Plan Review Details - Permit 09040174
Plan Review Stops For Permit 09040174
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 07:50 Rev Time 1.00
Received By jwitmer Date 2009-08-04 Time 07:02 Sent To  
Notes
2009-08-04 07:44:33BUILDING PLAN REVIEW
 PERMIT: 09040174
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTH EAST CERTIFIED CONTRACTORS
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 4 /09
 BUILDING PROVISO
 SHOP DRAWING TO BE REVIEWED BY DESIGN PROFESSIONAL
 BEFORE THE SUBMITTAL TO CITY FOR REVIEW BEFORE
 INSPECTION.
 NFPA 110: 8.4 OPERATIONAL INSPECTION AND TESTING.
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 1) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN 20 PEOPLE SHALL BE PERMITTED TO
 HAVE A MINIMUM CLEAR WIDTH OF 22 INCHES (559 MM),
 MINIMUM TREAD DEPTH OF 10 INCHES (254 MM), MAXIMUM
 RISER HEIGHT OF 9 INCHES (229 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 2) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 3) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2.AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE OF
 ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3.IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 4) BEFORE A CERTIFICATE OF COMPLETION CAN BE ISSUED
 PLEASE PROVIDE EVIDENCE THAT THE TOP OF THE GENERATOR
 SLAB IS AT OR ABOVE ELEVATION 13.5' NGVD, FLOOD ZONE
 A-9
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-07-27 Cont ID  
Sent By jwitmer Date 2009-07-27 Time 17:30 Rev Time 1.10
Received By jwitmer Date 2009-07-27 Time 12:30 Sent To  
Notes
2009-07-27 17:39:37BUILDING PLAN REVIEW
 PERMIT: 09040174
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTH EAST CERTIFIED CONTRACTORS
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 27/09
 3RD REVIEW
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) THE PLAN DOES NOT NDICATE IF THIS IS A NEW SLAB OR
 REUSE OF AN EXISTING SLAB. 2702.1.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.PLANS DO NOT INDICATE THE GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC BUILDING 1609.1.3
  
 5) COMMENT NUMBER 5 DEALS WWITH THE REASON A STAIR AND
 ACCESS PLATFORM IS REQUIRED. FOR MAINTENANCE AND WEEKLY
 VISUAL INSPECTION OF GENERATOR A ELEVATED PLATFORM,
 STAIR AND GUARDRAIL SYSTEM WILL BE REQUIRED. NFPA 110:
 8.4 OPERATIONAL INSPECTION AND TESTING. 8.4.1* EPSSS,
 INCLUDING ALL APPURTENANT COMPONENTS, SHALL BE
 INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT LEAST
 MONTHLY. DEPENDING ON TTHE HEIGHT OF THE FUEL TANK.
  
 6)PLEASE PROVIDE CODE COMPLIANCE. STAIRS 1009.3
 EXCEPTION# 7. INDUSTRIAL EQUIPMENT ACCESS STAIRS AND
 LANDINGS THAT SERVE AS A COMPONENT OF THE MEANS OF
 EGRESS FROM THE INVOLVED EQUIPMENT AND DO NOT SERVE
 MORE THAN 20 PEOPLE SHALL BE PERMITTED TO HAVE A
 MINIMUM CLEAR WIDTH OF 22 INCHES (559 MM), MINIMUM
 TREAD DEPTH OF 10 INCHES (254 MM), MAXIMUM RISER HEIGHT
 OF 9 INCHES (229 MM), MINIMUM HEADROOM OF 6 FEET 8
 INCHES (2032 MM), AND A MAXIMUM HEIGHT BETWEEN LANDINGS
 OF 12 FEET (36 576 MM).
  
 7) PLEASE PROVIDE CODE COMPLIANCE. GAURDRAILS: 1012.1
 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8)PLEASE GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 9) THE FLOOR PLAN DOES NOT INDICATE THIS GENERATOR
 BEING LOCATED IN A SEPERATE GENERATOR ROOM.
 NFPA 110 .7.2.1.2
 NFPA 110. 7.2.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-07-15 Cont ID  
Sent By jwitmer Date 2009-07-15 Time 15:39 Rev Time 0.55
Received By jwitmer Date 2009-07-15 Time 15:00 Sent To  
Notes
2009-07-15 15:45:02BUILDING PLAN REVIEW
 PERMIT: 09040174
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTH EAST CERTIFIED CONTRACTORS
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JUNE 15/09
 2ND REVIEW
 ACTION: DENIED
  
 NONE OF THE COMMENTS WERE ADDRESSED FROMTHE FIRST
 REVIEW!!!
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1C) THE LOCATION OF THIS PROJECT IS LOCATED WITHIN A
 A-9 FLOOD-ZONE REQUIRING A MINIMUM ELEVATION OF THE
 SLAB OF 13.5'.
  
 1D) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) IT APPEARS THE INSTALATION OF THIS GENERATOR AND
 TANK ARE ON THE EXTERIOR OF THE BUILDING AND EXPOSED TO
 WIND. PLEASE PROVIDE THE WIND DESIGN CRITERIA. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2A). BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B). WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C) . WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3) THE PLAN DO NOT NDICATE IF THIS IS A NEW SLAB OR
 REUSE OF AN EXISTING SLAB. 2702.1 INSTALLATION.
  
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING. PLANS INDICATE 1200 GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC
 BUILDING 1609.1.3.
  
 5) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 6) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 7) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-09 Cont ID  
Sent By jwitmer Date 2009-04-09 Time 17:33 Rev Time 1.00
Received By jwitmer Date 2009-04-09 Time 17:33 Sent To  
Notes
2009-04-09 17:39:24BUILDING PLAN REVIEW
 PERMIT: 09040174
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTH EAST CERTIFIED CONTRACTORS
 TEL: (561)635-6935
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 15/09
 2ND REVIEW
 ACTION: DENIED
  
 1A) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH THE 2009 SUPPLEMENTS.
  
 1C) THE LOCATION OF THIS PROJECT IS LOCATED WITHIN A
 A-9 FLOOD-ZONE REQUIRING A MINIMUM ELEVATION OF THE
 SLAB OF 13.5'.
  
 1D) (2007 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 2) IT APPEARS THE INSTALATION OF THIS GENERATOR AND
 TANK ARE ON THE EXTERIOR OF THE BUILDING AND EXPOSED TO
 WIND. PLEASE PROVIDE THE WIND DESIGN CRITERIA. 1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2A). BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2B). WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2C) . WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2D). THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3) THE PLAN DO NOT NDICATE IF THIS IS A NEW SLAB OR
 REUSE OF AN EXISTING SLAB. 2702.1 INSTALLATION.
  
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE NFPA 70, NATIONAL ELECTRICAL
 CODE, NFPA 110 AND NFPA 111.
 NFPA 110:
 3A) 7.4 MOUNTING.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE
 UNIT DURING OPERATION. PLANS DO NOT PROVIDE INFORMATION
 FOR SECONDARY CONTAINMENT. NFPA 110: 7.9.12 LISTED
 GENERATOR SUBBASE SECONDARY CONTAINMENT FUEL TANKS OF
 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING. PLANS INDICATE 1200 GALLON CAPACITY.
  
 4) PLANS FAIL TO PROVIDE INFORMATION FOR THE FOUNDATION
 AND SLAB FOR GENERATOR A TANK, PLEASE PROVIDE DETAILS
 FOR ANCHORING OF TANK AND GENERATOR AGAINST OVERTURNING
 ,UPLIFT AND SLIPPAGE FBC
 BUILDING 1609.1.3.
  
 5) FOR MAINTENANCE AND WEEKLY VISUAL INSPECTION OF
 GENERATOR A ELEVATED PLATFORM, STAIR AND GUARDRAIL
 SYSTEM WILL BE REQUIRED. NFPA 110: 8.4 OPERATIONAL
 INSPECTION AND TESTING.
  
 8.4.1* EPSSS, INCLUDING ALL APPURTENANT COMPONENTS,
 SHALL BE INSPECTED WEEKLY AND EXERCISED UNDER LOAD AT
 LEAST MONTHLY.
  
 6) STAIRS 1009.3 EXCEPTION# 7. INDUSTRIAL EQUIPMENT
 ACCESS STAIRS AND LANDINGS THAT SERVE AS A COMPONENT OF
 THE MEANS OF EGRESS FROM THE INVOLVED EQUIPMENT AND DO
 NOT SERVE MORE THAN
 20 PEOPLE SHALL BE PERMITTED TO HAVE A MINIMUM CLEAR
 WIDTH OF 22 INCHES (559 MM), MINIMUM TREAD DEPTH OF 10
 INCHES (254 MM), MAXIMUM RISER HEIGHT OF 9 INCHES (229
 MM), MINIMUM
 HEADROOM OF 6 FEET 8 INCHES (2032 MM), AND A MAXIMUM
 HEIGHT BETWEEN LANDINGS OF 12 FEET (36 576 MM).
  
 7) GAURDRAILS: 1012.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INDUSTRIAL EQUIPMENT PLATFORMS, LANDINGS
 WHICH ARE LOCATED MORE THAN 30 INCHES (762 MM) ABOVE
 THE FLOOR OR GRADE BELOW.
 GUARDS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7.
  
 8) GUARD 1012.3 OPENING LIMITATIONS. EXCEPTIONS:
 2. AT ELEVATED WALKING SURFACES FOR ACCESS TO AND USE
 OF ELECTRICAL, MECHANICAL OR PLUMBING SYSTEMS OR
 EQUIPMENT, GUARDS SHALL HAVE BALUSTERS OR BE OF SOLID
 MATERIALS SUCH THAT A
 SPHERE WITH A DIAMETER OF 21 INCHES (533 MM) CANNOT
 PASS THROUGH ANY OPENING.
 3. IN AREAS WHICH ARE NOT OPEN TO THE PUBLIC WITHIN
 OCCUPANCIES IN GROUP I-3, F, H OR S, BALUSTERS,
 HORIZONTAL INTERMEDIATE RAILS OR OTHER CONSTRUCTION
 SHALL NOT PERMIT A SPHERE WITH A
 DIAMETER OF 21 INCHES (533 MM) TO PASS THROUGH ANY
 OPENING.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2009-08-06 Cont ID  
Sent By btrobaug Date 2009-08-06 Time 11:27 Rev Time 0.00
Received By btrobaug Date 2009-08-06 Time 07:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 18:35 Sent To  
Notes
2009-07-24 18:40:58 
 ** DENIED **
  
 1) NOTE: PLEASE SUBMIT MANUFACTURES SPECS FOR ONE
 PRODUCT FOR ATS. THERE IS SUBMITTALS FOR CATERPILLAR
 EQUIPMENT AND ALSO LAKE SHORE. WHICH ONE WILL BE USED?
 110.3,90.7
  
 2) NOTE: THE SUBMITTED SP-1 AND RP-1 SHEETS ARE NOT
 SIGNED DATED OR SEALED BY THE RESPONSIBLE DESIGNER OF
 RECORD. SEE COMMENTS FROM OTHER TRADES
 FS 481.221
  
 3) NOTE: THE SUBMITTED LP-1 THROUGH LP-4 CONTAINED
 RAISED SEALS OVER PHOTO-COPIED SIGNATURES. THIS DOES
 NOT MEET THE MINIMUM UNDER FLORIDA STATUTES 481.221.
 ALL COPIES IN BOTH SETS SHALL BE RETAINED BY THIS
 OFFICE.
  
 4) NOTE: PLANS SUBMITTED DO NOT CONTAIN ANY STRUCTURAL
 DETAILS FOR SLAB. SEE COMMENTS FROM BUILDING REVIEW
 WITH RESPECT TO NO INFORMATION FOR SLAB, STAIRS AND
 PLATFORM.
  
 5) NOTE: RISER INDICATES GROUND FAULT PROTECTION ON THE
 800AMP BREAKER ON GENERATOR?? PLEASE HAVE ENGINEER CALL
 TO GO OVER THIS AS HAVING *GROUND FAULT PROTECTION*
 WILL CREATE A LACK OF COORDINATION FOR GENERATOR BACK
 UP. THIS IS NOT THE SAME AS GROUND FAULT SENSING AND
 THE COORDINATION OF POWER TRANSFER BACK TO NORMAL
 POWER.
  
  
  
 ** EMAIL WAS SENT TO OFFICE OF ENGINEER TO CALL AND GO
 OVER PLANS SPECIFIC TO COMMENT #4.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-22 Cont ID  
Sent By btrobaug Date 2009-07-22 Time 19:38 Rev Time 0.00
Received By btrobaug Date 2009-07-22 Time 18:21 Sent To  
Notes
2009-07-22 19:39:31 
  
 TO DOUG./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 16:11 Sent To  
Notes
2009-07-05 16:11:11 
  
  
  
  
  
 ** DENIED 2ND PLANS REVIEW **
  
 1) NOTE: THIS COMMENT WAS IGNORED: PERMIT APPLICATION
 VALUE SHALL INCLUDE: ALL LABOR, MATERIALS, EQUIPMENT,
 DESIGN COST ETC. AN APPLIED VALUE OF $12K DOES NOT
 COVER THE GENERATOR LET ALONE THE TRANSFER EQUIPMENT,
 SLAB WORK, ELECTRICAL, UNDERGROUND OR FUEL TANK.
 IF AN APPROPRIATE VALUE IS NOT STATED FOR COMPLETE
 SCOPE ONE WILL BE ASSESSED USING THE ADOPTED GUIDES FOR
 VALUE AND INCLUDING PRICING PROVIDED FROM MANUFACTURES.
 FBC 108.3
  
 2) NOTE: THIS COMMENT REMAINS AS THERE IS NOT ENOUGH
 INFORMATION FOR OTHER TRADES WHICH WILL CREATE 2ND
 ROUND OF COMMENTS FOR OTHER REVIEWS AS WELL.
 **PLEASE BE SURE TO SEE ALL COMMENTS FROM OTHER TRADES
 AS THERE WILL BE COMMENTS WITH RESPECT TO FUEL SIZE AND
 THE REQUIREMENT FOR AN ACCESS PLATFORM TO SERVICE
 EQUIPMENT PER NFPA-110 2002 AND FBC.
 THERE WILL BE COMMENTS WITH RESPECT TO MOUNTING, AND
 THE ACTUAL FUEL TANK PLANS NEEDING THE DERM STAMPS.
 ** THIS IS NOTED SO THAT DESIGN TEAM AND CONTRACTOR
 WILL BE AWARE TO SEE OTHER COMMENTS BEFORE MAKING
 DESIGN CHANGES.
  
 3) NOTE: REPEAT COMMENT: PLEASE SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT. THIS SHALL INCLUDE
 ATS EQUIPMENT, GENERATOR, AND FUEL TANK. (TANK REVIEWED
 BY OTHER TRADES).
 NEC 90.7,110.3, 702.6
  
 4) NOTE: SAME NOTE, THE ATS IS STILL SHOWN AS 3-POLE.
 THERE WILL BE A LACK OF COORDINATION OF EQUIPMENT AND
 WHEN POWER TRANSFER BACK TO NORMAL POWER.
  
 **PREVIOUS NOTE:
 PLEASE SEE ORIGINAL NOTES FOR BUILDING. THE CODE
 REQUIRES GROUND FAULT PROTECTION ON MAIN. THIS IS GIVEN
 FOR INFORMATION AS THIS IS ONLY A NEC 702 SYSTEM.
 AS THERE IS GROUND FAULT PROTECTION ON THE MAIN AND THE
 USE OF A THREE POLE TRANSFER SWITCH THIS MAY CREATE A
 LACK OF COORDINATION OR TRIPPING OF MAIN WITHOUT THE
 USE OF A FOUR POLE TRANSFER SWITCH. IF THIS WAS A 700
 OR 701 SYSTEM THERE ARE SPECIFIC CODE SECTIONS WHICH
 REQUIRE GROUND FAULT SENSING ON THE BACK UP SYSTEM.
 PLEASE SEE NFPA-110 6.2.15 WHEN GROUND FAULT SENSING IS
 REQUIRED OR PROVIDED THIS WOULD REQUIRE THE ISOLATION
 OF NEUTRALS THUS A FOUR POLE TRANSFER SWITCH.
 *** PLEASE BE AWARE OF THIS AS THIS MAY BE AN
 OPERATIONAL ITEM WHICH DEPENDING ON EQUIPMENT ORDERED
 MAY CREATE A LOSS OF COORDINATION OR NO OPERATION AT
 ALL.
 ** PLEASE SEE WHITE PAPERS BY CATERPILLAR, ASCO AND
 MANY OTHER TRANSFER SWITCH MANUFACTURES ON THIS TOPIC.
 ** THIS COMMENT IS ONLY MADE TO HELP IN THE DESIGN AS
 THIS IS A 702 SYSTEM NO BACK UP OF POWER IS REQUIRED
 FOR ANY 701 AND 702 SYSTEMS IN BUILDING.
  
 5) NOTE: NEW SITE PLANS ARE IN FACT PHOTO-COPIES OF
 SIGNED, DATED AND SEALED PLANS BY A DESIGN PROFESSIONAL
 WHICH IS NOT PERMITTED.
 FS 481.221, 471.025
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-12 Cont ID  
Sent By dpalmer Date 2009-04-12 Time 10:14 Rev Time 0.00
Received By dpalmer Date 2009-04-12 Time 10:14 Sent To  
Notes
2009-04-12 10:15:02** DENIED**
  
 1) NOTE: PLANS ARE STATING ALL DESIGNS PER 2004 FBC.
 ANY PLANS SUBMITTED FOR PER AFTER MARCH 1ST, 2009 MUST
 BE UNDER THE NEW 2007 FBC WITH 2009 AMENDMENTS.
 THE FAC 69A-60.003 AND 004 HAS ALSO REVISED ADOPTING
 THE NEW NFPA-1 AND NFPA-101
  
 PLEASE BE SURE THE FOLLOWING CODES ARE STATED ON PLANS
 AT A MINIMUM.
 2005 NFPA-70
 2002 NFPA-72
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
  
 2) NOTE: PERMIT APPLICATION VALUE SHALL INCLUDE: ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC. AN
 APPLIED VALUE OF $12K DOES NOT COVER THE GENERATOR LET
 ALONE THE TRANSFER EQUIPMENT, SLAB WORK, ELECTRICAL,
 UNDERGROUND OR FUEL TANK.
 IF AN APPROPRIATE VALUE IS NOT STATED FOR COMPLETE
 SCOPE ONE WILL BE ASSESSED USING THE ADOPTED GUIDES FOR
 VALUE AND INCLUDING PRICING PROVIDED FROM MANUFACTURES.
 FBC 108.3
  
 3) NOTE: PLEASE BE SURE TO SEE ALL COMMENTS FROM OTHER
 TRADES AS THERE WILL BE COMMENTS WITH RESPECT TO FUEL
 SIZE AND THE REQUIREMENT FOR AN ACCESS PLATFORM TO
 SERVICE EQUIPMENT PER NFPA-110 2002 AND FBC.
 THERE WILL BE COMMENTS WITH RESPECT TO MOUNTING, AND
 THE ACTUAL FUEL TANK PLANS NEEDING THE DERM STAMPS.
 ** THIS IS NOTED SO THAT DESIGN TEAM AND CONTRACTOR
 WILL BE AWARE TO SEE OTHER COMMENTS BEFORE MAKING
 DESIGN CHANGES.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR ALL EQUIPMENT. THIS SHALL INCLUDE ATS
 EQUIPMENT, GENERATOR, AND FUEL TANK. (TANK REVIEWED BY
 OTHER TRADES).
 NEC 90.7,110.3, 702.6
  
 5) NOTE: PLEASE SEE ORIGINAL NOTES FOR BUILDING. THE
 CODE REQUIRES GROUND FAULT PROTECTION ON MAIN. THIS IS
 GIVEN FOR INFORMATION AS THIS IS ONLY A NEC 702 SYSTEM.
 AS THERE IS GROUND FAULT PROTECTION ON THE MAIN AND THE
 USE OF A THREE POLE TRANSFER SWITCH THIS MAY CREATE A
 LACK OF COORDINATION OR TRIPPING OF MAIN WITHOUT THE
 USE OF A FOUR POLE TRANSFER SWITCH. IF THIS WAS A 700
 OR 701 SYSTEM THERE ARE SPECIFIC CODE SECTIONS WHICH
 REQUIRE GROUND FAULT SENSING ON THE BACK UP SYSTEM.
 PLEASE SEE NFPA-110 6.2.15 WHEN GROUND FAULT SENSING IS
 REQUIRED OR PROVIDED THIS WOULD REQUIRE THE ISOLATION
 OF NEUTRALS THUS A FOUR POLE TRANSFER SWITCH.
 *** PLEASE BE AWARE OF THIS AS THIS MAY BE AN
 OPERATIONAL ITEM WHICH DEPENDING ON EQUIPMENT ORDERED
 MAY CREATE A LOSS OF COORDINATION OR NO OPERATION AT
 ALL.
 ** PLEASE SEE WHITE PAPERS BY CATERPILLAR, ASCO AND
 MANY OTHER TRANSFER SWITCH MANUFACTURES ON THIS TOPIC.
 ** THIS COMMENT IS ONLY MADE TO HELP IN THE DESIGN AS
 THIS IS A 702 SYSTEM NO BACK UP OF POWER IS REQUIRED
 FOR ANY 701 AND 702 SYSTEMS IN BUILDING.
  
 6) NOTE: PLEASE SEE 225.31-225.39 FOR THE REQUIRED
 DISCONNECTING MEANS FOR FEEDERS AT THE BUILDING. THIS
 WAS NOTED ON THE ORIGINAL PLANS HOWEVER THE GENERATOR
 WAS REMOVED FORM PLANS. THIS REVIEWER STATED TO BE
 AWARE OF THIS CODE SECTION ON FUTURE PLANS. NEC
 700.12B6, 701.11B5 AND 702.11 ALL STATE THAT WHEN
 DISCONNECTING MEANS FROM THE GENERATOR IS LOCATED
 WITHIN SIGHT AND READILY ACCESSIBLE THEN AN ADDITIONAL
 DISCONNECTING MEANS IS NOT REQUIRED AT THE BUILDING IN
 WHICH THE FEEDERS SERVE. THE GENERATOR IS LOCATED
 WITHIN SIGHT PER DEFINITIONS HOWEVER THE DISCONNECTING
 MEANS AT GENERATOR MAY NOT BE READILY ACCESSIBLE. IN A
 LOCKED ENCLOSURE OR BEHIND A WALL/GATES LOCKED DOES NOT
 PERMIT READY ACCESS FOR FIRE DEPARTMENT OR ANY OTHER
 PERSONNEL. SEE ZONING COMMENTS AS THE GENERATOR WILL BE
 REQUIRED TO CONTAIN A WALL OR FENCE IN ETC. THE
 ENCLOSURE OF THE GENERATOR ALONE DOES NOT PERMIT READY
 ACCESS WITH THE BREAKER LOCKED INSIDE.
 PLEASE KNOW THAT A DISCONNECTING MEANS DOES NOT REQUIRE
 OVER CURRENT PROTECTION WHEN THE OCP IS ALREADY
 PROVIDED BY THE GENERATOR.
  
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG-F ENGINEERING FINAL DRAWING REV
Rev No 1 Status P Date 2009-07-17 Cont ID  
Sent By efabian Date 2009-07-17 Time 11:39 Rev Time 0.00
Received By efabian Date 2009-07-17 Time 11:38 Sent To  
Notes
2009-07-17 11:41:22PASSED
  
 CIVIL PLANS SETS RESUBMITTED 7-14-09 CONSISTING OF NEW
 POTABLE 4 INCH WATER SERVICES AND CROSS CONNECTIONS
 ACCEPTABLE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-10 Cont ID  
Sent By mawillia Date 2009-08-10 Time 11:09 Rev Time 0.00
Received By mawillia Date 2009-08-10 Time 10:51 Sent To  
Notes
2009-08-10 11:09:37*****APPROVED*****
  
  
 PLAN SHEETS A010 AND RP 1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-16 Cont ID  
Sent By mawillia Date 2009-04-16 Time 15:07 Rev Time 0.00
Received By mawillia Date 2009-04-16 Time 12:23 Sent To  
Notes
2009-04-16 12:36:52*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET. NO ADDRESS LISTED ON
 SHEETS E-1, E-2, AND E-3.
  
 2. UPDATE CODE INFORMATION ON SHEET E-1 TO REFLECT
 CURRENT EDITIONS OF NFPA 101 (2006) AND NFPA 110 (2005)
 WHICH ARE TO BE REFERENCED.
  
 3. ARE ANY DEVICES PLANNED TO PREVENT THE GENERATOR
 FROM RECEIVING MECHANICAL DAMAGE FROM VEHICLES.
  
 4. SHOW/ILLUSTRATE DISTANCE FROM THE GENERATOR/SLAB
 SETUP TO THE EDGE OF THE ONE WAY ASPHALT DRIVE.
  
 5. SHOW/ILLUSTRATE DISTANCES TO THE NEAREST BUILDING(S)
 OPENINGS SUCH AS WINDOWS AND DOORS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status P Date 2009-08-07 Cont ID  
Sent By rregueir Date 2009-08-07 Time 08:43 Rev Time 0.00
Received By rregueir Date 2009-08-07 Time 08:43 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 15:43 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 15:42 Sent To M
Notes
2009-07-20 15:43:29PROVIDE TWO SETS OF PBC DERM APPROVED PLANS, ONE OFR
 FILE SET AND ONE FOR FIELD SET.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-08-03 Cont ID  
Sent By lmartine Date 2009-08-03 Time 13:22 Rev Time 0.00
Received By lmartine Date 2009-08-03 Time 13:22 Sent To  
Notes
2009-08-03 13:22:39C-3

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 17:30 Sent To  
Notes
2009-07-24 17:30:22TO C10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-06-19 Cont ID  
Sent By btrobaug Date 2009-06-19 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2009-06-19 Time 14:34 Sent To  
Notes
2009-06-19 14:40:15 
  
 C-16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-16 Time   Rev Time 0.00
Received By adarroug Date 2009-04-09 Time 10:28 Sent To  
Notes
2009-04-09 10:41:02TO "C3"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-08-18 Cont ID  
Sent By rkussner Date 2009-08-18 Time 09:22 Rev Time 0.00
Received By rkussner Date 2009-08-18 Time 09:22 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-08-18 Cont ID  
Sent By rkussner Date 2009-08-06 Time 09:21 Rev Time 0.00
Received By rkussner Date 2009-08-06 Time 16:52 Sent To  
Notes
2009-08-06 16:54:44***LANDSCAPE REVIEW FAILED***
  
 PLEASE ADDRESS THE ZONING COMMENTS MADE ON 7/29/09.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2009-08-06 Cont ID  
Sent By rregueir Date 2009-08-06 Time 11:54 Rev Time 0.00
Received By rregueir Date 2009-08-06 Time 11:54 Sent To  
Notes
2009-08-06 11:54:31MISSING PAGES SUPPLIED

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 20:38 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 20:12 Sent To  
Notes
2009-08-05 20:38:34REVIEW COMPLETE. ONE SET OF PLANS IS COMPLIANT AND
 CONTAINS REVISED PAGE SP-1 WITH DERM APPROVAL AND PAGE
 RP-1. THIS WOULD BE ADEQUATE FOR A PASSED MECHANICAL
 REVIEW. HOWEVER, THE 2ND SET OF PLANS IS MISSING THESE
 TWO PAGES. REVIEW CANNOT BE PASSED UNTIL TWO COMPLETE
 AND MATCHING SETS OF PLANS ARE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2009-07-27 Cont ID  
Sent By rregueir Date 2009-07-27 Time 20:38 Rev Time 0.00
Received By rregueir Date 2009-07-27 Time 20:23 Sent To  
Notes
2009-07-27 20:38:17DENIED
  
 WRITTEN RESPONSE FROM ARCHITECT INDICATES PBC DERM
 APPROVED PLANS WERE INCLUDED. PAGE SP-1 WHICH WAS
 PREVIOUSLY APPROVED BY DERM HAS BEEN REVISED AND MUST
 BE RE-SUBMITTED TO DERM FOR APPROVAL PRIOR TO PERMIT
 ISSUANCE. PLEASE PROVIDE TWO COPIES OF DERM APPROVED
 PLANS (PAGE SP-1 AND TANK SUBMITTAL) UPON RESUBMISSION.
  
 NOTE: GENERATOR EXHAUST SHALL BE MINIMUM 10' (MEASURED
 HORIZONTALLY) FROM OUTSIDE AIR INTAKES AND OPENINGS
 INTO THE BUILDING INACCORDANCE WITH FBC-M 401.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-07-20 Cont ID  
Sent By rregueir Date 2009-07-20 Time 15:44 Rev Time 0.00
Received By rregueir Date 2009-07-20 Time 15:43 Sent To  
Notes
2009-07-20 15:44:11PREVIOUS REVIEW COMMENTS NOT ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-14 Cont ID  
Sent By rregueir Date 2009-04-14 Time 19:19 Rev Time 0.00
Received By rregueir Date 2009-04-14 Time 19:15 Sent To  
Notes
2009-04-14 19:19:09REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLEASE ADJUST THE PROVIDED PERMIT VALUATION TO
 INCLUDE ALL EQUIPMENT, MATERIALS, LABOR AND DESIGN
 COSTS ASSOCIATED WITH THIS SCOPE OF WORK, INCLUDING THE
 GENERATOR, FUEL TANK, TRANSFER SWITCHES, ELECTRICAL
 WORK, ETC.
  
 2. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA FOR THE
 SUB BASE FUEL TANK SHOWING LISTINGS AND RATINGS AS
 REQUIRED IN ACCORDANCE WITH FBC-M 915.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2009-08-17 Cont ID  
Sent By jroach Date 2009-08-17 Time 09:27 Rev Time 0.00
Received By jroach Date 2009-08-17 Time 09:27 Sent To  
Notes
2009-08-17 09:30:31ZONING PLAN REVIEW
  
 PERMIT NO.: 09040174
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: EMERGENCY GENERATOR
  
 REVIEW STATUS: PASSED WITH PROVISO
  
 THE PERMIT IS ISSUED SUBJECT TO THE FOLLOWING:
  
 1) THE SITE PLAN AND LANDSCAPE PLANS SUBMITTED AND
 APPROVED AS PART OF BLDG. PERMIT NO. 08090611 SHALL BE
 REVISED TO SHOW THE ACCURATE LOCATION OF THE GENERATOR,
 ALLOWING ALL PERMITS/PLANS TO BE CONSISTENT.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 3 Status F Date 2009-07-30 Cont ID  
Sent By jroach Date 2009-07-30 Time 17:29 Rev Time 0.00
Received By jroach Date 2009-07-30 Time 17:29 Sent To  
Notes
2009-07-30 17:32:43ZONING PLAN REVIEW
  
 PERMIT NO.: 09040174
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: EMERGENCY GENERATOR
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE COMMENT BELOW IS A REPEAT COMMENT...
  
 1) THE SITE PLAN SUBMITTED WITH THIS PERMIT DOES NOT
 MATCH THAT SUBMITTED AND APPROVED AS PART OF BLDG.
 PERMIT NO. 08090611. BLDG. PERMIT NO. 08090611 WILL
 NEED TO BE REVISED TO PROVIDE FOR THE REVISED LOCATION
 OF THE GENERATOR (THIS WILL INCLUDE THE SITE AND
 LANDSCAPE PLANS).
  
 A PROVISO WAS NOT ISSUED AS THIS APPLICATION HAS FAILED
 OTHER TRADES. PLEASE TRY TO ADDRESS THE COMMENT
 PROVIDED ABOVE SO AS TO AVOID HAVING A PROVISO. IF ALL
 OTHER TRADES HAVE PASSED THE APPLICATION AND THE ABOVE
 COMMENT REMAINS, A PROVISO WILL BE CONSIDERED.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 2 Status F Date 2009-06-24 Cont ID  
Sent By jroach Date 2009-06-24 Time 14:46 Rev Time 0.00
Received By jroach Date 2009-06-24 Time 14:46 Sent To  
Notes
2009-06-24 14:55:35ZONING PLAN REVIEW
  
 PERMIT NO.: 09040174
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: EMERGENCY GENERATOR
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 THE COMMENT BELOW IS A REPEAT COMMENT....ADDITIONAL
 INFORMATION IS PROVIDED IN ALL CAPS.
  
 1) PURUSANT TO SECTION 94-444(B) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS, GENERATORS SHALL BE
 SCREENED. SCREENING SHALL CONSIST OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. THE SCREENING SHALL COMPLETELY
 OBSCURE THE PROPOSED GENERATOR. IN ADDITION, THE
 SCREENING SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. THE SITE PLAN SUBMITTED
 WITH THIS PERMIT DOES NOT MATCH THAT SUBMITTED AND
 APPROVED AS PART OF BLDG. PERMIT NO. 08090611. BLDG.
 PERMIT NO. 08090611 WILL NEED TO BE REVISED TO PROVIDE
 FOR THE REVISED LOCATION OF THE GENERATOR (THIS WILL
 INCLUDE THE SITE AND LANDSCAPE PLANS). ADDITIONALLY,
 DETAILS WILL NEED TO BE PROVIDED REGARDING THE PROPOSED
 SCREENING. THE PLANS SHOW A CONCRETE WALL, BUT NO
 STRUCTURAL DETAILS HAVE BEEN PROVIDED (I.E. HEIGHT,
 ETC.). PLEASE PROVIDE THIS INFORMATION.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1459
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By jroach Date 2009-04-15 Time 10:32 Rev Time 0.00
Received By jroach Date 2009-04-15 Time 10:32 Sent To  
Notes
2009-04-15 10:40:55ZONING PLAN REVIEW
  
 PERMIT NO.: 09040174
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: 635.6935
 SCOPE OF REVIEW: EMERGENCY GENERATOR
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) PURUSANT TO SECTION 94-444(B) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS, GENERATORS SHALL BE
 SCREENED. SCREENING SHALL CONSIST OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. THE SCREENING SHALL COMPLETELY
 OBSCURE THE PROPOSED GENERATOR. IN ADDITION, THE
 SCREENING SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS.
  
 2) SETBACKS SHALL BE PROVIDED ON THE SITE PLAN SHOWING
 THE DISTANCE BETWEEN THE GENERATOR AND THE PROPERTY
 LINE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  