Plan Review Details - Permit 09040297
Plan Review Stops For Permit 09040297
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-09-23 Cont ID  
Sent By jwitmer Date 2009-09-23 Time 08:50 Rev Time 0.44
Received By jwitmer Date 2009-09-23 Time 08:30 Sent To  
Notes
2009-09-23 08:52:03REVISION: SHEET A4,S2, S3 & S4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-07-23 Cont ID  
Sent By jwitmer Date 2009-07-23 Time 16:33 Rev Time 1.00
Received By jwitmer Date 2009-07-20 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-12 Cont ID  
Sent By jwitmer Date 2009-06-12 Time 10:51 Rev Time 1.55
Received By jwitmer Date 2009-06-12 Time 10:51 Sent To  
Notes
2009-06-12 10:52:03BUILDING PLAN REVIEW
 PERMIT: 09040297
 ADD: 333 PILGRIM RD
 CONT: O/B RANDALL & KIMBERLY WOLF
 TEL: (561)628-2458
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1- 14) COMPLIED.
  
 15) NEW COMMENET, THE ENERGY PERFORMANCE LEVEL DISPLAY
 CARD INDICATES THE INSULATION UNDER ATTIC WILL BE:
 15A) A VENTED ATTIC
  
 15B) SHEET A.0 FLAT ROOF INDICATES R-30 BATT INSULATION
 WHERE A4.0 INDICATES A SPRAY FOAM AND THE ENERGY CALCS
 INDICATE THE USE OF R-30 INSULATION. PLEASE CORRELATE
 TO THE SAME TYPE OF INSULATION TO BE INSTALLED.
  
 15C) IF ICYNENE INSULATION IS TO BE INSTALLED PLEASE
 NOTE THE LEGACY REPORT INDICATES A MAXIMUM THICKNESS OF
 6". WITH 6" OF ICYNENE PLEASE PROVIDE DOCUMENTATION FOR
 A R-30 VALUE.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-20 Cont ID  
Sent By jwitmer Date 2009-04-20 Time 08:44 Rev Time 2.22
Received By jwitmer Date 2009-04-20 Time 08:43 Sent To  
Notes
2009-04-20 10:04:33BUILDING PLAN REVIEW
 PERMIT: 09040297
 ADD: 333 PILGRIM RD
 CONT: O/B RANDALL & KIMBERLY WOLF
 TEL: (561)628-2458
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO
 THE 2007 FBC RESIDENETIAL BUILDING CODE WITH THE 2009
 SUPPLEMENTS AND THE 2007 EXISTING FLORIDA BUILDING CODE
 WITH 2009 SUPPLEMENTS CHAPTER:
 CHAPTER 4; 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE.
 CHAPTER 10 ADDITIONS
 CHAPTER 11 HISTORIC BUILDING : A CONTRIBUTING BUILDING
  
 2) THERE APPEARS TO BE A DISCREPANCY BETWEEN THE PLANS
 AND THE PERMIT APPLICATION. THE PERMIT APPLICATION
 INDICATES UNDER THE DESCREPTION OF WORK, "MAIN HOUSE
 AND ADDITION". THE PERMIT SEET OF PLANS ALSO INCLUDES
 WORK TO BE COMPLETED ON THE REAR APPARTMENT;
 1) REPLACEMENT OF WINDOWSON THE REAR APARTMENT.
 2) NEW EXTERIOR STAIRS AT THE EXTERIOR APARTMENT.
 3) NEW OVERHANG AT REAR APARTMENT ( SEE ELEVATIONS)
 ELEVATION SHEETS A.2 & A.3 ARE OF THE MAIN HOUSE ONLY!
  
 THE INDEX ALSO FOUND ON THE COVERSHEET OF THE PLANS
 INDICATES THERE TO BE SHEETS CH.1, CH.2, CH-S.2 &
 CH-S.3 WHICH WERE NOT FOUND WITHIN THE PERMIT SET OF
 DOCUMENTS. IF THIS WORK IS TO BE PART OF THIS PROJECT
 IT WOULD BE MORE EFFICIENT TWO CREATE A SECOND PERMIT
 FOR THE REAR APARTMENT. THE INSPECTIONS WOULD BE ABLE
 TO BE IDENTIFIED AS TO WHICH BUILDING EACH INSPECTION
 WOULD HAVE BEEN TIED TO FOR RECORD RETENTION PURPOSES.
  
  
 3) 1105.1 STRICT COMPLIANCE. HISTORIC STRUCTURES OR
 PORTIONS OF SUCH STRUCTURES THAT DO NOT STRICTLY COMPLY
 WITH THIS CODE SHALL BE CONSIDERED TO BE IN COMPLIANCE
 IF IT CAN BE SHOWN TO THE SATISFACTION OF THE BUILDING
 CODE OFFICIAL THAT EQUIVALENT PROTECTION HAS BEEN
 PROVIDED OR THAT NO HAZARD WILL BE CREATED OR CONTINUED
 THROUGH NONCOMPLIANCE.
  
 1105.2 COMPLIANCE OPTION. LIFE SAFETY AND PROPERTY
 CONSERVATION SHALL BE PROVIDED IN ACCORDANCE WITH ONE
 OF THE FOLLOWING OPTIONS:
  
 1. PRESCRIPTIVE-BASED PROVISIONS OF THIS CODE.
  
 2. COMPLIANCE ALTERNATIVE-BASED PROVISIONS OF THIS
 CODE.
  
 3. PERFORMANCE-BASED PROVISIONS OF NFPA 914, CODE FOR
 FIRE PROTECTION OF HISTORIC STRUCTURES, CHAPTER 6,
 ALONG WITH A STRUCTURAL EVALUATION AS SPECIFIED IN
 SECTION 1201.4.1 OF THIS CODE.
  
 4) 1106.1 INVESTIGATION AND EVALUATION REPORT. AN
 HISTORIC BUILDING UNDERGOING ALTERATION OR CHANGE OF
 OCCUPANCY SHALL BE INVESTIGATED AND EVALUATED. IF IT IS
 INTENDED THAT THE BUILDING MEET THE REQUIREMENTS OF
 THIS CHAPTER, A WRITTEN REPORT SHALL BE PREPARED AND
 FILED WITH THE BUILDING OFFICIAL BY A
 FLORIDA-REGISTERED ARCHITECT OR ENGINEER. SUCH REPORT
 SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF SECTIONS
 4.3.1.2 THROUGH 4.3.2 OF NFPA 914, CODE FOR FIRE
 PROTECTION OF HISTORIC STRUCTURES AND SHALL IDENTIFY
 EACH REQUIRED SAFETY FEATURE THAT IS IN COMPLIANCE WITH
 THIS CHAPTER AND WHERE COMPLIANCE WITH THIS OR OTHER
 CHAPTERS WOULD BE DAMAGING TO THE CONTRIBUTING HISTORIC
 FEATURES. IN ADDITION, THE REPORT SHALL DESCRIBE EACH
 FEATURE THAT IS NOT IN COMPLIANCE AND DEMONSTRATE HOW
 THE INTENT OF THE PROVISIONS OF THIS OR OTHER CHAPTERS
 ARE COMPLIED WITH IN PROVIDING AN EQUIVALENT LEVEL OF
 SAFETY.
  
 5A) PLANS DO NOT INDICATE A VENTED UNDER FLOOR
 SPACE.R408.3 UNVENTED CRAWL SPACE.
 VENTILATION OPENINGS IN UNDER-FLOOR SPACES SPECIFIED IN
 SECTIONS R408.1 AND R408.2 SHALL NOT BE REQUIRED WHERE:
  
 1. EXPOSED EARTH IS COVERED WITH A CONTINUOUS VAPOR
 RETARDER. JOINTS OF THE VAPOR RETARDER SHALL OVERLAP BY
 6 INCHES (152 MM) AND SHALL BE SEALED OR TAPED. THE
 EDGES OF THE VAPOR RETARDER SHALL EXTEND AT LEAST 6
 INCHES (152 MM) UP THE STEM WALL AND SHALL BE ATTACHED
 AND SEALED TO THE STEM WALL; AND
  
 2. ONE OF THE FOLLOWING IS PROVIDED FOR THE UNDER-FLOOR
 SPACE:
  
 2.1. CONTINUOUSLY OPERATED MECHANICAL EXHAUST
 VENTILATION AT A RATE EQUAL TO 1 CFM (0.47 L/S) FOR
 EACH 50 FT2 (4.7 M2) OF CRAWLSPACE FLOOR AREA,
 INCLUDING AN AIR PATHWAY TO THE COMMON AREA (SUCH AS A
 DUCT OR TRANSFER GRILLE), AND PERIMETER WALLS INSULATED
 IN ACCORDANCE WITH SECTION N1102.B;
  
 2.2. CONDITIONED AIR SUPPLY SIZED TO DELIVER AT A RATE
 EQUAL TO 1 CFM (0.47 L/S) FOR EACH 50 FT2 (4.7 M2) OF
 UNDER-FLOOR AREA, INCLUDING A RETURN AIR PATHWAY TO THE
 COMMON AREA (SUCH AS A DUCT OR TRANSFER GRILLE), AND
 PERIMETER WALLS INSULATED IN ACCORDANCE WITH SECTION
 N1102.B;
  
 2.3. PLENUM COMPLYING WITH SECTION N110.ABC.3.6, IF
 UNDER-FLOOR SPACE IS USED AS A PLENUM.
  
 5B) PLANS FAIL TO INDICATE UNDER THE FLOOR ACCESS AS
 PER R408.4.
  
 6) SHEET A1 DOES NOT INDICATE ATTIC ACCESS:R807.1 ATTIC
 ACCESS. BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M2) AND
 HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR MORE.
  
 7) SHEET A3 INDICATES ROOFING UNDERLAYMENT NOTES FOR
 NEW SPANISH STYLE ROOFING, THE UNDERLAYMENT NOTES READ
 FOR THAT OF SHINGLES FOR ROOFS WITH LESS THAN A 4/12
 PITCH, PLEASE CORRECT THE UNDERLAYMENT NOTES AS PER
 R905.4.3 UNDERLAYMENT. UNDERLAYMENT SHALL COMPLY WITH
 ASTM D 226, TYPE I OR TYPE II OR ASTM D 1970 OR ASTM D
 4869. UNDERLAYMENT SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. SEE
 THE MIAMI- DADE NOA FOR REQUIREMENTS.
  
 THE MIAMI-DADE NOA FOR ARTEZANOS WORLD CLASS TWO PIECE
 HANDMADE TAPERED MISSION BARREL ROOF TILE UNDER TABLE 4
 HAS TWO TYPES OF APPLICATION, A MORTAR SET AND ADHESIVE
 SET SYSTEM.
 PLEASE CIRCLE WHICH SYSTEM IS TO BE INSTALLED WITH THE
 APPROPRIATE FOOT POUNDS.
  
 8) SHEET A-4 DETAIL 5 /S3 INDICATES A SINGLE PLY
 MEMBRANE ROOF THE OWNER SUBMITTED A MIAMI-DADE NOA
 TARCO 30# ASTM SPECIFICATION FELT EASY LAY, FAST 90,
 PS200 REPORT NOA 07-0717.04 THIS REPORT INDICATES IT IS
 TO BE USED WITH ROOF TILE, NO PRODUCT APPROVALS HAVE
 BEEN SUBMITTED FOR THE BALCONY COVERED FLOOR (FLOOR)
 THAT CAN BE USED AS A WALKABLE DECK AREA.
  
 9) SHEET S.1 THE PLANS INDICATE IN MULTIPLE AREAS THAT
 THE WIND DESIGN WAS DESIGNED UNDER ASCE 7-02, THE
 CURRENT 2007 FBC RESIDENTIAL IS DESIGNED UNDER THE ASCE
 7-05 SEE REFRENCED STANDARDS.
  
 10) SHEET S-1 SECTION D-4 ROOF LOADING INDICATES DEAD
 LOADBOTTOM CORD OF 10 LBS WHEREAS SHEET S-4 INDICATES A
 DEAD LOAD OF 10 LBS AND LIVE LOAD OF 10LBS. TABLE
 R301.5 ATTICS WITHOUT STORAGE
 INDICATE 10 LBS. LIVE LOAD.
  
 11) THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS. PLEASE PROVIDE WHERE COMPLIANCE IS
 TO BE MET.
  
 12) GUARD RAIL SHEET S-3 DETAIL# 5 INDICATES THE USE OF
 A WOOD GUARD RAIL SYSTEM PLEAE PROVIDE CALCULATIONS HOW
 200 LBS LIVE LOAD WILL BE MET TABLE R301.5 FOOTNOTE D.
 A SINGLE CONCENTRATED LOAD APPLIED IN ANY DIRECTION AT
 ANY POINT ALONG THE TOP.
  
 13) DISCREPANCY BETWEEN S.2 DETAIL# 3 AND SHEET S-4
 STRUCTURAL CONNECTIONS. SHEET S-2 INDICATES THE USE OF
 1/4" TAPCONS AT 32" O.C. WHERE AS S.4 INDICATES THE USE
 OF 1?2 INCHX 5 INCH WEDGE ANCHORS AT 32" O. C.
  
 14) RADON FEES OWED OF $21.04.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-06-22 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2009-06-22 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-21 Cont ID  
Sent By btrobaug Date 2009-04-21 Time 12:08 Rev Time 0.00
Received By btrobaug Date 2009-04-21 Time 10:57 Sent To  
Notes
2009-04-21 12:08:12 
  
  
 APPLICATION #09040297 ELECTRICAL PLAN REVIEW
 333 PILGRIM ROAD 4/21/09
 WEST PALM BEACH, FL.
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET E1UNLESS OTHERWISE NOTED.
  
 1} SHEET A.0 REFERENCES REAR APARTMENT SHEETS BUT NONE
 WERE SUBMITTED, THE APPLICATION ONLY MENTIONS WORK TO
 THE MAIN HOUSE BUT HAS BEEN ALTERED WITH WHITE OUT.
 INDICATE THE INTENTION OF THE SCOPE OF WORK AND SUBMIT
 PLANS ACCORDINGLY. 106.1.1 FBC AS AMENDED.
  
 2} LOCATE THE DISCONNECT FOR THE MAIN HOUSE ON THE
 PLAN. 225.31.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1) AND
 210.52(A)(2). 2005 NEC. SEE PARTITION WALLS BETWEEN THE
 LIVING ROOM AND DINING ROOM.
  
 4} THE HALLWAY ON THE SECOND FLOOR PLAN (SHEET E.2) IS
 REQUIRED TO HAVE A RECEPTACLE PER 210.52(H).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-07-21 Cont ID  
Sent By kstevens Date 2009-07-21 Time 15:45 Rev Time 0.00
Received By kstevens Date 2009-07-21 Time 15:45 Sent To  
Notes
2009-07-21 15:46:05SEE PERMIT NUMBER 09050462.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-06-16 Cont ID  
Sent By kstevens Date 2009-06-16 Time 09:03 Rev Time 0.00
Received By kstevens Date 2009-06-16 Time 09:03 Sent To  
Notes
2009-06-16 09:13:29DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 RESIDENTIAL CODE & FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1/G2412.8 THRU G2413.6.1 AND TABLES 402.4(1)
 THRU
 402.4(35)/G2413.4(1) THRU G2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTIONS 304 & G2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2. & G2413.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & G2426 THRU G2429.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-04-13 Cont ID  
Sent By swurafti Date 2009-04-13 Time 15:35 Rev Time 0.00
Received By swurafti Date 2009-04-13 Time 15:35 Sent To  
Notes
2009-04-13 15:35:28HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-22 Cont ID  
Sent By lmartine Date 2009-09-22 Time 16:19 Rev Time 0.00
Received By lmartine Date 2009-09-22 Time 16:19 Sent To  
Notes
2009-09-22 16:20:09GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-10 Cont ID  
Sent By lmartine Date 2009-07-10 Time 16:50 Rev Time 0.00
Received By lmartine Date 2009-07-10 Time 16:50 Sent To  
Notes
2009-07-10 16:51:43R-5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-03 Cont ID  
Sent By btrobaug Date 2009-06-22 Time 11:37 Rev Time 0.00
Received By btrobaug Date 2009-06-03 Time 16:01 Sent To  
Notes
2009-06-04 16:01:44TO R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-02 Cont ID  
Sent By rbrown Date 2009-05-12 Time 20:59 Rev Time 0.00
Received By rbrown Date 2009-04-13 Time 08:55 Sent To  
Notes
2009-04-14 08:56:17SENT RES #6

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2010-03-05 Cont ID  
Sent By rkussner Date 2010-03-05 Time 14:13 Rev Time 0.00
Received By rkussner Date 2010-03-05 Time 14:13 Sent To  
Notes
2010-03-05 14:34:01***LANDSCAPE REVISION #10020553 FAILED***
  
 1. IRRIGATION MUST BE APPROVED THROUGH A SEPARATE
 PERMIT.
  
 2. WEDELIA IS A PROHIBITED SPECIES AND CANNOT BE
 PLANTED.
  
 3. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED. SOD MUST BE PLANTED IN THE
 RIGHT-OF-WAY UNLESS YOU OBTAIN WRITTEN APPROVAL FROM
 THE ENGINEERING DEPARTMENT TO USE SHRUBS OR GROUND
 COVER. MULCH IS NOT A SUITABLE GROUND COVER.
  
 4. OPEN SPACE IS CALCULATED BY TAKING THE TOTAL LOT
 AREA AND DEDUCTING THE BUILDING FOOTPRINT. THE
 DIFFERENCE IS THE OPEN SPACE FOR WHICH THE LANDSCAPE
 CALCUATIONS ARE BASED UPON. PLEASE PROVIDE THE TOTAL
 LOT AREA AND THE SQUARE FOOTAGE OF THE STRUCTURES.
  
 5. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL
 AREAS, INCLUDING THE RIGHT-OF-WAY) THAT ARE TO BE
 PLANTED IN A CULTIVATED LANDSCAPE, IRRIGATION SYTEMS
 SHALL BE DESIGNED TO HAVE 120 PERCENT COVERAGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT KUSSNE
 @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-07-13 Cont ID  
Sent By rkussner Date 2009-07-13 Time 15:47 Rev Time 0.00
Received By rkussner Date 2009-07-13 Time 15:47 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-06-09 Cont ID  
Sent By rkussner Date 2009-06-09 Time 15:45 Rev Time 0.00
Received By rkussner Date 2009-06-09 Time 15:45 Sent To  
Notes
2009-06-09 16:20:09***LANDSCAPE REVIEW FAILED***
  
 1. THE STREETS AND RIGHTS-OF-WAY SHALL BE IDENTIFIED ON
 THE LANDSCAPE PLAN.
  
 2. SOD AND IRRIGATION IS REQUIRED IN THE RIGHT-OF-WAYL
  
 3. PROVIDE SCREENING FOR AIR CONDITIONING UNITS,
 GARBAGE CONTAINERS AND OTHER MECHANICAL EQUIPMENT.
  
 4. IN KEEPING WITH XERISCAPE PRINCIPLES, THE PALMS
 SHALL BE INCORPORATED INTO A PLANT BED AND THE OTHER
 PROPOSED AND EXISTING PLANTINGS SHALL BE INCORPORATED
 INTO PLANT BEDS WITH THE BED LINES SHOWN ON THE PLAN.
  
 5. ALL EXISITNG PLANT MATERIAL SHALL BE IDENTIFIED BY
 NAME AND SIZE.
  
 6. PLEASE SHOW THE OVERHEAD LINES. THE PROPOSED
 REVENALA MADAGASCAR TREES MAY BE TOO CLOSE TO THE
 LINES. YOU MUST ABIDE BY FPL'S 'PLANT THE RIGHT TREE IN
 THE RIGHT PLACE' GUIDELINES FOR PLANTING TREES NEAR OR
 UNDER POWER LINES.
  
 7. ADDITIONAL FOUNDATION PLANTING IS RECOMMENDED FOR
 THE STREET SIDE OF THE HOME.
  
 8. SUBMIT COST ESTIMATE THE INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462,

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-07-27 Cont ID  
Sent By rregueir Date 2009-07-27 Time 15:15 Rev Time 0.00
Received By rregueir Date 2009-07-27 Time 15:01 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-07-08 Cont ID  
Sent By rregueir Date 2009-07-08 Time 09:06 Rev Time 0.00
Received By rregueir Date 2009-07-08 Time 09:05 Sent To PC
Notes
2009-07-08 09:06:31REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CODE COMPLIANCE FORM 1100A-08 WAS PROVIDED, BUT IS
 INCOMPLETE. THE PAGE SUBMITTED IS PAGE 1 OF 6. THE
 REMAINING 5 PAGES WERE NOT SUBMITTED. PLEASE PROVIDE A
 COMPLETE COMPLIANCE FORM IN ORDER FOR REVIEWER TO
 CONFIRM THE DATA WHICH WAS INPUT CORRESPONDS WITH THE
 SUBMITTED PLANS.
  
 2. FLOOR PLANS AND THE DATA SHOWN ON THE INCOMPLETE
 ENERGY CODE COMPLIANCE FORM DO STILL NOT CORRESPOND.
 PLEASE SEE BUILDING REVIEW COMMENT #15 FOR ADDITIONAL
 INFORMATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-24 Cont ID  
Sent By rregueir Date 2009-04-24 Time 16:21 Rev Time 0.00
Received By rregueir Date 2009-04-24 Time 14:41 Sent To  
Notes
2009-04-24 16:20:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CODE COMPLIANCE FORM 1100A-08 WAS PROVIDED, BUT IS
 INCOMPLETE. THE PAGE SUBMITTED IS PAGE 1 OF 6. THE
 REMAINING 5 PAGES WERE NOT SUBMITTED. PLEASE PROVIDE A
 COMPLETE COMPLIANCE FORM IN ORDER FOR REVIEWER TO
 CONFIRM THE DATA WHICH WAS INPUT CORRESPONDS WITH THE
 SUBMITTED PLANS.
 EVEN WITHOUT THE COMPLETE REPORT, SOME DISCREPANCIES
 CAN BE IDENTIFIED. EXAMPLE: ENERGY CODE COMPLIANCE FORM
 CALLS FOR R-30 ROOF INSULATION WHILE THE PLANS CALL FOR
 R-19. WHEN SUBMITTING A COMPLETE FORM, PLEASE CONFIRM
 THAT THE THE FORM ACCURATELY REFLECTS THE SYSTEMS AND
 COMPONENTS SHOWN ON THE PLANS IN ACCORDANCE WITH FBC-R
 SECTION N1100.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-06-16 Cont ID  
Sent By kstevens Date 2009-06-16 Time 08:52 Rev Time 0.00
Received By kstevens Date 2009-06-16 Time 08:52 Sent To  
Notes
2009-06-16 08:54:20SHT P.1 INDICATES A GAS TANKLESS WATER HEATER. SEPARATE
 GAS PERMIT/PLANS REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 09:18 Rev Time 0.00
Received By kstevens Date 2009-04-28 Time 16:56 Sent To  
Notes
2009-04-30 09:33:33DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 CITY WPB AMENDMENTS (CHAPTER 1)
  
 1. SHT P.1 SECOND FLOOR PLUMBING PLAN & SANITARY RISER
 DIAGRAM. PER TABLE 906.1 THE MAXIMUM DISTANCE OF
 FIXTURE TRAP FROM THE VENT IS 8 FEET FOR 2". THE SHOWER
 SCALES OUT TO APPROX. 13 FEET. PLEASE SHOW CORRECT
 VENTING FOR THE SHOWER.
  
 2. SHT P.1 DETAIL 2 SECOND FLOOR SANITARY AND SECOND
 FLOOR PLUMBING PLAN SHOW A 2ND LAV ON THE SANITARY
 PIPING BUT THE 2ND LAV IS NOT SHOWN ON THE FLOOR PLAN
 NOR ON THE FLOOR PLAN ON SHT A.1 DETAIL 2. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 405.3.1.
  
 3. SHT P.1 INDICATES A TANKLESS GAS WATER HEATER.
 SEPARATE GAS PERMIT & PLANS SHALL BE SUBMITTED. SECTION
 105.1.
  
 4. SHT S.4 SIZING OF THE VERTICAL LEADERS & OVERFLOW
 SCUPPERS IS INDICATED AS BEING FROM THE FBC-2004
 EDITION. THE PRESENT CODE CYCLE IS THE FBC-2007
 EDITION. PLEASE SHOW DESIGN FROM THE CORRECT CODE
 CYCLE. SECTION. ALSO THE CALCULATIONS INDICATE LEADERS
 PROVIDED. THE PLANS DO NOT SHOW LEADERS. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-07-05 Cont ID  
Sent By mcruz Date 2009-07-05 Time 14:43 Rev Time 0.00
Received By mcruz Date 2009-06-09 Time 18:02 Sent To  
Notes
2009-07-05 14:43:19PASSED WITH PROVISO:
 THE LANDSCAPE/IRRIGATION PLANS SHALL BE APPROVED PRIOR
 TO FINAL C.O.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-05-12 Cont ID  
Sent By mcruz Date 2009-05-12 Time 14:09 Rev Time 0.00
Received By mcruz Date 2009-05-12 Time 13:57 Sent To  
Notes
2009-05-12 14:09:27PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. THE EXISTING DRIVEWAY IS LOCATED ON THE WEST SIDE OF
 THE PROPERTY. THE PROPSED SITE PLAN INDICATES A NEW
 BRICK DRIVEWAY BEING PLACED ON THE EAST SIDE OF THE
 LOT. IS THIS IN ADDITION TO THE EXISTING DRIVEWAY?
 PLEASE CLARIFY.
  
 NOTE THAT A SECOND ACCESS POINT IS NOT ALLOWED ON A
 SINGLE FAMILY RESIDENTIAL LOT. YOU MAY RELOCATE
 DRIVEWAY, BUT NOT CREATE AN ADDITIONAL ACCESS POINT PER
 THE ZLDR, SECTION 94-313, A MAXIMUM OF ONE (1) ACCESS
 POINT IS ALLOWED IN RESIDENTIAL TYPES OF DEVELOPMENT OF
 LESS THAN 75 UNITS.
  
 ADDITIONALLY, A A RIGHT-OF-WAY PERMIT WILL NEED TO BE
 ACQUIRED FROM THE CITY'S ENGINEERING DEPARTMENT
 (561.494.1040), FOR THE PROPOSED APPROACH EXTENSION.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  