Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 15:32 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 15:32 Sent To PC
Notes
2009-05-15 15:32:34REVISED PAGES 2 AND 5.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-04-29 Cont ID  
Sent By rregueir Date 2009-04-29 Time 13:24 Rev Time 0.00
Received By rregueir Date 2009-04-29 Time 13:24 Sent To PC
Notes
2009-04-29 13:25:06REVISION WITHDRAWN BY CONTRACTOR. PLANS TO BE
 RESUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-27 Cont ID  
Sent By rregueir Date 2009-04-27 Time 14:44 Rev Time 0.00
Received By rregueir Date 2009-04-27 Time 14:43 Sent To  
Notes
2009-04-27 14:44:26REVISED PAGES 1 AND 2. ALL PROVISO ITEMS HAVE BEEN
 ADDRESSED WITH THIS REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-04-17 Cont ID  
Sent By rregueir Date 2009-04-17 Time 15:12 Rev Time 0.00
Received By rregueir Date 2009-04-16 Time 11:12 Sent To FIRE
Notes
2009-04-17 15:12:05REVIEW #: 1ST
 ACTION: PASSED W/ PROVISO
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 **PROVISO**
  
 1. PROVIDE MANUFACTURER'S SUBMITTAL DATA FOR EXHAUST
 AND SUPPLY FANS SHOWING THEY ARE DESIGNED FOR WIND
 RESISTANCE. MECHANICAL APPLIANCES AND THAT ARE EXPOSED
 TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH FBC-M 301.12.
  
 2. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR. THE ACTIVATION OF THE EXHAUST
 FAN SHALL OCCUR THROUGH AN INTERLOCK WITH THE COOKING
 APPLIANCES, BY MEANS OF HEAT SENSORS OR BY MEANS OF
 OTHER APPROVED METHODS IN ACCORDANCE WITH FBC-M
 507.REVISE PLANS PRIOR TO INSPECTION SHOWING HOW THE
 EXHAUST SYSTEM WILL BE CONTROLLED FOR THIS REQUIREMENT
 IN ACCORDANCE WITH FBC-M 506.2.1.1.
  
 NOTE: REVISE PLANS FOR REVIEW TO SHOW COMPLIANCE WITH
 THESE REQUIREMENTS PRIOR TO INSPECTION.