT THE SECOND FLOOR AREAS IN THIS PROJECT
 ARE EXEMPT FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY PURSUANT TO EXCEPTION (3). PROVIDE SQUARE
 FOOTAGE TABULATIONS FOR THE GROUND FLOOR AND EACH OF
 THE THREE (3) SECOND FLOOR AREAS.
 3. FBC EXISTING BUILDINGS VOLUME 2007 - 912.4.2, 805, ,
 805.2, 805.3, 705.3, 705.3.2, DEMONSTRATE MEANS OF
 EGRESS IS COMPLIANT WITH APPLICABLE REQUIREMENT THROUGH
 A LIFE SAFETY PLAN, I.E., SINGLE EXIT. INCLUDE MEANS OF
 EGRESS LIGHTING, GUARDS AND RAILS ASSESSMENT.
 4. PROVIDE RECORDED UNITY OF TITLE FOR UNITS BEING
 CONNECTED.
 5. PROVIDE POA OR BUILDING OWNER'S CONSENT TO MODIFY
 SEPARATION WALLS WHICH DO NOT BELONG TO INDIVIDUAL
 PARCELS.
 PLEASE FEEL FREE TO CONTACT ME WITH QUESTIONS REGARDING
 THIS REVIEW.
 DOUG WISE - 561-805-6650
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 20:33 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 20:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By dwise Date 2009-06-03 Time 16:07 Rev Time 0.00
Received By dwise Date 2009-06-03 Time 16:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-07 Cont ID  
Sent By dwise Date 2009-05-07 Time 14:36 Rev Time 0.00
Received By dwise Date 2009-05-07 Time 14:35 Sent To FIRE
Notes
2009-05-07 15:01:291. FBC 2007 EXISTING BUILDINGS VOLUME - 404.1, 404.2 ,
 612.1, 711.1: PROVIDE ENERGY CALCULATIONS FOR THIS
 RECONFIGURATION OF AN EXISTING SPACE
 2. FBC 2007 13-415.ABC.1.1, 13-415.ABC.1.2 - NO
 OCCUPANCY SENSORS APPEAR TO HAVE BEEN PROVIDED FOR THE
 SECOND FLOOR AREA.
 3. FBC 2007 13-415.B.1 - IT APPEARS THAT METHOD "B" HAS
 BEEN UTILIZED TO DEMONSTRATE COMPLIANCE, HOWEVER
 APPROXIMATELY 2000 SQUARE FEET OF AREA HAS NOT BEEN
 INCLUDED IN THE TABULAR DATA PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-07-09 Cont ID  
Sent By mawillia Date 2009-07-09 Time 11:23 Rev Time 0.00
Received By mawillia Date 2009-07-09 Time 10:19 Sent To  
Notes
2009-07-09 11:09:25*****REVISION #F, DATED 6/19,29/09, APPROVED*****
  
 REVISED PLAN SHEETS A-2 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By mawillia Date 2009-06-03 Time 16:48 Rev Time 0.00
Received By mawillia Date 2009-06-03 Time 16:24 Sent To  
Notes
2009-06-03 16:48:04*****APPROVED*****
  
 THE COMMENTS FORM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A-2, A-4, A-5, FP-1, AND
 E-1 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-08 Cont ID  
Sent By mawillia Date 2009-05-08 Time 15:33 Rev Time 0.00
Received By mawillia Date 2009-05-08 Time 14:19 Sent To M
Notes
2009-05-08 14:19:18*****DENIED*****
  
  
 1. THE PROJECT DATA STATES THAT SUITES #101 THRU #104
 WILL COMBINE TO CREATE ONE TENANT SPACE. WHAT WILL BE
 THE SUITE DESIGNATION OF THIS TENANT SPACE? PLEASE BE
 ADVISED THAT THE ACTUAL SITE LOCATION, INCLUDING THE
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND
 NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE
 REFERENCED. PLEASE AMEND REFERENCE STANDARDS ON THE THE
 TITLE SHEET.
  
 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE
 TO THE EXIT(S) AND LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S).
  
 4. PLEASE BE ADVISED THAT THE STAIRS SHALL HAVE
 HANDRAILS ON BOTH SIDES. IF HANDRAILS/GUARDRAILS ARE TO
 BE INSTALLED, PROVIDE PRESCRIPTIVE STRENGTH FOR THE NEW
 GUARDRAILS AND HANDRAILS.
  
 5. PROVIDE A FIRE SPRINKLER HEAD LAYOUT FOR THE
 PROPOSED FLOOR LAYOUT. THESE HEADS MAY BE SHOWN ON THE
 REFLECTED CEILING AND/OR THE LIFE SAFETY PLAN SHEET(S).
  
 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I,
 OR CLASS II.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-08 Cont ID  
Sent By rregueir Date 2009-05-08 Time 16:36 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 16:35 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 20:29 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 20:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By dwise Date 2009-06-03 Time 16:07 Rev Time 0.00
Received By dwise Date 2009-06-03 Time 16:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dwise Date 2009-05-06 Time 18:52 Rev Time 0.00
Received By dwise Date 2009-05-06 Time 18:52 Sent To  
Notes
2009-05-06 19:02:211. FBC EXISTING BUILDINGS VOLUME 2007 - 909.1 -
 MECHANICAL SYSTEMS MUST COMPLY WITH FBC MECHANICAL DUE
 TO INCREASED VENTILATION REQUIREMENTS.
 2. FMC 2007 312.1 PROVIDE EQUIPMENT LOAD CALCULATIONS
 AND ENERGY CALCUALTIONS WHICH REFLECT THE INTENDED USE.
 3. FBC EXISTING BUILDINGS VOLUME 2007 - 909.1 KITCHEN
 EXHAUST EQUIPMENT SHALL COMPLY WITH THE REQUIREMENTS OF
 THE FMC 2007 FOR THE NEW OCCUPANCY.

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-07-08 Cont ID  
Sent By dwise Date 2009-07-08 Time 20:34 Rev Time 0.00
Received By dwise Date 2009-07-08 Time 20:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-06-03 Cont ID  
Sent By dwise Date 2009-06-03 Time 16:08 Rev Time 0.00
Received By dwise Date 2009-06-03 Time 16:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dwise Date 2009-05-06 Time 19:02 Rev Time 0.00
Received By dwise Date 2009-05-06 Time 19:02 Sent To  
Notes
2009-05-06 19:08:241. FBC EXISTING BUIILDINGS VOLUME 2007 - 910.1 PLEASE
 PROVIDE A PLUMBING FIXTURE TABULATION FOR THE ENTIRE
 SPACE.
 2. FBC EXISTING BUILDINGS VOLUME 2007 - 906: PLEASE
 PROVIDE ENLARGED BATHROOM FLOOR PLANS WHICH REFLECT
 COMPLIANCE WITH CHAPTER 11 (ACCESSIBILITY) AS
 APPLICABLE, INCLUDE CLEAR FLOOR SPACE AND TURNING
 RADIUS OR "T" AREA.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-04 Cont ID  
Sent By aaponte Date 2009-06-04 Time 15:24 Rev Time 0.00
Received By aaponte Date 2009-06-04 Time 15:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-05-15 Cont ID  
Sent By mflis Date 2009-05-15 Time 08:50 Rev Time 0.00
Received By mflis Date 2009-05-15 Time 08:50 Sent To I
Notes
***NONE***