Plan Review Details - Permit 09040197
Plan Review Stops For Permit 09040197
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-08 Cont ID  
Sent By jwitmer Date 2009-05-08 Time 14:48 Rev Time 0.66
Received By jwitmer Date 2009-05-08 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-10 Cont ID  
Sent By jwitmer Date 2009-04-10 Time 09:19 Rev Time 2.22
Received By jwitmer Date 2009-04-10 Time 09:19 Sent To  
Notes
2009-04-10 09:56:04BUILDING PLAN REVIEW
 PERMIT: 09040197
 ADD: 2461 METROCENTRE BLVD EAST
 CONT: ADVANCED HOOD SYSTEMS, LLC
 TEL: (561)732-2508
  
 FL BLD CODE= 2007FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS. 2007 FLORIDA
 EXISTING BUILDING CODE 401.5 A DESIGN PROFESSIONAL OR
 AN OWNER MUST ELECT ONE OR COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTION 403,404 AND 405 OF THIS
 CODE.
  
 2) PLANS DO NOT PROVIDE ANY WIND DESIGN INFORMATION:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2A. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B). WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C). WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2E). COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLEASE PROVIDE DOCUMENTATION THAT THE 301.12 WIND
 RESISTANCE.2007 FBC MECHANICAL.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. THIS MAY BE ACCOMPLISHED BY
 DESIGN OR BY APPLICATION OF SECTION 301.13.1.
 ROOF-MOUNTED MECHANICAL UNITS AND SUPPORTS SHALL BE
 SECURED TO THE STRUCTURE. THE USE OF WOOD SLEEPERS
 SHALL NOT BE PERMITTED. PLEASE PROVIDE PRODUCT TESTING
 REPORTS INDICATING COMPLIANCE WITH WIND PRESSURES.
  
 4) SHEET 1 OF 3 INDICATES A SECTION FOR FLASHING DETAIL
 SEE DETAIL D-7, THERE ARE ONLY 3 SHEETS, 106.1.2
 PROVIDE ADDTIONAL INFORMATION, ADMINISTRATIVE CODE, &
 1507.3.9 CLAY AND CONCRETE TILE ROOFING, AT THE
 JUNCTURE OF THE ROOF VERTICAL SURFACES, FLASHING AND
 COUNTERFLASHING SHALL BE PROVIDED IN ACCORDANCE WITH
 THE MANUFACTURER???S INSTALLATION INSTRUCTIONS OR THE
 RECOMMENDATIONS OF THE FRSA/TRI 07320 MANUAL.
  
 5) PLEASE PROVIDE THE HEIGTH AT WHICH THE EXHAUST FAN
 WILL BE LOCATED, MAY OR MAY NOT BE APPLICABLE. 1509.6
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES??? LEVEL SERVICE SPACE.
 SUCH ACCESS SHALL NOT REQUIRE CLIMBING OVER
 OBSTRUCTIONS GREATER THAN 30 INCHES (762 MM) HIGH OR
 WALKING ON ROOFS HAVING A SLOPE GREATER THAN 4 UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS (488.2 KG/M2) PER SQUARE FOOT.
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
 CATWALKS INSTALLED TO PROVIDE THE REQUIRED ACCESS SHALL
 BE NOT LESS THAN 24 INCHES (610 MM) WIDE AND SHALL HAVE
 RAILINGS AS REQUIRED FOR SERVICE PLATFORMS.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2009-04-15 Cont ID  
Sent By dpalmer Date 2009-04-15 Time 08:30 Rev Time 0.00
Received By dpalmer Date 2009-04-15 Time 08:30 Sent To  
Notes
2009-04-15 08:30:58** NOTED**
  
  
  
 1) NOTE: SEPARATE PERMIT AND PLANS REQUIRED FOR
 ELECTRICAL HOOD SYSTEM CONTROLS, SEPARATE FEEDS AND
 CONNECTIONS.
 NO ELECTRICAL PER NEC 2005, NO PERMIT APPLIED FOR.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-05-26 Cont ID  
Sent By btrobaug Date 2009-05-26 Time 10:17 Rev Time 0.00
Received By btrobaug Date 2009-05-26 Time 10:16 Sent To M
Notes
2009-05-26 10:17:31TO RON'S DESK./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2009-05-01 Time   Rev Time 0.00
Received By lmartine Date 2009-05-01 Time 16:49 Sent To  
Notes
2009-05-01 16:50:31GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-22 Cont ID  
Sent By rregueir Date 2009-04-22 Time 13:04 Rev Time 0.00
Received By rregueir Date 2009-04-09 Time 13:15 Sent To PC
Notes
2009-04-09 13:15:35TO "C21"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-06-01 Cont ID  
Sent By rregueir Date 2009-06-01 Time 13:36 Rev Time 0.00
Received By rregueir Date 2009-06-01 Time 13:14 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-05-15 Cont ID  
Sent By rregueir Date 2009-05-15 Time 15:17 Rev Time 0.00
Received By rregueir Date 2009-05-15 Time 15:11 Sent To PC
Notes
2009-05-15 15:17:54REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. NOT ADDRESSED. NO MANUFACTURER'S DATA WAS PROVIDED
 REGARDING THE WIND RESISTANCE CAPABILITIES OF THE
 EXHAUST FAN OR CURB. SHOW COMPLIANCE WIHT FBC-M 301.12.
  
 3. NOT ADDRESSED. FAN STILL APPEARS TO BE LESS THAN 10
 FEET FROM THE ROOF EDGE. GUARDS ARE REQUIRED AT THIS
 LOCATION IN ACCORDANCE WITH FBC-M 304.10.
  
 4. NOT ADDRESSED. FIRE WRAP IS SHOWN ON THE DUCT, BUT
 THE CLEARANCE REQUIREMENTS ALSO APPLY TO THE HOOD. SHOW
 COMPLIANCE WITH FBC-M 506.3.1.2.
  
 5. NOT ADDRESSED.NO INFORMATION IS PROVIDED REGARDING
 THE SCOPE OF WORK RELATED TO PROVISIONS FOR MAKEUP AIR.
 SHOW HOW MAKEUP AIR IS TO BE PROVIDED AS PART OF THE
 SCOPE OF THIS PERMIT OR PROVIDE SEPARATE PERMIT
 APPLICATION. SHOW COMPLIANCE WITH FBC-M 308.1.
  
 6. OK
  
 7. PARTIALLY ADDRESSED, PLAN DOES NOT INDICATE WHAT
 TYPE OF WALL FINISH IS TO BE USED ADJACENT TO THE HOOD.
 PLEASE CLARIFY AND SHOW COMPLIANCE WITH FBC-M 507.9.
  
 8. NOT ADDRESSED. PLEASE CONFIRM VALUATION AS STATED ON
 PERMIT APPLICATION. INCLUDE ALL RELATED WORK. SEE
 PREVIOUS COMMENT. FBC-B 108.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-22 Cont ID  
Sent By rregueir Date 2009-04-22 Time 13:04 Rev Time 0.00
Received By rregueir Date 2009-04-22 Time 10:51 Sent To I
Notes
2009-04-22 13:04:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE UPDATE PLANS TO REFERENCE THE CORRECT CODE
 EDITION. THE 2007 FLORIDA BUILDING CODE WITH 2009
 SUPPLEMENT IS IN EFFECT AS OF MARCH 1, 2009. ALSO, TWO
 OF THE REFERENCED CODE SECTIONS ON SHEET 1 COULD NOT BE
 FOUND IN THE CODE AND DO NOT APPEAR TO EXIST. PLEASE
 REFERENCE CORRECT CODE SECTIONS.
  
 2. PROVIDE MANUFACTURER'S DATA SHOWING THE EXHAUST FAN
 IS DESIGNED FOR WIND RESISTANCE. MECHANICAL APPLIANCES
 AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND PRESSURES AS
 DETERMINED IN ACCORDANCE WITH FBC-M 301.12.
  
 3. BASED ON THE SIDE VIEW ON SHEET 1, THE EXHAUST FAN
 APPEARS TO BE LESS THAN 10 FEET FROM THE ROOF EDGE.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES SUCH AS FANS
 OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE LOCATED
 WITHIN 10 FEET OF THE ROOF EDGE IN ACCORDANCE WITH
 FBC-M 304.10. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES BEYOND EACH END OF SUCH APPLIANCES AND THE TOP
 OF THE GUARD SHALL BE LOCATED NOT LESS THAN 42 INCHES
 ABOVE THE ELEVATED SURFACE ADJACENT TO THE GUARD. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO COMPLY WITH THE
 REQUIREMENTS FOR GUARDS SPECIFIED IN THE FLORIDA
 BUILDING CODE, BUILDING.
  
 4. BASED ON THE SIDE VIEW ON SHEET 1, THERE IS AN A/C
 SUPPLY DUCT IN CLOSE PROXIMITY TO THE NEW HOOD. DUCTS
 AND INSULATION INSTALLED WITHIN 18 INCHES OF A TYPE I
 HOOD SHALL BE NONCOMBUSTIBLE OR SHALL BE LISTED FOR THE
 APPLICATION IN ACORDANCE WITH FBC-M 506.3.1.2.
  
 5. NOTE ON SHEET 1 INDICATES THAT MAKEUP AIR IS TO BE
 PROVIDED BY A/C CONTRACTOR. THERE IS NO SCOPE OF WORK
 RELATED TO THIS WORK ASSOCIATED WITH THIS PERMIT. THE
 SUPPLY OF MAKEUP AIR IS AN INTEGRAL PART OF THE
 CMMERCIAL KITCHEN VENTILATION SYSTEM AND MUST BE DONE
 IN CONJUNCTION WITH THE INSTALLATION OF THE COMERCIAL
 KITCHEN EXHAUST SYSTEM IN ORDER TO PROVIDE A CODE
 COMPLIANT DESIGN IN ACCORDANCE WITH FBC-M 508.1. PLEASE
 EXPAND THE SCOPE OF THIS PERMIT TO INCLUDE MAKEUP AIR
 PROVISIONS OR PROVIDE SEPARATE PLANS AND PERMIT
 APPLICATION FOR THAT SCOPE OF WORK PRIOR TO ISSUANCE OF
 THIS PERMIT.
  
 6. TYPE I HOOD SYSTEMS SHALL BE DESIGNED AND INSTALLED
 TO AUTOMATICALLY ACTIVATE THE EXHAUST FAN WHENEVER
 COOKING OPERATIONS OCCUR IN ACCORDANCE WITH FBC-M
 507.2.1.1. THE ACTIVATION OF THE EXHAUST FAN SHALL
 OCCUR THROUGH AN INTERLOCK WITH THE COOKING APPLIANCES,
 BY MEANS OF HEAT SENSORS OR BY MEANS OF OTHER APPROVED
 METHODS. SHOW HOW AUTOMATIC OPERATION OF THE EXHAUST
 SYSTEM WILL BE ACHIEVED.
  
 7. SHEET 1 INDICATES A GYPSUM WALLBOARD FINISH ON THE
 WALL ADJACENT TO THE PROPOSED HOOD. CLEARANCE SHALL NOT
 BE REQUIRED FROM GYPSUM WALLBOARD PROVIDED THAT A
 SMOOTH, CLEANABLE, NONABSORBENT AND NONCOMBUSTIBLE
 MATERIAL IS INSTALLED BETWEEN THE HOOD AND THE GYPSUM
 WALLBOARD OVER AN AREA EXTENDING NOT LESS THAN 18
 INCHES IN ALL DIRECTIONS FROM THE HOOD IN ACCORDANCE
 WITH THE EXCEPTION UNDER FBC-M 507.9.
  
 8. PLEASE CONFIRM VALUATION AS STATED ON PERMIT
 APPLICATION. THE STATED VALUE ON PERMIT APPLICATION IS
 TO INCLUDE ALL LABOR, MATERIAL AND DESIGN COSTS
 ASSOCIATED WITH THE PROPOSED SCOPE OF WORK AT FAIR
 MARKET VALUE, INCLUDING THE PROPOSED ROOFING WORK IN
 ACCORDANCE WITH FBC-B 108.3.
  
 NOTE: SEPARATE ELECTRICAL PERMIT IS REQUIRED FOR POWER
 SUPPLIED TO THIS KITCHEN EXHAUST AND SUPPRESSION
 SYSTEM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]