| Plan Review Stops For Permit 09040357 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-09-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-09-09 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-09-09 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-10 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-10 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-05-01 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-05-01 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2009-05-01 16:43:26 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PLEASE REVISE GOVERNING CODE, INCLUDING 2009 | | | SUPPLEMENTS. REVISE SPECIFIC CODE SECTIONS REFERENCED | | | THROUGHOUT THE PLAN TO BE CONSISTENT WITH FBC2007. | | | | | | 2. PLEASE REVISE EXPOSURE CLASSIFICATION OR PROVIDE | | | JUSTIFICATION FOR EXPOSURE B, FBC R301. | | | | | | 3. SHEET S3, STANDARDS ARE OUTDATED; FOR INSTANCE, | | | ASCE7 98, ACI 99. CHECK ALL STANDARDS ON ALL SHEETS AND | | | REVISE, SEE FBC R43. | | | | | | 4. ONLY THE FIRST PAGE WAS PROVIDED FOR ENERGY CALCS; | | | PLEASE PROVIDE COMPLETE FORM FBC13-103. | | | | | | 5. PLYWOOD NAILING, NOTE ON PLYWOOD NAILING DETAIL AND | | | X BRACING CONFLICT WITH OTHER NOTES (SCHEDULE, | | | UNLABELED FLOOR PLAN) S1. SOME STATE 4IN/6IN, OTHERS | | | STATE 3IN/6IN. PLEASE CHECK ALL NOTES FOR CONSISTENCY. | | | NOTE ON S3 STATES 3IN/6IN. | | | | | | 6. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF | | | RECORD, FBC*103. | | | | | | 7. IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | PLANS MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. 233-5025. | | | | | | 8. PLEASE PROVIDE AREA CALCULATIONS; EXISTING SF AREA | | | (UNDER AIR), PROPOSED (UNDER AIR), NEW TOTAL. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-08-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-20 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-20 |
Time |
09:36 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-06-18 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-06-18 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2009-06-18 15:30:07 | | | | ** DENIED PLANS * | | | | | | 1) NOTE: PLANS CONTAIN SEVERAL ITEMS HAND DRAWN ON | | | SHEETS WHICH ARE ALREADY SIGNED, DATED AND SEALED BY | | | THE ARCHITECT. THIS IS NOT PERMITTED PER FS 481.221. | | | PLEASE HAVE SHEETS REVISED BY THE ARCHITECT, SIGNED, | | | DATED AND SEALED WITH THE RAISED SEAL. | | | | | | 2) NOTE: PLEASE COORDINATE CIRCUITING FOR SMOKE ALARMS. | | | THE PANEL SCHEDULE INDICATES THE SMOKE ALARMS ON | | | DEDICATE BATH CIRCUITED WHICH IS NOT PERMITTED. THE | | | PANEL SCHEDULE ALSO INDICATES THE SMOKE ALARMS ON THE | | | CIRCUIT WITH ONE OF THE BEDROOMS. | | | ** SMOKE ALARMS REQUIRED TO BE ON AN ARC FAULT | | | PROTECTED CIRCUIT. SMOKE ALARMS ARE REQUIRED TO BE | | | INTERCONNECTED WHICH WOULD MEAN THESE WOULD ALL BE ON | | | THE SAME AFCI PROTECTED CIRCUIT. (NOT ON BATH PER | | | 210.11C3). | | | | | | 3) NOTE: PLEASE PROVIDE LAYOUT OF EXISTING DWELLING | | | SHOWING NEW OR EXISTING SMOKE ALARMS MEETING CURRENT | | | NFPA-72. PLEASE KNOW THAT PER FS 553.885 IF THE HOUSE | | | HAS AN ATTACHED GARAGE OR GAS APPLIANCES ONE CARBON | | | MONOXIDE DETECTORS ARE REQUIRED. A SMOKE ALARM DEVICE | | | CAN BE A COMBINATION DEVICE. | | | 11.8.3, 11.5.1.1, FBC R313.1 | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-28 |
Time |
11:56 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2009-04-27 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2009-04-28 11:56:20 | **DENIED PLANS** | | | | | | ** THE MOST IMPORTANT COMMENT IS IF THERE ARE COMMENTS | | | WHICH ARE NOT UNDERSTOOD OR TYPED IN A MANNER WHICH IS | | | NOT CLEAR THEN PLEASE CALL THE REVIEWER. THIS WILL | | | GREATLY HELP WITH RESOLVING MANY ISSUES WHICH MAY DELAY | | | ANY PROJECT. | | | | | | | | | 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER | | | MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007 | | | FBC WITH 2009 AMENDMENTS. | | | | | | 2007 FBC W/ 2009 REVISIONS. | | | 2005 NFPA-70 | | | | | | PLEASE ADJUST NOTES. | | | | | | 2) NOTE: PLEASE PROVIDE INFORMATION ON SMOKE | | | ALARMS/DETECTORS PER FBC R313 AND NFPA-72 11.5.1. | | | PLEASE SHOW ALL EXISTING OR NEW SMOKE ALARMS AS | | | REQUIRED. | | | PLANS MAKE REFERENCE TO SMOKE DETECTORS HOWEVER THESE | | | ARE DEVICES WHICH ONLY DETECT AND DO NOT SOUND AN | | | ALARM. IN THIS CASE PLEASE INDICATE THE LOW VOLTAGE | | | FIRE ALARM PANEL AND SOUNDING DEVICES. IF THESE ARE | | | MEANT TO BE DEVICES WHICH DETECT AND SOUND AN ALARM | | | THEN THESE WOULD BE SMOKE ALARMS. | | | PLEASE ADJUST PLANS ACCORDINGLY. | | | | | | CIRCUITS ON PANEL SCHEDULE INDICATE TWO CIRCUITS; | | | HOWEVER AS DEVICES NEED TO BE INTERCONNECTED THEN THESE | | | MAY NOT BE ON MORE THAN ONE CIRCUIT. | | | | | | ** PLEASE ALSO SEE NFPA-72 118.3 AS THE LOCATIONS OF | | | SMOKE ALARMS/DETECTORS NEED TO COMPLY WITH INSTALLATION | | | LOCATIONS WITHIN TRAY CEILING AREAS. | | | | | | 3) NOTE: PLEASE REVISE PANEL SCHEDULE TO SHOW ALL | | | CONDUCTORS, CIRCUITS AND OVER CURRENT PROTECTION | | | DEVICES IN COMPLIANCE WITH THE MINIMUM NEC. | | | 240.4,310.16, 240.6, 408.4 ETC | | | PLEASE SEE ITEMS SUCH AS SPRINKLE PUMP WHICH INDICATES | | | 2-POLE 10AMP BREAKER WITH #6 CONDUCTOR. THIS IS NOT | | | POSSIBLE NOR CODE COMPLIANT. | | | PLEASE SEE THERE ARE OTHER ITEMS SUCH AS THE PANEL | | | SCHEDULE INDICATING A 34 CIRCUIT PANEL. THIS IS NOT A | | | STANDARD PANEL. 110.3 | | | PLEASE SEE LOAD NOTES WHICH STATE A 250AMP PANEL IS | | | RECOMMENDED HOWEVER THE PANEL SHOWN IS A 200AMP PANEL. | | | PLEASE SUBMIT A RISER DIAGRAM SHOWING THE FEEDERS AND | | | OVER CURRENT PROTECTION. THE FACT THE PLANS STATES IT | | | IS A 200AMP PANEL DOES NOT MEAN THE FEEDERS AND OVER | | | CURRENT PROTECTION FEEDING THIS PANEL IS THE | | | SAME.215.5, 240.4, 230 ETC | | | | | | 4) NOTE: THERE ARE UNDER CABINET LIGHTS WHICH DO NOT | | | INDICATE ANY CONTROLS. | | | FBC 106.1.1 FOR CLARITY AND DETAIL OF DOCUMENTS. | | | 210.70, 300,404 | | | | | | 5) NOTE: PLANS INDICATE NEW CABINETS, LAYOUT OF | | | KITCHEN, LIGHTS ETC HOWEVER NO RECEPTACLES PER | | | 210.52C1-5 ARE SHOWN. | | | PLEASE ALSO SEE 210.8A6 FOR REQUIRED GFCI PROTECTION. | | | | | | 6) NOTE: PLEASE SHOW THE DISCONNECT FOR AHU, | | | 440.11,440.14 | | | | | | 7) NOTE: PLEASE SEE 408.4 OF THE 2005 NEC. PANEL | | | SCHEDULES NEED TO BE SPECIFIC TO ALL ROOMS AND AREAS IN | | | WHICH THEY FEED. STATING GENERAL LIGHTS OR GENERAL | | | RECEPTACLES IS NOT PERMITTED. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2009-08-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-26 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-26 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2009-08-26 14:43:54 | PIPE SIZING FOR CSST TO MEET TABLE 402.4(13) SIZING | | | REQUIREMENTS FOR 90 FEET AND THE GALV. DROP TO THE | | | FUTURE POOL HEATER SHALL MEET TABLE 402.4(2) | | | REQUIREMENT FOR 90 FEET. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-16 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-16 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2009-06-16 14:48:14 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 RESIDENTIAL | | | FBC-2007 FUEL GAS | | | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS | | | PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 | | | RESIDENTIAL CODE & FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2007 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1/G2412.8 THRU G2413.6 AND TABLES 402.4(1) | | | THRU | | | 402.4(35)/G2413.4(1) THRU G2413.4(8). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2007 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2007 FUEL | | | GAS CODE SECTION 304 & G2407. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2007 FUEL GAS CODE | | | SECS. 502 THRU 505/G2426 THRU G2429. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2009-12-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-12-07 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-12-07 |
Time |
17:03 |
Sent To |
M |
|
| Notes |
| 2009-12-07 17:03:50 | SENT TO R. REGUEIRO'S DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2009-09-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-09-09 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-09-09 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2009-09-14 16:37:12 | IN ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-07 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-07 |
Time |
15:57 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-06-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-06-04 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-06-04 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-04 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-17 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2009-04-17 15:46:40 | WAITING FOR RESIDENTIAL BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-04 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-01 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2009-05-01 16:46:33 | TO RESIDENTIAL BOARD #13 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
2009-09-17 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-09-17 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-09-17 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-25 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-08-25 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-08-25 |
Time |
12:20 |
Sent To |
|
|
| Notes |
| 2009-08-25 13:04:38 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST | | | OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO | | | UNIT COST. | | | | | | 2. THE STRUCTURE AND HARDSCAPE DID NOT SHOW UP | | | SUFFICIENTLY ON THE LANDSCAPE PLAN TO READ. IT SHALL BE | | | DRAWN DARKER. | | | | | | 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE POINTS. | | | | | | 4. THE LANDSCAPE PLAN SHALL CONTAIN ALL OF THE ELEMENTS | | | LISTED IN SECTION 94-448 (D)(2), INCLUDING A PLANT LIST | | | THAT IDENTIFIES ALL EXISTING AND PROPOSED PLANT | | | MATERIAL AND PROVIDES THE QUANTITY, SIZE AND SPACING. | | | | | | 5. LANDSCAPING IS PROPOSED WITHIN A UTILITIY EASEMENT. | | | THE APPLICANT SHALL OBTAIN WRITTEN APPROVAL FROM THE | | | EASEMENT HOLDER TO ALLOW THE PROPOSED LANSCAPING WITHIN | | | THE EASEMENT. ALL UTILITIES, EASEMENTS, OVERHANGING | | | TREE CANOPIES FROM TREES GROWING ON NEIGHBORING | | | PROPERTY AND ANYTHING ELSE THAT MAY HAVE AN IMPACT ON | | | THE LANDSCAPING SHALL BE SHOWN ON THE LANDSCAPE PLAN TO | | | AVOID CONFLICTS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-08-31 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-31 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-31 |
Time |
08:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-14 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-14 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-14 |
Time |
13:12 |
Sent To |
R |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-05-01 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-05-01 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-05-01 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2009-05-01 10:40:13 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLEASE UPDATE PLANS TO REFERENCE THE CORRECT EDITION | | | OF THE FLORIDA BUILDING CODE AS WELL AS ALL REFERENCED | | | CODE SECTIONS. THE 2007 FLORIDA BUILDING CODE WITH 2009 | | | SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009. | | | | | | 2. PLANS HAVE A NOTE WITH AN OPTION FOR BATH EXHAUST TO | | | BE TERMINATED AT THE SOFFIT. BATHROOM EXHAUST SHALL NOT | | | TERMINATE IN A SOFFIT IN ACCORDANCE WITH FBC-R SECTION | | | M1501.1. | | | | | | 3. PLAN SHOWS THE MAIN RETURN FOR THE AHU LOCATED IN | | | THE KITCHEN. THE KITCHEN IS A PROHIBITED SOURCE OF | | | RETURN AIR IN ACCORDANCE WITH FBC-R SECTION M1602.2. | | | THE RETURN AIR INTAKE MUST BE LOCATED IN AN AREA OF THE | | | HOUSE NOT LISTED AS PROHIBITED UNDER THIS SECTION. | | | | | | 4. ONLY PAGE 1 OF THE FORM 1100-08 ENERGY CODE | | | COMPLIANCE FORM WAS SUBMITTED. PLEASE PROVIDE A | | | COMPLETE FORM (2 SETS ENERGY AND COOLING LOAD) FOR | | | REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2009-06-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-16 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-16 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2009-06-16 14:03:24 | | | | | | | | | | | | | ENLARGING THE SHOWER, MOVING THE LAV WALL BACK APPROX | | | 1'9". DEAD ENDS PROHIBITED. LEAVE CAPPED PIPING FOR THE | | | POWDER ROOM DEMO UNCOVERED UNTILL FIELD INSPECTOR | | | APPROVAL. | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-05-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-05-04 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-05-04 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2009-05-04 09:34:26 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 PLUMBING | | | FBC-2007 CHAPTER 1 AMMENDMENTS | | | | | | 1. SHTS D-1 & A-1 INDICATES THE DESIGN OF THE PLANS PER | | | FBC-2004. ALL APPLICATIONS SUBMITTED ON OR AFTER MARCH | | | 1, 2009 ARE TO BE DESIGNED TO THE FBC-2007 WITH 2009 | | | SUPPLEMENTS. SECTION 106.1.1. | | | | | | 2. SHTS D-1 & A-1 INDICATES A REMODEL OF THE MASTER | | | BATH. PLEASE SHOW THE EXISTING FLOOR PLAN FOR THE | | | MASTER BATH IN ORDER TO SEE THE EXTENT OF THE REMODEL. | | | SECTION 106.1.1, & CHAPTER 7 OF THE PLUMBING CODE. | | | | | | 3. SHT A-1 INDICATES GAS SERVICE TO BE INSTALLED. A | | | SEPARATE GAS PERMIT WITH PLANS IS REQUIRED. SECTION | | | 105.1. | | | | | | 4. (INFORMATIONAL) IF FIXTURES HAVE BEEN MOVED FROM | | | PRESENT LOCATION, A SANITARY RISER DIAGRAM WILL BE | | | REQUIRED PER SECTION 106.3.5.1.3. ALSO IN THE REMOVAL | | | OF ANY PART OF A SANITARY SYSTEM, DEAD ENDS ARE | | | PROHIBITED. SECTION 704.5. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-09-22 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-09-22 |
Time |
09:41 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2009-08-26 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-08-26 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-08-26 |
Time |
13:39 |
Sent To |
P |
|
| Notes |
| 2009-08-26 13:39:42 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE ADDRESS COMMENTS BY LANDSCAPE PLANNER, ROBERT | | | KUSSNER. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-06-16 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-06-16 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-06-16 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2009-06-16 08:48:00 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK | | | EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS | | | "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDR. | | | | | | **CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER, AT | | | 561.822.1462, REGARDING ANY LANDSCAPE CODE REQUIREMENT | | | QUESTIONS.** | | | | | | 3. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH | | | INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION. | | | | | | 4. INDICATE THE SETBACK DIMENSIONS FROM ANY ADDITIONS | | | TO ALL ADJACENT PROPERTY LINES. PURSUANT TO THE ZLDR, | | | SECTION 94-72(A)(2): SINGLE-FAMILY LOW DENSITY (SF7) | | | RESIDENTIAL DISTRICT - MINIMUM SETBACKS FOR PRINCIPAL | | | BUILDING ARE AS FOLLOWS: | | | | | | A. FRONT: 25 FEET; | | | | | | B. CORNER: 12.5 FEET; | | | | | | C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER | | | IS LESS; | | | | | | D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | 4. INDICATE SETBACK DIMENSIONS FROM PROPOSED/RELOCATED | | | A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR, | | | SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT | | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | 5. CLEARLY INDICATE ON THE FLOOR LAYOUT AND ELEVATION | | | PLAN THE LOCATION OF THE PROPOSED WORK, BY LABELING THE | | | AREA "PROPOSED" VS. "EXISTING. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | | | | PLACED BACK IN R17 | | | |
|
|