Plan Review Details - Permit 09040295
Plan Review Stops For Permit 09040295
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By jgomez Date 2010-02-25 Time 09:38 Rev Time 0.00
Received By jgomez Date 2010-02-25 Time 09:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-05-11 Cont ID  
Sent By jgomez Date 2009-05-11 Time 10:15 Rev Time 0.00
Received By jgomez Date 2009-05-11 Time 10:10 Sent To PC
Notes
2009-05-11 11:12:42RESIDENTIAL (R3) REMODELING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE.
  
 1- PLANS NEED TO BE DESIGNED PER FBC 2007 NOT FBC 2001.
 REVISE GENERAL NOTE #1 IN ALL DRAWINGS SUBMITTED.
  
 2- NEED TO PROVIDE THE NAME AND SIGNATURE OF THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THIS
 STRUCTURE. IF THE DESIGN PROFESSIONAL IS AN ARCHITECT
 OR ENGINEER, THEN PLANS NEED TO BE SIGNED AND SEALED
 ACCORDINGLY AS REQUIRED BY CHAPTER 481/471 FLORIDA
 STATUTES. SEC. 106.1 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE ALL DESIGN INFORMATION REQUIRED BY SEC.
 R301.1 OF 2007 FLORIDA RESIDENTIAL CODE. SPECIFY ALL
 DESIGN LOADS. SPECIFY ALL DEAD LOADS, LIVE LOADS, ROOF
 LOADS AND WIND LOADS.
 ALSO, SPECIFY ALL DESIGN PRESSURES FOR DOORS AND
 WINDOWS.
  
 4- PROVIDE SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 PROTECTION AGAINST WOOD DECAY FOR FLOOR JOISTS ON FIRST
 FLOOR CRAWLING AREA AS REQUIRED BY SEC. R319 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 5- ALL FLOOR FRAMING PLANS AND DETAILS SECTIONS NEED TO
 PROVIDE COMPLETE INFORMATION SHOWING ALL CONNECTORS
 THAT PROVIDE A CONTINUOUS LOAD PATH AS REQUIRED BY SEC.
 R601.2 OF 2007 FLORIDA RESIDENTIAL CODE. EG: FLOOR
 FRAMING PLANS ON SHEET A-2 ARE MISSING CONNECTIONS OF
 2X10 FLOOR JOISTS ON BOTH ENDS, INCLUDING ATTACHMENT OF
 LEDGERS. WALL SECTIONS ON SHEET A-5 DON'T PROVIDE
 COMPLETE INFORMATION FOR CONNECTION OF 2X10 JOIST TO
 BEARING WALLS.. WALL SECTIONS ARE MISSING ATTACHMENT OF
 2X4 STUDS AT BOTTOM END.
  
 6- PROVIDE 2 COPIES OF EACH PRODUCT APPROVALS AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) EXTERIOR DOOR. CLARIFY WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. THERE ARE TWO DIFFERENT PRODUCT
 APPROVALS SUBMITTED. CLARIFY IF USING NOA 07-0820.08
 (JELD-WEN DOOR) OR OTHER PRODUCT FROM MASONITE
 INTERNATIONAL.
 NOTE: MASONITE INTERNATIONAL PRODUCT APPROVAL SUBMITTED
 IS INCOMPLETE AND NEED STORM SHUTTERS. NEED TO PROVIDE
 COVER PAGE OF PRODUCT APPROVAL AND COMPLETE INFORMATION
 FOR STORM SHUTTERS INCLUDING SHUTTERS PRODUCT APPROVAL
 AND COMPLETE INSTALLATION SCHEDULE.
  
 B) SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED.
  
 C) FLAT ROOF PRODUCT APPROVAL: * INDICATE WHICH
 APPROVED ASSEMBLY FROM NOA 05-0819.05 IS GOING TO BE
 USED. ** SPECIFY WHICH BASE SHEET FASTENING OPTION IS
 GOING TO BE USED. *** PROVIDE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE LAST PAGE ON NOA
 SUBMITTED.
  
 7- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 8- OWES $62.17. PERMIT VALUATION WAS NOT ENTERED AT
 TIME OF PERMIT APPLICATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-10 Cont ID  
Sent By dpalmer Date 2010-02-10 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2010-02-10 Time 08:49 Sent To  
Notes
2010-02-10 08:50:05*REDLINED/PROVISO*
  
 PLEASE REVISE PLANS BEFORE FINAL. IF THERE ARE OTHER
 REVISIONS OR SUBSTANTIAL CHANGES THEN THOSE CHANGES
 WILL NEED TO BE REVISED BEFORE ROUGH.
  
  
 1) NOTE: SMOKE DETECTOR ADDED TO LAUNDRY ROOM. HOWEVER
 THAT WAS NOT THE PREVIOUS COMMENT. PLEASE SEE FBC
 R313.1 AND 313.4 WHICH REQUIRES SMOKE ALARMS AND CARBON
 MONOXIDE ALARM(S) TO MEET CURRENTS CODES WHEN DOING
 WORK AS DESCRIBE IN THE SECTIONS NOTED.
 PLEASE SEE NFPA-72 11.5.1, 118.3 FOR SMOKE ALARM
 LOCATIONS.
 PLEASE REVISE TO SHOW LOCATIONS AS REQUIRED INSIDE AND
 OUTSIDE SLEEPING ROOMS. PLANS SHOW ONE IN LAUNDRY ROOM
 HOWEVER IT IS NOT REQUIRED IN THE LAUNDRY ROOM.
  
 2) NOTE: LOAD CALCULATIONS DO NOT COORDINATE WITH THE
 SUBMITTED PANEL SCHEDULE. FOR EXAMPLE, THE ADDITIONAL
 ONE OR MORE SMALL APPLIANCE CIRCUIT(S) SHALL BE FIGURED
 AT 1500VA. THIS WOULD REQUIRE 1500VA FOR THE TWO
 MINIMUM AND 1500VA FOR EACH ABOVE THE TWO.
 210.11C1, 220.52
 LOAD CALCULATIONS STATE THERE ARE 57 CIRCUITS, HOWEVER
 PANEL SCHEDULE SHOWS PANEL BEING A 20 CIRCUIT PANEL?
 408.4.
  
 3) NOTE: NO MINIMUM CONDUCTOR SIZES PER NEC 310.16 ON
 PANEL SCHEDULE.
  
 4) NOTE: BASED ON THE SYMBOL LEGEND, THE WASHER
 RECEPTACLE IS SHOWN AS A DUPLEX WHEN IT IS REQUIRED TO
 BE A DEDICATED SINGLE RECEPT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-27 Cont ID  
Sent By dpalmer Date 2009-04-27 Time 14:34 Rev Time 0.00
Received By dpalmer Date 2009-04-27 Time 14:34 Sent To  
Notes
2009-04-27 14:34:39**DENIED PLANS**
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS.
  
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70
  
 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS/ DETAILS FOR
 THE ELECTRICAL SCOPE OF WORK. THE FLOOR PLAN HAS SOME
 ITEMS HOWEVER NOT COMPLETE FOR CODE COMPLIANT FOR A NEW
 LAUNDRY ROOM.
 PLEASE SHOW LOCATIONS OF NEW LAUNDRY EQUIPMENT.
 PLEASE BE SURE TO SEE THAT LAUNDRY AND WASHER CIRCUITS
 SHALL BE DEDICATED AND REQUIRED SIZING PER 210.52F,
 210.11C2, AND LOADS PER 220.52.
 PLEASE SEE 220.54 FOR ELECTRIC DRYERS.
 PLEASE SEE 310.16, 240. FOR SIZING OF CONDUCTORS.
 PLEASE SEE 210.8A7 FOR REQUIRED GFCI PROTECTION.
 PLEASE SEE 210.70 FOR LIGHTING FOR ROOM AND EGRESS
 EXIT.
 ETC
 ** PLEASE SEE 220 FOR LOAD CALCULATIONS
 ** PLEASE SHOW PANEL SCHEDULE FOR DEDICATED NEW
 CIRCUITS. BREAKER SIZES AS NOTED ABOVE FOR BRANCH
 CIRCUITS.
  
 3) NOTE: PLEASE SEE FBC R313 AND NFPA-72 11.5.1. PLEASE
 SHOW ALL EXISTING OR NEW SMOKE ALARMS AS REQUIRED.
  
 *** IMPORTANT: AS MOST ELECTRICAL IS NOT SHOWN FOR
 MINIMUM COMPLIANCE IT IS NOT POSSIBLE TO GIVE A FULL
 REVIEW FOR CODE COMPLIANCE. THERE MAY BE NEW COMMENTS
 ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-09 Cont ID  
Sent By btrobaug Date 2010-02-09 Time 10:47 Rev Time 0.00
Received By btrobaug Date 2010-02-09 Time 10:47 Sent To  
Notes
2010-02-09 10:51:51R-5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-11 Cont ID  
Sent By jgomez Date 2009-05-11 Time 11:12 Rev Time 0.00
Received By jgomez Date 2009-04-13 Time 08:52 Sent To  
Notes
2009-04-14 08:52:30SENT TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-05-01 Cont ID  
Sent By rregueir Date 2009-05-01 Time 09:01 Rev Time 0.00
Received By rregueir Date 2009-05-01 Time 09:00 Sent To  
Notes
2009-05-01 09:01:23NO MECHANICAL SCOPE ON THIS PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-04-30 Cont ID  
Sent By kstevens Date 2009-04-30 Time 10:39 Rev Time 0.00
Received By kstevens Date 2009-04-30 Time 10:33 Sent To  
Notes
2009-04-30 10:40:46APPLICATION INDICATES LAUNDRY ROOM, BUT NO PLUMBING
 PLANS SUBMITTED. SEPARATE PLUMBING PLANS/PERMIT
 REQUIRED IF PLUMBING WORK TO BE DONE IN THE LAUNDRY
 ROOM.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-01 Cont ID  
Sent By jroach Date 2010-03-01 Time 15:12 Rev Time 0.00
Received By jroach Date 2010-03-01 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-23 Cont ID  
Sent By mcruz Date 2009-04-23 Time 14:15 Rev Time 0.00
Received By mcruz Date 2009-04-23 Time 13:38 Sent To E
Notes
2009-04-23 14:15:15PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. CLEARLY INDICATE ON THE SITE PLAN THE LOCATION OF
 THE LAUNDRY ROOM.
  
 4. INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION. PURSUANT TO THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-305(B): OVERHANGS SHALL NOT PROJECT MORE THAN THREE
 (3) FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  