Plan Review Details - Permit 09040226
Plan Review Stops For Permit 09040226
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-04-14 Cont ID  
Sent By jnguyen Date 2009-04-14 Time 09:04 Rev Time 0.00
Received By jnguyen Date 2009-04-14 Time 08:26 Sent To  
Notes
2009-04-14 08:44:24I HAVE COMPLETED MY ADDRESSING REVIEW FOR PERMIT#
 09040226. THIS WAS ONE OF THOSE SPECIAL CASE-SCENARIO
 PERMITS (I.E., CITY OF WPB, BELLSOUTH, FPL, NPBCID,
 PALM TRAN, ADELPHIA, ETC.) THAT DEALT WITH PROVIDING
 ELECTRICAL POWER TO AN AT&T DIGITAL TELEPHONE CABINET.
 THEREFORE IN COMMUNITYPLUS, PLEASE MOVE & ATTACH THIS
 PERMIT RECORD TO THE AT&T PCN# 74434321090010031 -
 SEQUENTIAL UNIT RECORD 0015 @ 4300 SPRUCE AVE (RECALL
 THAT THE @ SYMBOL MEANS ROUGHLY AT OR AN AROUND THE
 BALLPARK LOCATION FOR THESE SPECIAL CIRCUMSTANCES). I
 HAVE ALREADY ADJUSTED THE ADDRESS TO @ 4300 SPRUCE AVE
 & PCN# 74434321090010031 ON THE ORIGINAL PERMIT
 APPLICATION & PLACED IT BACK ON AISHA'S DESK.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-14 Cont ID  
Sent By btrobaug Date 2009-04-14 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2009-04-14 Time 13:21 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By dpalmer Date 2009-04-13 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2009-04-13 Time 14:33 Sent To AD
Notes
2009-04-13 14:33:41** DENIED**
  
  
 1) NOTE: TEMPORARY FAILED AS THIS IS NOT PERMITTED TO
 BE ASSIGNED TO AN INDIVIDUAL'S HOME ADDRESS. PLANS
 ROUTED TO ADDRESSING.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  