Plan Review Details - Permit 09040407
Plan Review Stops For Permit 09040407
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-30 Cont ID  
Sent By jwitmer Date 2009-09-30 Time 16:59 Rev Time 0.50
Received By jwitmer Date 2009-09-30 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-24 Cont ID  
Sent By jwitmer Date 2009-04-24 Time 13:32 Rev Time 2.22
Received By jwitmer Date 2009-04-24 Time 11:56 Sent To  
Notes
2009-04-24 13:59:00BUILDING PLAN REVIEW
 PERMIT: 09040407
 ADD: 529 S FLAGLER DR. #3005
 CONT: WOOLEMS, INC.
 TEL: (561)835-0401
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) COMPLIED FL S S 713.13 NOTICE OF COMMENCEMENT, TO
 BE FILED WITH THE CLERK OF THE COURT. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6) THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009
  
 1D) RENOVATIONS APPLYING AFTER MARCH 1S, 2009 SHALL BE
 REVIEWED TO THE 2007 EXISTING BUILDING CODE WITH 2009
 SUPPLEMENTS, PLEASE INDICATE AS SUCH ON PLANS. PLEASE
 REVIEW SECTION 401.4 OF THE EXISTING BUILDING CODE, THE
 DESIGN PROFESSIONAL OR OWNER(O/B) MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO 403,
 404, 405.
  
 2) PLANS ARE COPIES OF THE 06070806 PERMIT, THEY ARE
 NEITHER SIGNED NOR SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHETECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 3) THE PERMIT APPLICATION NOR PLANS STATE IF THIS WORK
 WAS EVER STARTED UNDER PERMIT 06070806 OR WHAT WORK
 REMAINS TO BE INSPECTED UNDER THE NEW OR CURRENT PERMIT
 APPLICATION. THE EXPIRED PERMIT DID SHOW SOME
 INSPECTION ACTIVITY, A LETTER INDICATING WHAT WORK WILL
 BE COMPLETED UNDERTHIS PERMIT WOULD BE HELPFUL OR IS
 THIS A TOTAL REDESIGN? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED!
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-02 Cont ID  
Sent By dpalmer Date 2009-10-02 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2009-10-02 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 13:35 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 13:35 Sent To  
Notes
2009-04-28 13:35:35**DENIED PLANS**
  
 ** THE MOST IMPORTANT NOTE WHICH CAN BE MADE IS IF
 THERE ARE COMMENTS WHICH ARE NOT UNDERSTOOD OR TYPED IN
 A MANNER WHICH IS NOT CLEAR THEN PLEASE CALL THE
 REVIEWER.
 THIS WILL GREATLY HELP WITH RESOLVING MANY ISSUES WHICH
 MAY DELAY ANY PROJECT.
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS.
  
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70
 2006 NFPA-101
 2002 NFPA-72
  
 PLEASE ADJUST NOTES.
  
 2) NOTE: PLANS SUBMITTED ARE IN FACT PHOTO-COPIES OF
 SIGNED AND SEALED PLANS WHICH ARE NOT PERMITTED. PLEASE
 SUBMIT PLANS IN ACCORDANCE WITH FLORIDA STATUTES
 471.025, AND 481.221. FLORIDA ADMINISTRATIVE CODE
 61G15-23.002
  
 3) NOTE: PLEASE SUBMIT PLANS IN ACCORDANCE WITH THE NEW
 ADOPTED CODES. THE NEC 2005 EDITION IS NOW IN EFFECT
 ALONG WITH NEW BUILDING REQUIREMENTS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-14 Cont ID  
Sent By mawillia Date 2009-10-14 Time 15:09 Rev Time 0.00
Received By mawillia Date 2009-10-14 Time 14:44 Sent To  
Notes
2009-10-14 15:09:11*****APPROVED*****
  
 PLAN SHEETS A-200 AND R-100 WERE STAMPED, INITIALED,
 AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-05-01 Cont ID  
Sent By mawillia Date 2009-05-01 Time 12:55 Rev Time 0.00
Received By mawillia Date 2009-05-01 Time 11:58 Sent To  
Notes
2009-05-01 12:21:25*****DENIED*****
  
 THE FOLLOWING FIRE PLAN REVIEW WAS CONDUCTED BASED ON
 THE SUBMITTED PLAN SHEETS; HOWEVER THESE SHEETS ARE
 COPIES WHICH WERE PREVIOUSLY SIGNED AND SEALED (PLEASE
 SEE OTHER PLAN EXAMINERS' COMMENT(S) IN REFERENCE TO
 THIS MATTER)
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2. THE ADDRESS IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN INDICATES THE PROJECT SITE AS PENTHOUSE 1E &
 CABANA 41. HOW DOES THAT CORRELATE WITH SUITE 30E AS
 LISTED ON THE PERMIT APPLICATION AND/OR IN THE CITY'S
 PERMITTING SYSTEM. PLEASE BE ADVISED THAT THE ACTUAL
 PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 3. THE SUBMITTED PLAN SHEETS MEP-1 THRU P-101 HAVE NO
 PROJECT SITE ADDRESS. PLEASE BE ADVISED THAT THE ACTUAL
 PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.
  
 4. AS OF DECEMBER 31ST 2008, THE 2007 EDITION OF
 FLORIDA FIRE PREVENTION CODE (BASED ON NFPA 101, LIFE
 SAFETY CODE, 2006 EDITION AND NFPA 1, UNIFORM FIRE
 CODE, 2006 EDITION) SHALL BE REFERENCED.
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 6. SHOW THE LOCATION OF THE SMOKE ALARMS (SA) FOR THIS
 PROJECT SITE. UNSURE IF THESE DEVICES ARE THE SAME AS
 THOSE LISTED AS FIRE ALARM LISTED ON SHEET R-100 IN THE
 SYMBOLS LEGEND.
  
 7. UNABLE TO DIFFERENTIATE BETWEEN FIRE ALARM AND
 DECORATIVE PENDANT/SCONCE SURFACE MOUNTED LIGHT AS
 LISTED ON SHEET R-100 IN THE SYMBOLS LEGEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-23 Cont ID  
Sent By lmartine Date 2009-09-23 Time 16:39 Rev Time 0.00
Received By lmartine Date 2009-09-23 Time 16:39 Sent To  
Notes
2009-09-23 16:43:28B--2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-01 Cont ID  
Sent By mawillia Date 2009-05-01 Time 11:58 Rev Time 0.00
Received By mawillia Date 2009-04-22 Time 09:04 Sent To  
Notes
2009-04-22 09:05:12TO "B7"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 11:25 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 11:25 Sent To  
Notes
2009-10-17 11:28:17**PROVISO**
  
 THE FOLLOWING CONDITIONS ARE TO BE ADDRESSED IN THE
 FIELD. NO FURTHER REVISIONS REQUIRED IF WORK IS
 COMPLETED PER THE STAMPED PLANS.
  
 1. DRYER EXHAUST DUCT PENETRATION AT SHAFT ENCLOSURE
 SHALL BE PROTECTED WITH A THROUGH-PENETRATION FIRESTOP
 SYSTEM IN ACCORDANCE WITH FBC-M 607.1.1.
  
 2. EF-2 AND EF-3 ABOVE HARD CEILINGS SHALL BE
 ACCESSIBLE FOR SERVICE OR REPLACEMENT IN ACCORDANCE
 WITH FBC-M 306.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 09:52 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 08:49 Sent To  
Notes
2009-04-30 09:52:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENT
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THE PLANS SUBMITTED WERE ORIGINALLY FOR EXPIRED
 PERMIT #06070806. AS THE PREVIOUS PERMIT HAS EXPIRED,
 THE PROPOSED WORK IS NOW SUBJECT TO THE REQUIREMENTS OF
 THE CODE IN EFFECT AT TIME OF NEW PERMIT APPLICATION.
 THE 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENT IS
 IN EFFECT AS OF MARCH 1, 2009. THESE PLANS ARE3 BEING
 REVIEWED FOR COMPLIANCE WITH THE NEW CODE.
  
 1. PAGE M100 SHOWS SEVERAL NEW DUCT PENETRATIONS OF
 EXISTING SHAFT ENCLOSURES. PLEASE SHOW HOW THESE DUCT
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC-EB 703.2.1.
  
 2. PAGE M100 SHOWS NEW KITCHEN AND DRYER EXHAUST DUCTS
 BEING INSTALLED IN THE CEILING PLENUM AREA. EXHAUST
 DUCTS UNDER POSITIVE PRESSURE SHALL NOT EXTEND INTO OR
 PASS THROUGH A PLENUM IN ACCORDANCE WITH FBC-M 601.5.
  
 3. PAGE M100 (PHOTOCOPY OF PREVIOUS PERMIT SET)
 CONTAINS HAND-WRITTEN NOTES FROM FIELD INSPECTOR
 IDENTIFYING WORK WHICH WAS DONE CONTRARY TO THE
 APPROVED PLANS. WORK SHALL BE INSTALLED IN ACCORDANCE
 WITH THE APPROVED CONSTRUCTION DOCUMENTS, AND ANY
 CHANGES MADE DURING CONSTRUCTION THAT ARE NOT IN
 COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS
 SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBC-B 106.4.
 PLEASE REVISE PLANS TO REFLECT THE WORK WHICH WAS NOT
 DONE IN ACCORDANCE WITH THE PREVIOUS PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By kstevens Date 2009-09-28 Time 11:31 Rev Time 0.00
Received By kstevens Date 2009-09-28 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 15:15 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 15:15 Sent To  
Notes
2009-04-30 15:27:31DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 ADMINISTRATIVE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL PLANS. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS
 OF THIS STATE REGULATING THE PRACTICE OF ARCHITECTURE
 AND PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES PART
 1, OR ENGINEERING AS PROVIDED FOR IN CHAPTER 471,
 FLORIDA STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS AS
 REQUIRED BY FLORIDA STATUTE. SECTION 106.1. PLANS
 SUBMITTED ARE PHOTO COPIES OF SIGNED/SEALED/DATED
 PLANS.
  
 2. ALL PLANS SUBMITTED FOR PERMIT ON OR AFTER MARCH 1,
 2009 SHALL BE DESIGNED TO THE FBC-2007 WITH 2009
 SUPPLEMENTS. PLEASE INDICATE ON THE PLANS THE CORRECT
 DESIGN CRITERIA AND CODE CYCLE. SECTION 106.1.1.
  
 3. SHT P101 A VENT IS REQUIRED AT THE LAV IN THE POWDER
 ROOM. SECTION 901.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-27 Cont ID  
Sent By aaponte Date 2009-04-27 Time 15:10 Rev Time 0.00
Received By aaponte Date 2009-04-27 Time 15:10 Sent To  
Notes
***NONE***