Plan Review Details - Permit 09040483
Plan Review Stops For Permit 09040483
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By dpalmer Date 2009-05-11 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2009-05-11 Time 09:59 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 09:18 Sent To PC
Notes
2009-05-06 09:18:17**DENIED PLANS**
  
  
  
 1) NOTE: ALL WIRING METHODS SHALL MEET NEC 525. PLEASE
 BE SURE TO INCLUDE NOTES ACCORDINGLY.
  
 2) NOTE: PLEASE SHOW LOCATIONS AND TYPE OF FIXTURES FOR
 LIGHTING. PLEASE SHOW THE LOCATIONS FOR EGRESS
 LIGHTING, EMERGENCY LIGHTING AND EXIT LIGHTING PER THE
 NFPA-101 2006 7.8 AND 7.9.
  
 3) NOTE: PLEASE NOTE A MINIMUM OF TWO GROUND RODS WILL
 BE REQUIRED. 250.50, 250.56.
  
 4) NOTE: PLEASE INDICATE ALL GFI RECEPTACLE LOCATIONS
 AND ALL AS GFCI PROTECTED PER 210.8B4
  
 5) NOTE: THE GENERATOR LOCATION SHALL MEET MINIMUM
 CLEARANCES FOR EXHAUST PER NFPA-37. THE PLANS DO NOT
 GIVE CLEARANCE DIMENSIONS HOWEVER BASED ON THE PLAN
 LAYOUT THE LOCATION SHOWN IS TOO CLOSE TO BUILDING,
 VENTS, OPENINGS, A/C EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-11 Cont ID  
Sent By dpalmer Date 2009-05-11 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2009-05-11 Time 09:18 Sent To E
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved