Plan Review Details - Permit 09040215
Plan Review Stops For Permit 09040215
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-07-28 Cont ID  
Sent By jnguyen Date 2009-07-28 Time 11:50 Rev Time 0.00
Received By jnguyen Date 2009-07-27 Time 16:01 Sent To  
Notes
2009-07-28 11:34:16TODAY, I DROVE OUT ON LOCATION TO CONDUCT A FIELD
 INSPECTION & VERIFY ALL OF THE ADDRESSES FOR THE THREE
 STRUCTURES ASSOCIATED WITH PCN# 74434316150060010
 (SOUTHEAST PARCEL BOUNDARY - PRIMARY ADDRESS OF 505
 20TH ST& SECONDARY ONE OF 517 20TH ST, NORTHEAST PARCEL
 BOUNDARY - 518 21ST ST, AND WEST PARCEL BOUNDARY - 550
 21ST ST). I CONFIRMED THAT THE STRUCTURE ON THE
 SOUTHEAST PARCEL BOUNDARY OF PCN# 74434316150060010
 SOLELY HAD THE ADDRESS OF 517 20TH ST ON IT (NOT 505
 20TH ST TOO). THROUGH FURTHER RESEARCH & ANALYSIS, I
 REALIZED THAT CLOSED PERMIT# 07060953 WAS FOR A
 DEMOLITION OF A STRUCTURE THAT ONCE REFERENCED 505 20TH
 ST (ON WHAT IS TODAY KNOWN AS PCN# 74434316240000220
 BECAUSE BACK THEN IT WAS A PART OF PCN#
 74434316150060010). THEREFORE, I RETIRED THE PRIMARY
 ADDRESS OF 505 20TH ST & SUBSEQUENTLY MADE 517 20TH ST
 (STRUCTURE ON THE SE PARCEL BOUNDARY) AS THE NEW
 PRIMARY ONE. 518 21ST ST (NE PARCEL BOUNDARY) & 550
 21ST ST (WEST PARCEL BOUNDARY) WILL REMAIN AS SECONDARY
 ADDRESSES. I CONTACTED KAY BRAND OF PAPA TO INFORM HER
 THAT THE FORMER PRIMARY ADDRESS OF 505 20TH WAS RETIRED
 & THAT THEIR WEB SITE SHOULD REFLECT THE NEW ONE OF 517
 20TH ST. IN COMMUNITYPLUS, I CHANGED THE MAIN LOCATION
 RECORD FROM 505 TO 517 20TH ST & REARRANGED ALL OF THE
 ASSOCIATED RECORDS TO THEIR REFERENCED LOCATIONS. IN
 GIS, THE 505 20TH ST WAS DESIGNATED AS KEYCODE=3
 (MEANING MISCELLANEOUS, UNOFFICIAL OR A RETIRED
 ADDRESS) & 517 20TH ST CONVERTED TO KEYCODE=1 (MEANING
 PRIMARY ADDRESS). ALL OF THE DOCUMENTS WERE RETURNED
 BACK INTO THE R17 BOX.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-11-10 Cont ID  
Sent By jgomez Date 2009-11-10 Time 13:06 Rev Time 0.00
Received By jgomez Date 2009-11-10 Time 11:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-09-21 Cont ID  
Sent By jgomez Date 2009-09-16 Time 16:50 Rev Time 0.00
Received By jgomez Date 2009-09-16 Time 16:12 Sent To  
Notes
2009-09-21 09:01:29PLANS OK, BUT NEED TO APPLY FOR PERMIT TO PASS BUILDING
 STOP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-07-30 Cont ID  
Sent By jgomez Date 2009-07-29 Time 16:27 Rev Time 0.00
Received By jgomez Date 2009-07-29 Time 16:27 Sent To  
Notes
2009-07-30 09:24:50BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- CLASSIFICATION OF WORK IS NOT ALTERATION-LEVEL 1 AS
 STATED ON SHEET A0.1. KITCHEN LAYOUT (ALL UNITS) AND
 BATHROOMS LAYOUTS (AT FIRST FLOOR) WERE CHANGED. SEE
 DEMOLITION PLANS AND DEMOLITIONS NOTES #8 AND #13.
 CLASSIFICATION OF WORK IS ALTERATION-LEVEL 2. SEE SEC.
 404 OF 2007 FLORIDA BUILDING CODE-EXISTING BUILDING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-16 Cont ID  
Sent By jgomez Date 2009-04-16 Time 16:05 Rev Time 0.00
Received By jgomez Date 2009-04-16 Time 16:05 Sent To  
Notes
2009-04-16 16:27:11RESIDENTIAL (R2) REMODELING, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA BUILDING CODE.
  
 1- DESIGNER OF RECORD TO SPECIFY TYPE OF ALTERATION AS
 REQUIRED BY SEC. 401.4 OF 2007 EXISTING BUILDING CODE.
 NOTE: ACCORDING TO PROPOSED SCOPE OF WORK THIS IS
 ALTERATION TYPE 3.
  
 2- IF THERE IS ANY FEDERAL MONEY INVOLVED IN THE
 RENOVATION OF THIS BUILDINGS, THEN COMPLIANCE WITH
 SECTION 504 OF THE REHABILITATION ACT (1973) NEED TO BE
 ACCOMPLISHED.
  
 3- ALL DRAWINGS NEED TO BE UPDATED. CURRENT CODE IS THE
 2007 FBC, NOT 2004. UPDATE ALL INFORMATION THAT IS
 REFERRING TO THE 2004 FBC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-11-17 Cont ID  
Sent By btrobaug Date 2009-11-17 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2009-11-17 Time 07:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-20 Cont ID  
Sent By dpalmer Date 2009-09-20 Time 10:25 Rev Time 0.00
Received By dpalmer Date 2009-09-20 Time 10:25 Sent To  
Notes
2009-09-20 10:25:36** DENIED **
  
 PLANS WERE REVIEWED FOR PREVIOUS COMMENTS MADE BY
 PREVIOUS REVIEWER. HOWEVER THE FOLLOWING ITEMS ARE
 NOTED AS SOME ITEMS WHICH WERE NOT PART OF PREVIOUS
 REVIEW NOTES. SOME ARE LIFE SAFETY RELATED AND SOME ARE
 NOT.
 PERMIT APPLICATION HAS NOT BEEN MADE. A PROVISO COULD
 HAVE POSSIBLY ISSUED ONLY IF PERMIT APPLICATION HAD
 BEEN MADE. SEE COMMENST BELOW, AS PERMIT APPLICATION IS
 CRITICAL TO MANY ITEMS FOR CODE COMPLIANCE.
 ** SOME OF THE BELOW ITEMS ARE LIFE SAFETY AS WELL AS
 LIFE SAFETY DEPENDING ON WHEN PERMIT APPLICATION IS
 MADE.
  
  
  
 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED
 CONTRACTOR. AS OF OCTOBER 1ST, 2009 THE 2008 NEC/
 NFPA-70 WILL GO INTO AFFECT. THIS WILL SUBSTANTIALLY
 CHANGE MANY ITEMS SHOWN ON PLANS INCLUDING ITEMS UNDER
 THE NEW CODE WHICH WILL BE CONSIDERED LIFE SAFETY BY
 NFPA.
  
 2) NOTE:
  
 3) NOTE: PLANS INDICATE SMOKE ALARMS, HOWEVER SYMBOL
 LEGEND INDICATES SMOKE DETECTORS. WHICH ONE WILL BE
 INSTALLED? IF THESE ARE IN FACT SMOKE DETECTORS THIS
 WILL AFFECT DESIGN AND INFORMATION ON PLANS FOR FA
 PANEL, DEVICES, HORNS, STROBE ETC.
 IF SMOKE ALARMS THEN PLEASE ADJUST SYMBOL LEGEND.
  
 4) NOTE: HOUSE PANEL INDICATES A TIME CLOCK FOR
 EXTERIOR LIGHTING CONTROLS. PLEASE SEE 13-415.AB.1.4.
 ALL EXTERIOR LIGHTING SHALL BE EITHER OF THE TWO
 METHODS IN SECTION. A STANDARD TIME CLOCK IS NOT
 ACCEPTABLE.
  
 5) NOTE: ** NOTED: RISER INDICATES FOOTER STEEL TO BE
 PART OF THE GROUNDING ELECTRODE SYSTEM. THIS IS AN
 EXISTING BUILDING; IF THIS ATTACHMENT DOES NOT EXIST IT
 WOULD NOT BE REQUIRED TO ACCESS STEEL OF EXISTING
 FOOTING. THIS WOULD ACTUALLY AFFECT THE STRUCTURAL
 INTEGRITY OF THE EXISTING FOOTERS. IF SHOWN ON RISER
 THEN IT WILL BE REQUIRED. 250.50
  
 ** ONCE AGAIN PERMIT APPLICATION HAS NOT BEEN MADE.
 2008 NEC WILL CHANGE MANY ITEMS.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-17 Cont ID  
Sent By btrobaug Date 2009-07-17 Time 12:34 Rev Time 0.00
Received By btrobaug Date 2009-07-17 Time 11:40 Sent To  
Notes
2009-07-17 11:55:58 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE
 TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH
 700.12(F)(4), 2005 NEC.*** THE CIRCUITS THAT IS NOW
 BEING USED FOR THE EMERGENCY LIGHTS ARE NOT FROM THE
 HOUSE PANEL IN VIOLATION 210.25 COMMON AREA BRANCH
 CIRCUITS
 BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY
 LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED
 ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED
 FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL,
 COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON
 AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT
 BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL
 DWELLING UNIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
 .

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-16 Cont ID  
Sent By btrobaug Date 2009-04-16 Time 09:50 Rev Time 0.00
Received By btrobaug Date 2009-04-16 Time 08:39 Sent To  
Notes
2009-04-16 09:43:17 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 2} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 3} NOTE: THE ROOM LABELS ON THE SECOND FLOOR SHEET
 E1.0.1 ARE MARKED WITH 1ST AND 2ND FLOOR NUMBERS,
 PLEASE CORRECT ON PERMIT SET.106.1.1 FBC AS AMENDED.
  
 4} NOTE: THE EMERGENCY LIGHTS MUST NOT BE WIRED TO THE
 TIME CLOCK (IE: HP 1&2) BUT MUST COMPLY WITH
 700.12(F)(4), 2005 NEC.
  
 5} PROVIDE MECHANICAL PLANS AND UNIT SPECIFICATIONS FOR
 A/C EQUIPMENT SO THAT LOADS AND CIRCUIT SIZING CAN BE
 REVIEWED ON THE SCHEDULES AND CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2009-11-18 Cont ID  
Sent By mawillia Date 2009-11-18 Time 18:00 Rev Time 0.00
Received By mawillia Date 2009-11-18 Time 17:41 Sent To  
Notes
2009-11-18 18:00:38*****APPROVED*****
  
 PLAN SHEETS A2.0.1, A2.0.2, E1.0.1, AND E2.0.2 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2009-09-23 Cont ID  
Sent By mawillia Date 2009-09-23 Time 13:24 Rev Time 0.00
Received By mawillia Date 2009-09-23 Time 13:05 Sent To  
Notes
2009-09-23 13:14:24*****PROVISO*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN:
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN
 SATISFIED.
  
 3. AN APPLICATION FOR PERMIT IS ON FILE
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-08-14 Cont ID  
Sent By mawillia Date 2009-08-14 Time 18:05 Rev Time 0.00
Received By mawillia Date 2009-08-14 Time 16:24 Sent To  
Notes
2009-08-14 19:17:34*****UNSAT*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN:
  
 1. THIS COMMENT FROM THE PREVIOUS REVIEW HAS BEEN
 ADDRESSED. "THE PROJECT SITE ADDRESS SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET."
  
 2. (THIS IS A NEW COMMENT) PROVIDE A 2A:10BC RATED FIRE
 EXTINGUISHER WHICH SATISFIES THE 75' TRAVEL DISTANCE.
 THIS REQUIREMENT MAY BE ACCOMPLISHED BY EITHER
 INSTALLING FIRE EXTINGUISHER(S) IN THE COMMON AREA OF
 THE BUILDING ACCESSIBLE TO ALL FOUR DWELLING UNITS OR
 INSTALLING A FIRE EXTINGUISHER IN EACH DWELLING UNIT.
  
 3. THE OTHER PLAN EXAMINERS' COMMENTS HAVE BEEN
 SATISFIED.
  
 4. AN APPLICATION FOR PERMIT IS ON FILE.
  
 5. NO OTHER ADDITIONS, DELETIONS, OR CHANGES (OTHER
 THAN THOSE AS A RESULT OF THE PLAN EXAMINERS' COMMENTS)
 ARE MADE TO TO THIS EXISTING PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-24 Cont ID  
Sent By mawillia Date 2009-04-24 Time 12:31 Rev Time 0.00
Received By mawillia Date 2009-04-24 Time 11:28 Sent To  
Notes
2009-04-24 11:45:02*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101 - LIFE SAFETY CODE - 2006 EDITION
 AND NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION) SHALL BE
 REFERENCED.
  
 4. SPECIFY THE INTERIOR FINISH MATERIAL IN TERMS OF
 CLASS A, CLASS B, OR CLASS C FOR THE NEW WALL AND
 CEILING.
  
 5. ON SHEETS E1.0.1 AND E2.0.1, THE USE OF SMOKE
 DETECTORS ARE INDICATED. AMEND VERBAGE TO REFLECT THAT
 THE DEVICES ARE SMOKE ALARMS. PLEASE BE ADVISED THAT
 SMOKE DETECTORS ARE TIED INTO A FIRE ALARM SYSTEM,
 WHEREAS SMOKE ALARMS ALERT THE OCCUPANT(S) OF THE
 DWELLING UNIT AND IS NOT TIED INTO A FIRE ALARM SYSTEM.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-11-19 Cont ID  
Sent By kstevens Date 2009-09-02 Time 16:04 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 16:04 Sent To  
Notes
2009-09-02 16:05:51SEPARATE GAS PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 15:40 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 15:40 Sent To  
Notes
2009-08-05 15:57:29DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 ****FROM PREVIOUS REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE PIPE LENGTH IS NOT
 INDICATED ON THE SECTIONS OF PIPE FROM THE METER DOWN
 TO THE HORIZONTAL PIPING, FROM THE HORIZONTAL PIPING TO
 THE WATER HEATERS, FROM THE HORIZONTAL TO THE RISER UP
 TO THE SECOND FLOOR AND FROM THE SECOND FLOOR RISER
 OVER TO THE SECOND FLOOR RANGE IS NOT SHOWN.
  
 2. OK
 3. OK
 4. OK
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2005 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT NUMBER
 1 IS ADDRESSED.
  
 6. N/A
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2.
 IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT IF THE PRESSURE DELIVERED IS 2
 PSI THEN REGULATORS WILL BE REQUIRED AT EACH APPLIANCE
 WITH THE SHUT OFF VALVE INSTALLED IMMEDIATELY AHEAD OF
 EACH REGULATOR. SECTIONS 409.4 & 410.1.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & G2426 THRU G2429.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED FOR THE
 WATER HEATERS. THERE ARE TWO WINDOWS IN CLOSE PROXIMITY
 OF THE WATER HEATERS.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 10. N/A
 11. N/A
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-28 Cont ID  
Sent By kstevens Date 2009-04-28 Time 10:50 Rev Time 0.00
Received By kstevens Date 2009-04-28 Time 10:50 Sent To  
Notes
2009-04-28 11:04:44DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE
 SEPARATE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1/G2412.8 THRU G2413.6.1 AND TABLES 402.4(1)
 THRU
 402.4(33)/ G2413.4(1) THRU G2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2005 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & G2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2 & G2413.2.
 IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & G2426 THRU G2429.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & G2413.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-08-31 Cont ID  
Sent By lmartine Date 2009-08-31 Time 16:16 Rev Time 0.00
Received By shill Date 2009-08-31 Time 16:16 Sent To  
Notes
2009-11-16 09:51:33B 22 **NEEDS FIRE**
 CONTRACTOR SUBMITTED APPLICATION
  
2009-08-31 16:28:26B-7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-15 Cont ID  
Sent By shill Date 2009-07-15 Time 14:38 Rev Time 0.00
Received By shill Date 2009-07-15 Time 14:38 Sent To  
Notes
2009-07-15 14:39:08R17
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-05 Cont ID  
Sent By jgomez Date 2009-04-28 Time 15:31 Rev Time 0.00
Received By jgomez Date 2009-04-09 Time 16:50 Sent To  
Notes
2009-04-09 16:50:52TO "R7"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2009-09-08 Cont ID  
Sent By rregueir Date 2009-09-08 Time 16:58 Rev Time 0.00
Received By rregueir Date 2009-09-08 Time 16:52 Sent To  
Notes
2009-09-08 16:59:02NO PERMIT APPLIED FOR AT THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 11:05 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 11:02 Sent To  
Notes
2009-08-04 11:05:17PREVIOUS COMMENTS ADDRESSED. REVIEW WILL REMAIN IN FAIL
 STATUS PENDING APPLICATION FOR PERMIT AS THIS WAS A
 MAJOR WORKING DRAWEING REVIEW WITHOUT A PERMIT
 APPLICATION.
 IF A/C WORK IS TO BE PERFORMED UNDER SEPARATE PERMIT,
 THE A/C WORK WILL NEED TO BE COMPLETED PRIOR TO
 BUILDING FINAL TO SHOW COMPLIANCE WITH FBC-B 1204.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-22 Cont ID  
Sent By rregueir Date 2009-04-22 Time 09:50 Rev Time 0.00
Received By rregueir Date 2009-04-22 Time 08:56 Sent To  
Notes
2009-04-22 09:50:29REVIEW #: 1ST **PLAN CHECK ONLY**
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
  
 1. PROVIDE EQUIPMENT SCHEDULE FOR PROPOSED NEW BATHROOM
 EXHAUST FANS. MECHANICAL PERMIT REQUIRED FOR THIS SCOPE
 OF WORK.
  
 2. UPDATE PLANS TO REFLECT COMPLIANCE WITH FBC 2007
 WITH 2009 SUPPLEMENT. THIS CODE IS IN EFFECT AS OF
 MARCH 1, 2009.
  
 NOTE: ELECTRICAL PLANS INDICATE POWER BEING PROVIDED
 FOR "FUTURE" SPLIT A/C SYSTEMS. SEPARATE PLANS,
 EQUIPMENT SCHEDULE AND COOLING LOAD CALCULATIONS WILL
 BE REQUIRED FOR THIS SCOPE OF WORK IF BEING DONE AT A
 LATER DATE. COOLING LOAD CALCULATIONS SHALL BE IN
 ACCORDANCE WITH FBC-B 13-607.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2009-11-17 Cont ID  
Sent By kstevens Date 2009-11-17 Time 14:57 Rev Time 0.00
Received By kstevens Date 2009-11-17 Time 14:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 16:06 Rev Time 0.00
Received By kstevens Date 2009-08-31 Time 16:52 Sent To  
Notes
2009-09-02 16:06:55PLANS ARE CODE COMPLIANT BUT PLUMBING REVIEW WILL
 REMAIN IN FAILED STATUS UNTILL PERMIT APPLIED FOR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-08-05 Cont ID  
Sent By kstevens Date 2009-08-05 Time 15:39 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 15:39 Sent To  
Notes
2009-08-05 15:40:44PLUMBING CODE COMPLIANT BUT WILL REMAIN IN FAILED
 STATUS UNTIL PERMIT APPLIED FOR.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-28 Cont ID  
Sent By kstevens Date 2009-04-28 Time 10:09 Rev Time 0.00
Received By kstevens Date 2009-04-27 Time 16:54 Sent To  
Notes
2009-04-28 10:29:01DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 CHAPTER 1
 FBC-2007 EXISTING BUILDING
 FBC-2007 RESIDENTIAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLEASE INDICATE THE CORRECT CODE CYCLE ON EACH
 SHEET. THE FBC-2007 CODE WITH 2009 SUPPLEMENTS ARE THE
 DESIGN CODE FOR ALL APPLICATIONS SUBMITTED ON OR AFTER
 MARCH 1, 2009. SECTION 106.1.1.
  
 2. PLEASE INDICATE THE LEVEL OF ALTERATION ON THE
 PLANS. SECTION 404.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2009-11-18 Cont ID  
Sent By eschneid Date 2009-11-16 Time 16:12 Rev Time 0.50
Received By eschneid Date 2009-11-16 Time 16:12 Sent To  
Notes
2009-11-16 16:23:16PASS
  
 1) THE PERMIT VALUE FOR THE RENOVATION EXCEEDS 50% OF
 THE VALUE OF THE STRUCTURE, THEREFORE THE LANDSCAPE
 SHALL BE BROUGHT INTO CONFORMITY WITH THE CURRENT CITY
 LANDSCAPE REGULATIONS. PAPA VALUES THE BUILDING AT
 APPROXIMATELY $110,000 AND THE SUBMITTED APPRAISAL
 VALUES A COMPARABLE BUILDING AT APPROXIMATELY $150,000
 - THIS PERMIT VALUE IS $85,000. ADDITIONALLY, PERMIT
 NO. 09020657 HAS A VALUE OF $27,818. TOTAL PERMITS
 WITHIN THE LAST 12 MONTHS EXCEED 50% OF THE STRUCTURE
 VALUE.
  
 2) THE SUBMISSION OF A LANDSCAPE PERMIT IS REQUIRED.
 NOTE: ALL LANDSCAPE SHALL BE INSTALLED AND BE APPROVED
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY
 FOR THE BUILDING.
  
 3) A SEPARATE IRRIGATION PERMIT IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 3 Status F Date 2009-09-03 Cont ID  
Sent By eschneid Date 2009-09-03 Time 17:04 Rev Time 0.25
Received By eschneid Date 2009-09-03 Time 17:04 Sent To  
Notes
2009-09-03 17:15:23PLAN REVIEW FAIL
  
 NO ZONING ISSUES, BUT PLEASE REMEMBER THAT IF THE
 PERMIT VALUE FOR THE RENOVATION, INCLUDING THE INTERIOR
 DEMOLITION, OF ANY STRUCTURE EXCEEDS 50% OF THE VALUE
 OF THE STRUCTURE, THEN THE LANDSCAPE SHALL BE BROUGHT
 INTO CONFORMITY WITH THE CURRENT CITY LANDSCAPE
 REGULATIONS. WHILE THERE WAS NO UPDATED INFORMATION
 PROVIDED WITH THE RESUBMITTAL, AN EARLIER CONVERSATION
 WITH THE ARCHITECT AND THE HOUSING AUTHORITY INDICATES
 THAT THE WORK WILL NOT EXCEED THE 50% THRESHOLD. THE
 PERMIT VALUATION AND BUILDING VALUE WILL BE VERIFIED
 ONCE THE ACTUAL BUILDING PERMIT IS SUBMITTED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2009-07-27 Cont ID  
Sent By eschneid Date 2009-07-27 Time 11:05 Rev Time 0.50
Received By eschneid Date 2009-07-27 Time 11:05 Sent To  
Notes
2009-07-27 11:59:25FAILED 2ND PLAN REVIEW
  
 1) PLEASE NOTE THAT 517 20TH STREET ALSO HAS AN ADDRESS
 OF 505 20TH STREET. THE PERMIT IS BEING ROUTED TO
 ADDRESSING IN ORDER TO DETERMINE WHICH ADDRESS SHALL BE
 USED FOR THE ACTUAL BUILDING PERMIT APPLICATION (NOT
 THE PLAN REVIEW) FOR THIS BUILDING.
  
 2) REPEAT COMMENT - IF THE PERMIT VALUE FOR THE
 RENOVATION, INCLUDING THE INTERIOR DEMOLITION, OF ANY
 STRUCTURE EXCEEDS 50% OF THE VALUE OF THE STRUCTURE,
 THEN THE LANDSCAPE SHALL BE BROUGHT INTO CONFORMITY
 WITH THE CURRENT CITY LANDSCAPE REGULATIONS. THE
 RESPONSE TO THE INITIAL PLAN REVIEW STATES THAT EACH
 BUILDING WILL BE RENOVATED FOR $80, 000 AND LISTS THE
 VALUE OF EACH STRUCTURE AT $400,000. THIS VALUE
 CONFLICTS WITH THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S WEBSITE, WHICH LISTS THE IMPROVEMENT VALUE
 (THE STRUCTURE) FOR 604 21ST STREET AS $82,259 AND 517
 20TH STREET $358,398 FOR MULTIPLE BUILDINGS LISTED
 UNDER THE SAME PARCEL CONTROL NUMBER. AT THE TIME OF
 THE BUILDING PERMIT APPLICATION, PLEASE PROVIDE EITHER
 A CERTIFIED APPRAISAL FOR EACH BUILDING SHOWING A VALUE
 IN EXCEEDING 2 TIMES THE VALUE OF THE BUILDING PERMIT,
 OR A LANDSCAPE PLAN VERIFYING CONFORMITY WITH HE CITY'S
 LANDSCAPE REGULATIONS.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-28 Cont ID  
Sent By eschneid Date 2009-04-28 Time 16:40 Rev Time 0.50
Received By eschneid Date 2009-04-28 Time 16:40 Sent To M
Notes
2009-04-28 16:53:37FAILED PLAN REVIEW
  
 1) THE PARCEL CONTROL NUMBER, THE ADDRESS AND THE
 LOCATION PLAN SHALL ALL CORRECTED BASED ON THE SPECIFIC
 BUILDING THAT IS BEING RENOVATED.
  
 2) PLEASE NOTE THAT IF THE PERMIT VALUE FOR THE
 RENOVATION, INCLUDING THE INTERIOR DEMOLITION, OF ANY
 STRUCTURE EXCEEDS 50% OF THE VALUE OF THE STRUCTURE,
 THEN THE LANDSCAPE SHALL BE BROUGHT INTO CONFORMITY
 WITH THE CURRENT CITY LANDSCAPE REGULATIONS. A
 LANDSCAPE PLAN VERIFYING CONFORMITY IS REQUIRED.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.