| 2009-05-11 11:12:42 | RESIDENTIAL (R3) REMODELING, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 1- PLANS NEED TO BE DESIGNED PER FBC 2007 NOT FBC 2001. |
| | REVISE GENERAL NOTE #1 IN ALL DRAWINGS SUBMITTED. |
| | |
| | 2- NEED TO PROVIDE THE NAME AND SIGNATURE OF THE DESIGN |
| | PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THIS |
| | STRUCTURE. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT |
| | OR ENGINEER, THEN PLANS NEED TO BE SIGNED AND SEALED |
| | ACCORDINGLY AS REQUIRED BY CHAPTER 481/471 FLORIDA |
| | STATUTES. SEC. 106.1 CITY AMENDMENTS TO FBC. |
| | |
| | 3- PROVIDE ALL DESIGN INFORMATION REQUIRED BY SEC. |
| | R301.1 OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY ALL |
| | DESIGN LOADS. SPECIFY ALL DEAD LOADS, LIVE LOADS, ROOF |
| | LOADS AND WIND LOADS. |
| | ALSO, SPECIFY ALL DESIGN PRESSURES FOR DOORS AND |
| | WINDOWS. |
| | |
| | 4- PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH THE |
| | PROTECTION AGAINST WOOD DECAY FOR FLOOR JOISTS ON FIRST |
| | FLOOR CRAWLING AREA AS REQUIRED BY SEC. R319 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- ALL FLOOR FRAMING PLANS AND DETAILS SECTIONS NEED TO |
| | PROVIDE COMPLETE INFORMATION SHOWING ALL CONNECTORS |
| | THAT PROVIDE A CONTINUOUS LOAD PATH AS REQUIRED BY SEC. |
| | R601.2 OF 2007 FLORIDA RESIDENTIAL CODE. EG: FLOOR |
| | FRAMING PLANS ON SHEET A-2 ARE MISSING CONNECTIONS OF |
| | 2X10 FLOOR JOISTS ON BOTH ENDS, INCLUDING ATTACHMENT OF |
| | LEDGERS. WALL SECTIONS ON SHEET A-5 DON'T PROVIDE |
| | COMPLETE INFORMATION FOR CONNECTION OF 2X10 JOIST TO |
| | BEARING WALLS.. WALL SECTIONS ARE MISSING ATTACHMENT OF |
| | 2X4 STUDS AT BOTTOM END. |
| | |
| | 6- PROVIDE 2 COPIES OF EACH PRODUCT APPROVALS AS |
| | REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) EXTERIOR DOOR. CLARIFY WHICH PRODUCT APPROVAL IS |
| | GOING TO BE USED. THERE ARE TWO DIFFERENT PRODUCT |
| | APPROVALS SUBMITTED. CLARIFY IF USING NOA 07-0820.08 |
| | (JELD-WEN DOOR) OR OTHER PRODUCT FROM MASONITE |
| | INTERNATIONAL. |
| | NOTE: MASONITE INTERNATIONAL PRODUCT APPROVAL SUBMITTED |
| | IS INCOMPLETE AND NEED STORM SHUTTERS. NEED TO PROVIDE |
| | COVER PAGE OF PRODUCT APPROVAL AND COMPLETE INFORMATION |
| | FOR STORM SHUTTERS INCLUDING SHUTTERS PRODUCT APPROVAL |
| | AND COMPLETE INSTALLATION SCHEDULE. |
| | |
| | B) SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE |
| | SUBMITTED. |
| | |
| | C) FLAT ROOF PRODUCT APPROVAL: * INDICATE WHICH |
| | APPROVED ASSEMBLY FROM NOA 05-0819.05 IS GOING TO BE |
| | USED. ** SPECIFY WHICH BASE SHEET FASTENING OPTION IS |
| | GOING TO BE USED. *** PROVIDE RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE ON NOA |
| | SUBMITTED. |
| | |
| | 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 8- OWES $62.17. PERMIT VALUATION WAS NOT ENTERED AT |
| | TIME OF PERMIT APPLICATION. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |