Plan Review Details - Permit 09040579
Plan Review Stops For Permit 09040579
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-03 Cont ID  
Sent By rmcdouga Date 2009-11-03 Time 14:25 Rev Time 0.00
Received By rmcdouga Date 2009-11-03 Time 14:25 Sent To  
Notes
2009-11-03 14:27:03REVIEWED TRUSS DRAWINGS FOR CODE COMPLIANCE.
  
 CORRECTIONS TO THE TRUSS ANCHOR SCHEDULE ON SHEET S-4
 ARE REQUIRED. ANCHOR MARK 05 SHOULD BE USC 63 BECAUSE
 THE ROOF PITCH IS 6:12. ANCHOR MARK 6.1 SHOULD ALSO BE
 USC 63 WITH AN UPLIFT CAPACITY OF 11,150 #. A SIGNED
 AND SEALED LETTER OF CLARIFICATION FROM THE DESIGNER OF
 RECORD AS DISCUSSED WITH THE ARCHITECT WILL BE
 ACCEPTABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2009-10-20 Cont ID  
Sent By rmcdouga Date 2009-10-20 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2009-10-20 Time 11:16 Sent To  
Notes
2009-10-20 11:18:26TRUSS DRAWINGS ARE DENIED
 CORRECTIONS ARE REQUIRED.
  
 1) THE FLOOR TRUSS AND LOWER ROOF LAYOUT SPECIFIES THE
 DESIGN CRITERIA AS FBC 07 / ASCE 7-05 AND EXPOSURE B.
 THE TRUSS DRAWING COVERSHEET SPECIFIES EXPOSURE C. THE
 LOWER ROOF TRUSS DRAWINGS IN THIS PACKAGE SPECIFY ASCE
 7-02 AND EXPOSURE B WITH TCDL OF 5 PSF AND BCDL OF 5
 PSF. PLEASE COORDINATE THE DESIGN CRITERIA AND LOADS
 WITH THE APPROVED PLANS. THE PLANS WERE PERMITTED UNDER
 THE 2004 FBC / ASCE 7-02 AND EXPOSURE B.
  
 NOTE: YOU CAN DESIGN THE TRUSSES USING FBC 2007 AND
 ASCE 7-05, HOWEVER, BECAUSE OF THE CHANGES TO THE
 EXPOSURE CATEGORY DETERMINATIONS IN THE 2009 REVISIONS
 TO FBC 07, THE STRUCTURE IS IN EXPOSURE CATEGORY C
 USING THIS DESIGN CRITERIA.
  
 2) THE TRUSS LAYOUT DRAWINGS ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE TRUSS ENGINEER. THE SIGNATURE ON THE
 TRUSS DRAWING COVER SHEET IS REQUIRED TO BE AN ORIGINAL
 WET SIGNATURE, PHOTO-COPIES, STAMPS, ETC. ARE NOT
 ALLOWED. FAC 61G-15-23.002 AND FS 471. ELECTRONIC
 SIGNATURES OR DIGITAL SIGNATURES ARE ONLY USED FOR
 PLANS OR OTHER DOCUMENTS ARE TRANSMITTED
 ELECTRONICALLY. SEE SS 668.002 AND FAC 61G15-23.003.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:02:50OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:02 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:03:02OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:03:14OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:03:30OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-09 Cont ID  
Sent By shill Date 2009-09-09 Time 13:40 Rev Time 0.00
Received By shill Date 2009-09-09 Time 13:40 Sent To B
Notes
2009-09-09 13:40:38TO LM DESK (TRUSS ENGINEERING)
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:03:44OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:03:56OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:04 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:04:09OK, PER PERMIT # 08070618 UNDER 2004 FBC

Review Stop Z ZONING
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By dpalmer Date 2009-04-29 Time 16:04 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2009-04-29 16:04:24OK, PER PERMIT # 08070618 UNDER 2004 FBC