| Plan Review Stops For Permit 09040215 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2009-07-28 |
|
|
Cont ID |
|
| Sent By |
jnguyen |
Date |
2009-07-28 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
jnguyen |
Date |
2009-07-27 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2009-07-28 11:34:16 | TODAY, I DROVE OUT ON LOCATION TO CONDUCT A FIELD | | | INSPECTION & VERIFY ALL OF THE ADDRESSES FOR THE THREE | | | STRUCTURES ASSOCIATED WITH PCN# 74434316150060010 | | | (SOUTHEAST PARCEL BOUNDARY - PRIMARY ADDRESS OF 505 | | | 20TH ST& SECONDARY ONE OF 517 20TH ST, NORTHEAST PARCEL | | | BOUNDARY - 518 21ST ST, AND WEST PARCEL BOUNDARY - 550 | | | 21ST ST). I CONFIRMED THAT THE STRUCTURE ON THE | | | SOUTHEAST PARCEL BOUNDARY OF PCN# 74434316150060010 | | | SOLELY HAD THE ADDRESS OF 517 20TH ST ON IT (NOT 505 | | | 20TH ST TOO). THROUGH FURTHER RESEARCH & ANALYSIS, I | | | REALIZED THAT CLOSED PERMIT# 07060953 WAS FOR A | | | DEMOLITION OF A STRUCTURE THAT ONCE REFERENCED 505 20TH | | | ST (ON WHAT IS TODAY KNOWN AS PCN# 74434316240000220 | | | BECAUSE BACK THEN IT WAS A PART OF PCN# | | | 74434316150060010). THEREFORE, I RETIRED THE PRIMARY | | | ADDRESS OF 505 20TH ST & SUBSEQUENTLY MADE 517 20TH ST | | | (STRUCTURE ON THE SE PARCEL BOUNDARY) AS THE NEW | | | PRIMARY ONE. 518 21ST ST (NE PARCEL BOUNDARY) & 550 | | | 21ST ST (WEST PARCEL BOUNDARY) WILL REMAIN AS SECONDARY | | | ADDRESSES. I CONTACTED KAY BRAND OF PAPA TO INFORM HER | | | THAT THE FORMER PRIMARY ADDRESS OF 505 20TH WAS RETIRED | | | & THAT THEIR WEB SITE SHOULD REFLECT THE NEW ONE OF 517 | | | 20TH ST. IN COMMUNITYPLUS, I CHANGED THE MAIN LOCATION | | | RECORD FROM 505 TO 517 20TH ST & REARRANGED ALL OF THE | | | ASSOCIATED RECORDS TO THEIR REFERENCED LOCATIONS. IN | | | GIS, THE 505 20TH ST WAS DESIGNATED AS KEYCODE=3 | | | (MEANING MISCELLANEOUS, UNOFFICIAL OR A RETIRED | | | ADDRESS) & 517 20TH ST CONVERTED TO KEYCODE=1 (MEANING | | | PRIMARY ADDRESS). ALL OF THE DOCUMENTS WERE RETURNED | | | BACK INTO THE R17 BOX. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-11-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-11-10 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-11-10 |
Time |
11:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-09-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-09-16 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-09-16 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2009-09-21 09:01:29 | PLANS OK, BUT NEED TO APPLY FOR PERMIT TO PASS BUILDING | | | STOP. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-07-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-07-29 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-07-29 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2009-07-30 09:24:50 | BUILDING REVIEW SECOND CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- CLASSIFICATION OF WORK IS NOT ALTERATION-LEVEL 1 AS | | | STATED ON SHEET A0.1. KITCHEN LAYOUT (ALL UNITS) AND | | | BATHROOMS LAYOUTS (AT FIRST FLOOR) WERE CHANGED. SEE | | | DEMOLITION PLANS AND DEMOLITIONS NOTES #8 AND #13. | | | CLASSIFICATION OF WORK IS ALTERATION-LEVEL 2. SEE SEC. | | | 404 OF 2007 FLORIDA BUILDING CODE-EXISTING BUILDING. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-04-16 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-04-16 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2009-04-16 16:27:11 | RESIDENTIAL (R2) REMODELING, BUILDING REVIEW CHECKLIST. | | | REVIEW UNDER 2007 FLORIDA BUILDING CODE. | | | | | | 1- DESIGNER OF RECORD TO SPECIFY TYPE OF ALTERATION AS | | | REQUIRED BY SEC. 401.4 OF 2007 EXISTING BUILDING CODE. | | | NOTE: ACCORDING TO PROPOSED SCOPE OF WORK THIS IS | | | ALTERATION TYPE 3. | | | | | | 2- IF THERE IS ANY FEDERAL MONEY INVOLVED IN THE | | | RENOVATION OF THIS BUILDINGS, THEN COMPLIANCE WITH | | | SECTION 504 OF THE REHABILITATION ACT (1973) NEED TO BE | | | ACCOMPLISHED. | | | | | | 3- ALL DRAWINGS NEED TO BE UPDATED. CURRENT CODE IS THE | | | 2007 FBC, NOT 2004. UPDATE ALL INFORMATION THAT IS | | | REFERRING TO THE 2004 FBC. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-11-17 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-11-17 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2009-09-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-20 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-20 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2009-09-20 10:25:36 | ** DENIED ** | | | | | | PLANS WERE REVIEWED FOR PREVIOUS COMMENTS MADE BY | | | PREVIOUS REVIEWER. HOWEVER THE FOLLOWING ITEMS ARE | | | NOTED AS SOME ITEMS WHICH WERE NOT PART OF PREVIOUS | | | REVIEW NOTES. SOME ARE LIFE SAFETY RELATED AND SOME ARE | | | NOT. | | | PERMIT APPLICATION HAS NOT BEEN MADE. A PROVISO COULD | | | HAVE POSSIBLY ISSUED ONLY IF PERMIT APPLICATION HAD | | | BEEN MADE. SEE COMMENST BELOW, AS PERMIT APPLICATION IS | | | CRITICAL TO MANY ITEMS FOR CODE COMPLIANCE. | | | ** SOME OF THE BELOW ITEMS ARE LIFE SAFETY AS WELL AS | | | LIFE SAFETY DEPENDING ON WHEN PERMIT APPLICATION IS | | | MADE. | | | | | | | | | | | | 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED | | | CONTRACTOR. AS OF OCTOBER 1ST, 2009 THE 2008 NEC/ | | | NFPA-70 WILL GO INTO AFFECT. THIS WILL SUBSTANTIALLY | | | CHANGE MANY ITEMS SHOWN ON PLANS INCLUDING ITEMS UNDER | | | THE NEW CODE WHICH WILL BE CONSIDERED LIFE SAFETY BY | | | NFPA. | | | | | | 2) NOTE: | | | | | | 3) NOTE: PLANS INDICATE SMOKE ALARMS, HOWEVER SYMBOL | | | LEGEND INDICATES SMOKE DETECTORS. WHICH ONE WILL BE | | | INSTALLED? IF THESE ARE IN FACT SMOKE DETECTORS THIS | | | WILL AFFECT DESIGN AND INFORMATION ON PLANS FOR FA | | | PANEL, DEVICES, HORNS, STROBE ETC. | | | IF SMOKE ALARMS THEN PLEASE ADJUST SYMBOL LEGEND. | | | | | | 4) NOTE: HOUSE PANEL INDICATES A TIME CLOCK FOR | | | EXTERIOR LIGHTING CONTROLS. PLEASE SEE 13-415.AB.1.4. | | | ALL EXTERIOR LIGHTING SHALL BE EITHER OF THE TWO | | | METHODS IN SECTION. A STANDARD TIME CLOCK IS NOT | | | ACCEPTABLE. | | | | | | 5) NOTE: ** NOTED: RISER INDICATES FOOTER STEEL TO BE | | | PART OF THE GROUNDING ELECTRODE SYSTEM. THIS IS AN | | | EXISTING BUILDING; IF THIS ATTACHMENT DOES NOT EXIST IT | | | WOULD NOT BE REQUIRED TO ACCESS STEEL OF EXISTING | | | FOOTING. THIS WOULD ACTUALLY AFFECT THE STRUCTURAL | | | INTEGRITY OF THE EXISTING FOOTERS. IF SHOWN ON RISER | | | THEN IT WILL BE REQUIRED. 250.50 | | | | | | ** ONCE AGAIN PERMIT APPLICATION HAS NOT BEEN MADE. | | | 2008 NEC WILL CHANGE MANY ITEMS. | | | | | | | | | ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT | | | INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS | | | REQUIRED. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-07-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-07-17 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-07-17 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2009-07-17 11:55:58 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE | | | TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH | | | 700.12(F)(4), 2005 NEC.*** THE CIRCUITS THAT IS NOW | | | BEING USED FOR THE EMERGENCY LIGHTS ARE NOT FROM THE | | | HOUSE PANEL IN VIOLATION 210.25 COMMON AREA BRANCH | | | CIRCUITS | | | BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY | | | LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED | | | ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED | | | FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL, | | | COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON | | | AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT | | | BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL | | | DWELLING UNIT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | . |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-04-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-04-16 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-04-16 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2009-04-16 09:43:17 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. | | | | | | 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN | | | THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE | | | INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS | | | DESIGNED. | | | | | | 3} NOTE: THE ROOM LABELS ON THE SECOND FLOOR SHEET | | | E1.0.1 ARE MARKED WITH 1ST AND 2ND FLOOR NUMBERS, | | | PLEASE CORRECT ON PERMIT SET.106.1.1 FBC AS AMENDED. | | | | | | 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE | | | TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH | | | 700.12(F)(4), 2005 NEC. | | | | | | 5} PROVIDE MECHANICAL PLANS AND UNIT SPECIFICATIONS FOR | | | A/C EQUIPMENT SO THAT LOADS AND CIRCUIT SIZING CAN BE | | | REVIEWED ON THE SCHEDULES AND CALCULATIONS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2009-11-18 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-11-18 |
Time |
18:00 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-11-18 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2009-11-18 18:00:38 | *****APPROVED***** | | | | | | PLAN SHEETS A2.0.1, A2.0.2, E1.0.1, AND E2.0.2 WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2009-09-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-09-23 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-09-23 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2009-09-23 13:14:24 | *****PROVISO***** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN: | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN | | | SATISFIED. | | | | | | 3. AN APPLICATION FOR PERMIT IS ON FILE | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-14 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-14 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2009-08-14 19:17:34 | *****UNSAT***** | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN: | | | | | | 1. THIS COMMENT FROM THE PREVIOUS REVIEW HAS BEEN | | | ADDRESSED. "THE PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET." | | | | | | 2. (THIS IS A NEW COMMENT) PROVIDE A 2A:10BC RATED FIRE | | | EXTINGUISHER WHICH SATISFIES THE 75' TRAVEL DISTANCE. | | | THIS REQUIREMENT MAY BE ACCOMPLISHED BY EITHER | | | INSTALLING FIRE EXTINGUISHER(S) IN THE COMMON AREA OF | | | THE BUILDING ACCESSIBLE TO ALL FOUR DWELLING UNITS OR | | | INSTALLING A FIRE EXTINGUISHER IN EACH DWELLING UNIT. | | | | | | 3. THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN | | | SATISFIED. | | | | | | 4. AN APPLICATION FOR PERMIT IS ON FILE. | | | | | | 5. NO OTHER ADDITIONS, DELETIONS, OR CHANGES (OTHER | | | THAN THOSE AS A RESULT OF THE PLAN EXAMINERS' COMMENTS) | | | ARE MADE TO TO THIS EXISTING PLAN. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-04-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-24 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-24 |
Time |
11:28 |
Sent To |
|
|
| Notes |
| 2009-04-24 11:45:02 | *****DENIED***** | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION | | | AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE | | | REFERENCED. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIAL IN TERMS OF | | | CLASS A, CLASS B, OR CLASS C FOR THE NEW WALL AND | | | CEILING. | | | | | | 5. ON SHEETS E1.0.1 AND E2.0.1, THE USE OF SMOKE | | | DETECTORS ARE INDICATED. AMEND VERBAGE TO REFLECT THAT | | | THE DEVICES ARE SMOKE ALARMS. PLEASE BE ADVISED THAT | | | SMOKE DETECTORS ARE TIED INTO A FIRE ALARM SYSTEM, | | | WHEREAS SMOKE ALARMS ALERT THE OCCUPANT(S) OF THE | | | DWELLING UNIT AND IS NOT TIED INTO A FIRE ALARM SYSTEM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2009-11-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-02 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-02 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2009-09-02 16:05:51 | SEPARATE GAS PERMIT REQUIRED. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-05 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-05 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2009-08-05 15:57:29 | DENIED | | | REFERENCE: | | | FBC-2007 FUEL GAS | | | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARATE GAS PERMIT: | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT THE PIPE LENGTH IS NOT | | | INDICATED ON THE SECTIONS OF PIPE FROM THE METER DOWN | | | TO THE HORIZONTAL PIPING, FROM THE HORIZONTAL PIPING TO | | | THE WATER HEATERS, FROM THE HORIZONTAL TO THE RISER UP | | | TO THE SECOND FLOOR AND FROM THE SECOND FLOOR RISER | | | OVER TO THE SECOND FLOOR RANGE IS NOT SHOWN. | | | | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2005 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT NUMBER | | | 1 IS ADDRESSED. | | | | | | 6. N/A | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2. | | | IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | ****RESPONSE NOTED, BUT IF THE PRESSURE DELIVERED IS 2 | | | PSI THEN REGULATORS WILL BE REQUIRED AT EACH APPLIANCE | | | WITH THE SHUT OFF VALVE INSTALLED IMMEDIATELY AHEAD OF | | | EACH REGULATOR. SECTIONS 409.4 & 410.1. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2007 FUEL GAS CODE | | | SECS. 502 THRU 505 & G2426 THRU G2429. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE | | | WATER HEATERS. THERE ARE TWO WINDOWS IN CLOSE PROXIMITY | | | OF THE WATER HEATERS. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2. | | | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. | | | | | | 10. N/A | | | 11. N/A | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-28 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-28 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2009-04-28 11:04:44 | DENIED | | | REFERENCE: | | | FBC-2007 FUEL GAS | | | | | | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE | | | SEPARATE GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 | | | FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2007 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1/G2412.8 THRU G2413.6.1 AND TABLES 402.4(1) | | | THRU | | | 402.4(33)/ G2413.4(1) THRU G2413.4(8). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2005 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2007 FUEL | | | GAS CODE SECTION 304 & G2407. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2. | | | IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2007 FUEL GAS CODE | | | SECS. 502 THRU 505 & G2426 THRU G2429. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-08-31 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-08-31 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-08-31 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2009-11-16 09:51:33 | B 22 **NEEDS FIRE** | | | CONTRACTOR SUBMITTED APPLICATION | | | | | 2009-08-31 16:28:26 | B-7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-15 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-15 |
Time |
14:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-05-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-04-28 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-04-09 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2009-04-09 16:50:52 | TO "R7" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2009-09-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-09-08 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-09-08 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2009-09-08 16:59:02 | NO PERMIT APPLIED FOR AT THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2009-08-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-04 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-04 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2009-08-04 11:05:17 | PREVIOUS COMMENTS ADDRESSED. REVIEW WILL REMAIN IN FAIL | | | STATUS PENDING APPLICATION FOR PERMIT AS THIS WAS A | | | MAJOR WORKING DRAWEING REVIEW WITHOUT A PERMIT | | | APPLICATION. | | | IF A/C WORK IS TO BE PERFORMED UNDER SEPARATE PERMIT, | | | THE A/C WORK WILL NEED TO BE COMPLETED PRIOR TO | | | BUILDING FINAL TO SHOW COMPLIANCE WITH FBC-B 1204.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-04-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-22 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-22 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2009-04-22 09:50:29 | REVIEW #: 1ST **PLAN CHECK ONLY** | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | | | | 1. PROVIDE EQUIPMENT SCHEDULE FOR PROPOSED NEW BATHROOM | | | EXHAUST FANS. MECHANICAL PERMIT REQUIRED FOR THIS SCOPE | | | OF WORK. | | | | | | 2. UPDATE PLANS TO REFLECT COMPLIANCE WITH FBC 2007 | | | WITH 2009 SUPPLEMENT. THIS CODE IS IN EFFECT AS OF | | | MARCH 1, 2009. | | | | | | NOTE: ELECTRICAL PLANS INDICATE POWER BEING PROVIDED | | | FOR "FUTURE" SPLIT A/C SYSTEMS. SEPARATE PLANS, | | | EQUIPMENT SCHEDULE AND COOLING LOAD CALCULATIONS WILL | | | BE REQUIRED FOR THIS SCOPE OF WORK IF BEING DONE AT A | | | LATER DATE. COOLING LOAD CALCULATIONS SHALL BE IN | | | ACCORDANCE WITH FBC-B 13-607.AB.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-11-17 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-11-17 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2009-09-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-02 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-31 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2009-09-02 16:06:55 | PLANS ARE CODE COMPLIANT BUT PLUMBING REVIEW WILL | | | REMAIN IN FAILED STATUS UNTILL PERMIT APPLIED FOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-05 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-05 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2009-08-05 15:40:44 | PLUMBING CODE COMPLIANT BUT WILL REMAIN IN FAILED | | | STATUS UNTIL PERMIT APPLIED FOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-04-28 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-04-27 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2009-04-28 10:29:01 | DENIED | | | REFERENCE: | | | FBC-2007 W/2009 SUPPLEMENTS | | | FBC-2007 CHAPTER 1 | | | FBC-2007 EXISTING BUILDING | | | FBC-2007 RESIDENTIAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. PLEASE INDICATE THE CORRECT CODE CYCLE ON EACH | | | SHEET. THE FBC-2007 CODE WITH 2009 SUPPLEMENTS ARE THE | | | DESIGN CODE FOR ALL APPLICATIONS SUBMITTED ON OR AFTER | | | MARCH 1, 2009. SECTION 106.1.1. | | | | | | 2. PLEASE INDICATE THE LEVEL OF ALTERATION ON THE | | | PLANS. SECTION 404.4. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-11-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-11-16 |
Time |
16:12 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-11-16 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2009-11-16 16:23:16 | PASS | | | | | | 1) THE PERMIT VALUE FOR THE RENOVATION EXCEEDS 50% OF | | | THE VALUE OF THE STRUCTURE, THEREFORE THE LANDSCAPE | | | SHALL BE BROUGHT INTO CONFORMITY WITH THE CURRENT CITY | | | LANDSCAPE REGULATIONS. PAPA VALUES THE BUILDING AT | | | APPROXIMATELY $110,000 AND THE SUBMITTED APPRAISAL | | | VALUES A COMPARABLE BUILDING AT APPROXIMATELY $150,000 | | | - THIS PERMIT VALUE IS $85,000. ADDITIONALLY, PERMIT | | | NO. 09020657 HAS A VALUE OF $27,818. TOTAL PERMITS | | | WITHIN THE LAST 12 MONTHS EXCEED 50% OF THE STRUCTURE | | | VALUE. | | | | | | 2) THE SUBMISSION OF A LANDSCAPE PERMIT IS REQUIRED. | | | NOTE: ALL LANDSCAPE SHALL BE INSTALLED AND BE APPROVED | | | PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY | | | FOR THE BUILDING. | | | | | | 3) A SEPARATE IRRIGATION PERMIT IS REQUIRED. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-09-03 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-09-03 |
Time |
17:04 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2009-09-03 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2009-09-03 17:15:23 | PLAN REVIEW FAIL | | | | | | NO ZONING ISSUES, BUT PLEASE REMEMBER THAT IF THE | | | PERMIT VALUE FOR THE RENOVATION, INCLUDING THE INTERIOR | | | DEMOLITION, OF ANY STRUCTURE EXCEEDS 50% OF THE VALUE | | | OF THE STRUCTURE, THEN THE LANDSCAPE SHALL BE BROUGHT | | | INTO CONFORMITY WITH THE CURRENT CITY LANDSCAPE | | | REGULATIONS. WHILE THERE WAS NO UPDATED INFORMATION | | | PROVIDED WITH THE RESUBMITTAL, AN EARLIER CONVERSATION | | | WITH THE ARCHITECT AND THE HOUSING AUTHORITY INDICATES | | | THAT THE WORK WILL NOT EXCEED THE 50% THRESHOLD. THE | | | PERMIT VALUATION AND BUILDING VALUE WILL BE VERIFIED | | | ONCE THE ACTUAL BUILDING PERMIT IS SUBMITTED. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2009-07-27 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-07-27 |
Time |
11:05 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-07-27 |
Time |
11:05 |
Sent To |
|
|
| Notes |
| 2009-07-27 11:59:25 | FAILED 2ND PLAN REVIEW | | | | | | 1) PLEASE NOTE THAT 517 20TH STREET ALSO HAS AN ADDRESS | | | OF 505 20TH STREET. THE PERMIT IS BEING ROUTED TO | | | ADDRESSING IN ORDER TO DETERMINE WHICH ADDRESS SHALL BE | | | USED FOR THE ACTUAL BUILDING PERMIT APPLICATION (NOT | | | THE PLAN REVIEW) FOR THIS BUILDING. | | | | | | 2) REPEAT COMMENT - IF THE PERMIT VALUE FOR THE | | | RENOVATION, INCLUDING THE INTERIOR DEMOLITION, OF ANY | | | STRUCTURE EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, | | | THEN THE LANDSCAPE SHALL BE BROUGHT INTO CONFORMITY | | | WITH THE CURRENT CITY LANDSCAPE REGULATIONS. THE | | | RESPONSE TO THE INITIAL PLAN REVIEW STATES THAT EACH | | | BUILDING WILL BE RENOVATED FOR $80, 000 AND LISTS THE | | | VALUE OF EACH STRUCTURE AT $400,000. THIS VALUE | | | CONFLICTS WITH THE PALM BEACH COUNTY PROPERTY | | | APPRAISER'S WEBSITE, WHICH LISTS THE IMPROVEMENT VALUE | | | (THE STRUCTURE) FOR 604 21ST STREET AS $82,259 AND 517 | | | 20TH STREET $358,398 FOR MULTIPLE BUILDINGS LISTED | | | UNDER THE SAME PARCEL CONTROL NUMBER. AT THE TIME OF | | | THE BUILDING PERMIT APPLICATION, PLEASE PROVIDE EITHER | | | A CERTIFIED APPRAISAL FOR EACH BUILDING SHOWING A VALUE | | | IN EXCEEDING 2 TIMES THE VALUE OF THE BUILDING PERMIT, | | | OR A LANDSCAPE PLAN VERIFYING CONFORMITY WITH HE CITY'S | | | LANDSCAPE REGULATIONS. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-04-28 |
Time |
16:40 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2009-04-28 |
Time |
16:40 |
Sent To |
M |
|
| Notes |
| 2009-04-28 16:53:37 | FAILED PLAN REVIEW | | | | | | 1) THE PARCEL CONTROL NUMBER, THE ADDRESS AND THE | | | LOCATION PLAN SHALL ALL CORRECTED BASED ON THE SPECIFIC | | | BUILDING THAT IS BEING RENOVATED. | | | | | | 2) PLEASE NOTE THAT IF THE PERMIT VALUE FOR THE | | | RENOVATION, INCLUDING THE INTERIOR DEMOLITION, OF ANY | | | STRUCTURE EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, | | | THEN THE LANDSCAPE SHALL BE BROUGHT INTO CONFORMITY | | | WITH THE CURRENT CITY LANDSCAPE REGULATIONS. A | | | LANDSCAPE PLAN VERIFYING CONFORMITY IS REQUIRED. | | | | | | CONTACT ERIC SCHNEIDER (561) 822-1435. |
|
|