| 2009-05-12 13:24:29 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009 |
| | REVISIONS. |
| | |
| | 1- PERMIT FEES NEED TO BE PAID AT TIME OF PERMIT |
| | APPLICATION. FEES WERE NOT PAID. IN ADDITION VALUATION |
| | DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | VALUATION WAS UPDATED AS REQUIRED BY SEC. 108.3 CITY |
| | AMENDMENTS TO FBC. OWES $4,456.66. THIS INCLUDES |
| | UPDATED PERMIT VALUATION, RADON FEES AND THE FEES THAT |
| | WERE NOT PAID AT TIME OF PERMIT APPLICATION. |
| | |
| | 2- AFTER PLANS ARE REVISED BY THE ENGINEER, BRING THEM |
| | TO PALM BEACH COUNTY (2300 N. JOG RD (561)233-5120) TO |
| | CHECK IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 |
| | OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 FBC 2007. NOTE: MAKE SURE ALL INFORMATION IS |
| | PROVIDED AND OWNER/AGENT SIGNS AND DATES BOTTOM OF |
| | FORM. |
| | |
| | 5- SPECIFY ATTIC SIZE AND LOCATION. SEC. R807 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY |
| | IDENTIFY ON PRODUCT APPROVAL SPECIFIC MULLION SIZE AND |
| | ANCHORS TO VERIFY COMPLIANCE WITH THE CALCULATED DESIGN |
| | PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) EXTERIOR SWING DOORS AS SHOWN ON PLANS. INFORMATION |
| | SUBMITTED IS NOT AN APPROVED PRODUCT APPROVAL REPORT. |
| | |
| | C) ROOF SHINGLES. NONE SUBMITTED. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE CONNECTOR. NO NEED TO |
| | SUBMIT COMPLETE REPORT. NOTE: THIS APPLIES ONLY FOR |
| | STRUCTURAL CONNECTORS. OTHER PRODUCT APPROVALS REQUIRE |
| | COMPLETE REPORT. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- WINDOWS SHOWN ON EXTERIOR ELEVATIONS AND WINDOW |
| | SCHEDULE ARE FIXED WINDOWS, WHILE PRODUCT APPROVAL |
| | SUBMITTED IS FOR SINGLE HUNG WINDOWS. REVISE AS REQUIRE |
| | INFORMATION ON EXTERIOR ELEVATIONS AND WINDOW SCHEDULE |
| | TO MATCH PRODUCT APPROVAL SUBMITTED. |
| | |
| | 9- PROVIDE DETAILS AND SPECIFICATION FOR BALCONY |
| | GUARDRAIL CONSTRUCTION TO SHOW COMPLIANCE WITH TABLE |
| | R301.5 AND SEC. R312 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 10- SHEET A2: |
| | A) REVISE ALL NOTES SHOWN ON EMERGENCY EGRESS WINDOWS. |
| | SEE 2007 FLORIDA RESIDENTIAL CODE AND REVISE |
| | CORRESPONDING CODE SECTIONS ACCORDINGLY. ALSO, CLARIFY |
| | WHAT'S NET CLEAR OPENING OF 20" FOR?. SEE COMMENTS ON |
| | PLANS AND REVISE AS REQUIRED. |
| | |
| | B) SPECIFY SIZE OF EGRESS WINDOW FOR BEDROOM #2 TO |
| | VERIFY COMPLIANCE WITH EGRESS REQUIREMENTS OF SEC. R310 |
| | OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY SIZE OF |
| | INDIVIDUAL WINDOW. |
| | |
| | C) SPECIFY EGRESS REQUIREMENTS FOR BEDROOM ADJACENT TO |
| | BEDROOM #2. NOTE STATING THAT "CONTRACTOR TO VERIFY |
| | BEDROOM TO HAVE EGRESS WINDOW" IS NOT ACCEPTABLE. |
| | COMPLIANCE SHALL BE SHOWN ON THESE DRAWINGS. |
| | |
| | D) UPDATE DESIGN INFORMATION SHOWN ON UPPER RIGHT |
| | CORNER. REVISE BUILDING EXPOSURE AND CORRESPONDING |
| | DESIGN PRESSURES. SEE REVISED AND NEW SECTIONS ON 2009 |
| | REVISIONS TO THE 2007 FLORIDA RESIDENTIAL CODE. SEE |
| | SECTIONS R301.2.1.4 THRU R301.2.1.4.3 AND REVISE AS |
| | REQUIRED. |
| | |
| | E) REVISE INFORMATION REGARDING ALTERATION LEVEL TYPE |
| | AND SPECIFIC SECTIONS REFERENCED. SEE SEC. 403 OF 2007 |
| | EXISTING FLORIDA BUILDING CODE TO DEFINE ALTERATION |
| | LEVEL. THIS IS NOT ALTERATION LEVEL 1. ALSO, TAKE INTO |
| | CONSIDERATION THAT THIS IS AN ADDITION. SEE CHAPTER 10 |
| | OF 2007 EXISTING FLORIDA BUILDING CODE. |
| | |
| | F) AREA TABULATION DOESN'T ADD UP CORRECTLY. 971SF AND |
| | 860SF IS NOT EQUAL TO 1830SF. REVISE AS REQUIRED. |
| | |
| | 11- SHEET A3: |
| | A) TYPICAL STAIR DETAIL. * SPECIFY FIREBLOCKING |
| | MATERIAL AND LOCATION AS REQUIRED BY SEC. R602.1.2 OF |
| | 2007 FLORIDA RESIDENTIAL CODE. MISSING FIREBLOCKING AT |
| | TOP AND MIDDLE OF STAIRS. ** CLARIFY HOW IS THE 2 1/2" |
| | NOSING BUILT. THIS CAN'T BE ACCOMPLISHED WITH THE STAIR |
| | RISE AND TREAD SPECIFIED. |
| | |
| | B) REVISE CODE SECTIONS REFERENCED ON INTERIOR STAIR |
| | RAILING DETAIL. SEE 2007 FLORIDA RESIDENTIAL CODE FOR |
| | PROPER CODE SECTIONS TO BE REFERENCED. |
| | |
| | C) FOOTING DIMENSIONS SHOWN ON TYP. WALL SECTION ARE |
| | TOO SMALL AND THEY CAN'T BE READ. REVISE AS REQUIRED. |
| | |
| | 12- SHEET S2: SPECIFY HOW LONG ARE THE 3/4" SLEEVE |
| | ANCHORS SPECIFIED TO SUPPORT THE (2)2X8 WOOD LEDGER |
| | THAT SUPPORTS THE FLOOR TRUSSES TO VERIFY COMPLIANCE |
| | WITH THE CALCULATED LOADS OF SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 13- SHEET S3: |
| | A) REVISE THE DESIGN SPECIFICATIONS SHOWN ON THE |
| | STRUCTURAL NOTES. COORDINATE WITH ITEM 10D ABOVE. |
| | REVISE COMPONENTS AND CLADDING DESIGN PRESSURES |
| | ACCORDINGLY. |
| | |
| | B) WHERE IS THE TRUSS ANCHOR SCHEDULE?. |
| | |
| | C) REVISE MASONRY NOTE. MIN. COMPRESSIVE STRENGTH OF |
| | MASONRY UNIT IS 1900PSI, NOT 1500PSI. SEE SEC. R606.4 |
| | OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 14- SHEET S4: |
| | A) GENERAL LOADING TO INCLUDE THE ATTIC LIVE LOAD AS |
| | REQUIRED BY TABLE R301.5 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) REVISE DOORS AND WINDOWS BUCK DETAILS. NEED TO |
| | PROVIDE BUCKS THAT PROVIDE FULL SUPPORT TO THE DOOR AND |
| | WINDOW FRAME AS REQUIRED BY SEC. R613.6 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. SEE COMMENTS ON PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |