Plan Review Details - Permit 09040427
Plan Review Stops For Permit 09040427
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-12 Cont ID  
Sent By shill Date 2009-08-12 Time 11:18 Rev Time 0.00
Received By shill Date 2009-08-12 Time 11:18 Sent To  
Notes
2009-08-12 11:19:59REVISION, SHEET S1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-11 Cont ID  
Sent By lmartine Date 2009-06-11 Time 17:13 Rev Time 0.00
Received By SHILL Date 2009-06-11 Time 17:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-03 Cont ID  
Sent By shill Date 2009-06-03 Time 15:55 Rev Time 0.00
Received By shill Date 2009-06-03 Time 15:55 Sent To  
Notes
2009-06-03 16:14:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENT FROM PREVIOUS LIST:
  
 2. DESIGN PRESSURE APPEARS TOO LOW (+-35PSF). THIS IS A
 HIGH RISE BUILDING LOCATED IN EXPOSURE C. PROVIDE
 ENGINEERING FOR DESIGN PRESSURES FOR THIS OPENING,
 FBC1609.
  
 2ND REVIEW, ENGINEERING NOT PROVIDED. ALSO SEE NEW
 COMMENT
  
 3. THIS IS A COMMERCIAL BUILDING; IS ANY FIRE
 RESISTANCE RATING REQUIRED? HOW HAS THIS BEEN
 DETERMINED? FBC CHAPTER 6, 7.
  
 NOT ADDRESSED OTHER THAN CONTRACTOR'S NOT "NOT
 REQUIRED."
  
 NEW COMMENT:
  
 PROVIDE A LOCATION PLAN SHOWING DOOR LOCATIONS. IT IS
 NOT CLEAR WHETHER THESE DOORS WILL BE INSTALLED IN ZONE
 4 OR ZONE 5, FBC16. APPLICATION STATES "DOUBLE DOOR
 SYSTEM TO MEET WIND LOAD." PLEASE CLARIFY WHAT THIS
 MEANS. BASED ON PAPERWORK PROVIDED, IT APPEARS THAT TWO
 DOORS WILL BE INSTALLED.
  
  
 (NOTE - CALLED CONTRACTOR; CONTR HAS ENGINEERING TO
 CLARIFY ALL ISSUES, WILL PROVIDE WITH THE RESUBMITTAL)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-20 Cont ID  
Sent By shill Date 2009-04-20 Time 15:03 Rev Time 0.00
Received By shill Date 2009-04-20 Time 15:03 Sent To  
Notes
2009-04-20 15:07:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 FAC9B72. THE PRODUCT APPROVAL SUBMITTED IS EXPIRED.
  
 2. DESIGN PRESSURE APPEARS TOO LOW (+-35PSF). THIS IS A
 HIGH RISE BUILDING LOCATED IN EXPOSURE C. PROVIDE
 ENGINEERING FOR DESIGN PRESSURES FOR THIS OPENING,
 FBC1609.
  
 3. THIS IS A COMMERCIAL BUILDING; IS ANY FIRE
 RESISTANCE RATING REQUIRED? HOW HAS THIS BEEN
 DETERMINED? FBC CHAPTER 6, 7.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-06 Cont ID  
Sent By lmartine Date 2009-08-06 Time 10:37 Rev Time 0.00
Received By lmartine Date 2009-08-06 Time 10:37 Sent To  
Notes
2009-08-06 10:37:54GAVE TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-26 Cont ID  
Sent By shill Date 2009-05-26 Time 16:56 Rev Time 0.00
Received By shill Date 2009-05-26 Time 16:56 Sent To B
Notes
2009-05-26 16:56:44TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-20 Cont ID  
Sent By shill Date 2009-04-20 Time 15:07 Rev Time 0.00
Received By shill Date 2009-04-20 Time 11:41 Sent To  
Notes
2009-04-20 11:41:41TO MISC 1
  