| 2009-04-16 17:58:50 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PLEASE PROVIDE A SITE PLAN SHOWING LOCATION OF |
| | PROPOSED WORK, FBC*106. |
| | |
| | 2. GOVERNING CODE SHOULD INCLUDE 2009 SUPPLEMENTS |
| | (RATHER THAN 2008); THIS MAY BE CHANGED BY HAND (AND |
| | INITIALED) BY THE ENGINEER. |
| | |
| | 3. CODES AND STANDARDS, ACI 318 IS TO REFERENCE 05 |
| | EDITION (RATHER THAN 02); PLEASE REVISE. |
| | |
| | 4. PLEASE DECLARE WIND DESIGN CRITERIA FBC 1609.4(3). |
| | |
| | 5. PLEASE INCLUDE THE STATEMENT OF COMPLIANCE |
| | (THRESHOLD BUILDING), FS553.79(D): ALL PLANS FOR THE |
| | BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRESAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND CHAPTER |
| | 633. |
| | |
| | 6. PLEASE CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR, |
| | REGARDING THE PROCESS FOR INSPECTIONS FOR THRESHOLD |
| | BUILDINGS, FS553.79. 561-805-6666. PLEASE PROVIDE A |
| | COPY OF THE APPROVED THRESHOLD INSPECTION PLAN AS WELL |
| | AS A COPY OF THE APPROVED INSPECTOR AGREEMENT. BOTH ARE |
| | TO BE APPROVED BY KEN CONRAD PRIOR TO PERMIT ISSUANCE. |
| | |
| | 7. REVISED COMMENT - AS DISCUSSED WITH CONTRACTOR, THIS |
| | IS THE EOR FOR THE PROJECT FAC61G15-31. |
| | |
| | 8. PLEASE NOTE THAT THE ELEVATOR SHAFT PERMIT IS |
| | EXPIRED, 06090238. THIS ISSUE DOES NOT AFFECT THIS |
| | PERMIT APPLICATION BUT MAY AFFECT THE OTHER |
| | APPLICATIONS PENDING AS THE ELEVATOR IS THE ACCESSIBLE |
| | ROUTE FOR THE ROOFTOP STRUCTURE. |
| | |
| | |