Plan Review Details - Permit 09040494
Plan Review Stops For Permit 09040494
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-18 Cont ID  
Sent By shill Date 2009-06-18 Time 17:22 Rev Time 0.00
Received By shill Date 2009-06-18 Time 17:22 Sent To  
Notes
2009-06-18 17:27:37PASSED W/PROVISO & REDLINE
  
 1. CONTRACTOR TO SUBMIT 2ND SET OF PLANS BEFORE
 ISSUANCE (ONLY 1 SET SUBMITTED)
  
 2. REDLINED PLAN - SLOPE OF ACCESSIBLE PARKING ACCESS
 AISLE NOT TO EXCEED 1:50, FBC11-4.6.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-08 Cont ID  
Sent By aaponte Date 2009-06-18 Time 15:16 Rev Time 0.00
Received By shill Date 2009-05-08 Time 10:27 Sent To ENG
Notes
2009-05-08 10:32:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SITE PLAN, A1, DOES NOT INCLUDE ACCESSIBLE PARKING.
 PLEASE CLEARLY SHOW PROPOSED LOCATION, SIGNAGE, AND
 ACCESS AISLE, FBC11-4.6.
  
 2. SHOW ACCESSIBLE ENTRANCE(S) ON THE PLAN,
 FBC11-4.6.2.
  
 3. SHOW THE ACCESSIBLE ROUTE, FBC11-4.5. IT APPEARS
 THAT THE SCOPE OF WORK INCLUDES PAVING, BUT SLOPES ARE
 NOT SHOWN. THE PLANS STATE "SLOPE" WITH ARROWS BUT DOES
 NOT SPECIFY SLOPE. SHOW SLOPE AND CROSS SLOPE FOR THE
 ACCESSIBLE PARKING SPACE, ACCESS AISLE, AND ROUTE TO
 ACCESSIBLE ENTRANCE.
  
 4. WHEN RESUBMITTING, PLEASE ENSURE THAT THE
 ARCHITECT'S IMPRESSED SEAL IS LEGIBLE. FS481,
 FAC61G1-15.
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2010-01-19 Cont ID  
Sent By mgonzale Date 2010-01-19 Time 14:40 Rev Time 1.00
Received By mgonzale Date 2010-01-19 Time 14:39 Sent To  
Notes
2010-01-19 14:41:17ENGINEERING HAS REVIEWED THE STORMWATER CALCS AND PLANS
 AND HAVE APPROVED PLANS. NO FURTHER COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2009-06-19 Cont ID  
Sent By dlauderm Date 2009-06-19 Time 11:22 Rev Time 0.00
Received By dlauderm Date 2009-06-19 Time 11:22 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-05-26 Cont ID  
Sent By mgonzale Date 2009-05-26 Time 14:35 Rev Time 2.00
Received By mgonzale Date 2009-05-26 Time 14:24 Sent To  
Notes
2009-05-26 14:35:20***** NOT APPROVED *****
  
 PLAN NEEDS THE FOLLOWING INFORMATION:
  
 PROJECT NAME
 LOCATION
 PARCEL ID #
 SUBMITTED BY
 DESCRIPTION PREVIOUSLY PERMITTED
 (ACRES)
 CHANGES DUE TO THIS PHASE (ACRES)
 TOTAL PROJECT AREA (ACRES)
 IMPERVIOUS
 PERVIOUS
  
 NEEDS TO SHOW WATER QUALITY ELEMENT FOR STORM WATER
 RETENTION - SUBMIT TO CITY OF WPB ENGINEERING DIV FOR
 APPROVAL (561) 494 1040 PLAN REVIEW
  
 NEW DRIVEWAY WILL NEED A ROW PERMIT WITH ENGINEERING
 DIVISION (561) 494-1040
 HTTP://WWW.CITYOFWPB.ORG/ENGINEERING/UPLOADS/2009-05-11
 -09-51-23-CWPBRIGHT-OF-WAYPERMITPACKAGE.PDF
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/STANDARDS/2007_DET
 AILS_PDFS/GENERAL_CONSTRUCTION/GC-6.PDF
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/STANDARDS/2007_DET
 AILS_PDFS/GENERAL_CONSTRUCTION/GC-7.PDF
  
 NEW DRIVEWAY WILL REQUIRE ADA SLOPES AND DETECTABLE
 WARNING PADS.
 HTTP://WWW.DOT.STATE.FL.US/RDDESIGN/RD/RTDS/06/304.PDF
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-12-09 Cont ID  
Sent By rmcdouga Date 2009-12-09 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2009-12-09 Time 11:05 Sent To  
Notes
2009-12-09 11:06:27TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-18 Cont ID  
Sent By lmartine Date 2009-06-10 Time 16:15 Rev Time 0.00
Received By lmartine Date 2009-06-10 Time 16:15 Sent To  
Notes
2009-06-18 16:16:09C-12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-08 Cont ID  
Sent By shill Date 2009-05-08 Time 11:27 Rev Time 0.00
Received By shill Date 2009-04-22 Time 12:26 Sent To Z
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-12-09 Cont ID  
Sent By rkussner Date 2009-12-09 Time 16:12 Rev Time 0.00
Received By rkussner Date 2009-12-09 Time 16:12 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By rkussner Date 2009-06-18 Time 14:13 Rev Time 0.00
Received By rkussner Date 2009-06-18 Time 14:09 Sent To  
Notes
2009-06-18 14:36:56***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-444 (B), GARBAGE OR TRASH
 RECEPTACLES, FUEL OIL OR PROPANE TANKS, STORAGE RACKS
 AND OTHER MECHANICAL EQUIPMENT SHALL NOT BE PERMITTED
 UNLESS APPRROPRIATE SCREENING IS PROVIDED. THE EXISTING
 CHAINLINK FENCE THAT SURROUNDS THE AIR CONDITIONING
 UNITS SHALL BE CHANGED TO A SOLID WOOD FENCE OR OTHER
 OPAQUE,VISION OBSCURING MATERIAL. SIMILAR SCREENING
 SHALL ALSO BE PROVIDED TO SCREEN THE HOT WATER TANK AND
 CAN WASH.
  
 2. PURSUANT TO SECTION 94-443 (C)(2), VEHICULAR USE
 AREAS SHALL BE SCREENED FROM THOROUGHFARES AND
 RESIDENTIAL USES AND DISTRCTS BY A LANDSCAPE BUFFER OF
 AT LEAST FIVE FEET IN WIDTH. SHADE TREES SHALL BE
 PLANTED AT 30 -FOOT INTERVALS. THIS APPLIES TO THE
 NORTH AND WEST SIDES OF THE SITE. BECAUSE ONLY 3 FEET
 HAS BEEN PROVIDED ALONG THE WEST PERIMETER OF THE
 PARKING LOT, THE PARKING STALLS CAN BE REDUCED TO 16
 FEET WITH A TWO FOOT OVERHANG. INSTEAD OF USING CAR
 STOPS, THE CURBING IS INSTALLED AT THE HEAD OF THE
 STALL. ONLY SOD OR MULCH CAN BE INSTALLED IN THE
 VEHICLE OVERHANG AREA BUT ADDITIONAL GREEN AREA IS
 AVAILABLE FOR THE ROOTS OF THE HEDGE AND TREES.
  
 3. PURSUANT TO SECTION 94-442 (C), PALM TREES MAY BE
 SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE SHADE
 OR FLOWERING TREES REQUIRED BY THIS ARTICLE. WHEN PALM
 TREES ARE SUSTITUTED FOR SHADE TREES, TWO PALM TREES
 SHALL BE PROVIDED FOR EACH REQUIRED SHADE TREE. BECAUSE
 ONLY TWO TREES ARE REQUIRED, NEITHER OF THEM CAN BE
 PALMS.. WHEN SELECTING THE TREE SPECIES, YOU WILL NEED
 TO ADHERE TO THE PRINCIPLES SETFORTH BY FPL'S 'PLANT
 THE RIGHT TREE IN THE RIGHT PLACE' WHICH REGULATES WHAT
 TREES CAN BE PLANTED NEAR OF UNDER OVERHEAD POWER
 LINES. PERHAPS DAHOON HOLLY, EAST PALATKA HOLLY, SILVER
 BUTTOWOOD OR GEIGER TREES COULD BE CONSIDERED.
  
 4. THE APPLICANT SHALL BE RESPONSIBLE TO INSTALL THE
 MISSING GREEN ISLAND FICUS IN THE LANDSCAPE NODE ON
 10TH STREET.
  
 5. AN IRRIGATION PERMIT IS REQUIRED. PLEASE APPLY FOR
 PERMIT AND SUBMIT IRRIGATION PLAN.
  
 6. SUBMIT A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,.

Review Stop Z ZONING
Rev No 3 Status P Date 2009-12-16 Cont ID  
Sent By aaponte Date 2009-12-16 Time 10:11 Rev Time 0.00
Received By aaponte Date 2009-12-16 Time 10:11 Sent To  
Notes
2009-12-16 10:34:33PROVISO:
 DUMPSTER DIMENSION IS ACCEPTABLE IS THE OWNER CHANGES
 THE PROPOSED CONTAINER FOR TWO RESIDENTIAL 93 GALLON
 CONTAINERS.
 IF THE OWNER DECIDES TO MAINTAIN THE DUMPSTER, THE
 ENCLOSURE SHALL BE MODIFIED TO A MINIMUM CLEARANCE OF
 88 INCHES BY 64 INCHES.
 PLEASE CONTACT EMERY FABIAN AT 561-822-1078.
 IF DUMPSTER ENCLOSURE IS MODIFIED, LANDSCAPE DRAWINGS
 SHALL BE REVISED.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-06-19 Cont ID  
Sent By aaponte Date 2009-06-19 Time 08:14 Rev Time 0.00
Received By aaponte Date 2009-06-19 Time 08:14 Sent To B
Notes
2009-06-19 08:17:081.DUMPSTER IS NOT MEETING MINIMUM DIMENSIONS ACCORDING
 TO CITY STANDARDS. A SMALLER DUMSTER NEEDS TO BE
 APPROVED BY ENG. DEPARTMENT. PLEASE CONTACT EMERY
 FABIAN AT 494-1078.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-01 Cont ID  
Sent By shill Date 2009-05-01 Time 11:27 Rev Time 0.00
Received By MFLIS Date 2009-05-01 Time 17:32 Sent To B
Notes
2009-05-01 14:58:16ZONING REVIEW: FAILED
  
 ** PARKING AND LANDSCAPE IMPROVEMENTS
  
 1) PLEASE PROVIDE COPY OF SIGNED/SEALED LANDSCAPE
 DRAWINGS
 2) PLEASE PROVIDE COPY OF IRRIGATION DRAWINGS. PER
 94-445 (G) (3) - IRRIGATION SYSTEMS ARE REQUIRED FOR
 LANDSCAPE AREAS ON ALL PROPERTIES
 3) CORRECT ADA PARKING DETAIL TO CORRECTLY INDICATE
 DIFFERENT COLOR STRIPING (BLUE/WHITE)
 4) INDICATE ADA ACCESSIBLE SIDE AISLE WITH HATCHING ON
 PLAN. ALSO, INDICATE ACCESSIBLE PATH FROM SIDE AISLE TO
 SIDEWALK.
  
 MATT FLIS - 822-1445