Plan Review Details - Permit 09040157
Plan Review Stops For Permit 09040157
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-05-18 Cont ID  
Sent By jnguyen Date 2009-05-18 Time 13:31 Rev Time 0.00
Received By jnguyen Date 2009-04-14 Time 09:16 Sent To  
Notes
2009-05-18 12:02:27UPDATE ON 5-18-2009: THE INITIAL ISSUE PERTAINED TO THE
 UNITY OF TITLE DEED THAT WAS TO PROSPECTIVELY MERGE THE
 TWO PARCELS, PCN# 74434403220000030 - 260 PALMETTO LN &
 PCN# 74434403220000040 - 250 PALMETTO LN INTO ONE
 (DATED APRIL 18, 2007). ORIGINALLY, JOHN ENCK CALLED &
 TOLD ME THAT THE UNITY OF TITLE DEED WAS NO GOOD
 BECAUSE THE PROPERTY OWNER NAMES WERE DIFFERENT OR NOT
 THE SAME, SO THEREFORE PAPA WOULD NOT MERGE THEM. HE
 ALSO ACKNOWLEDGED TO ME THAT USUALLY THE LOWER PCN#
 TAKES PRECEDENT AS A RESULT OF MERGERS (IN THIS CASE,
 PCN# 74434403220000030). HOWEVER, TWO QUIT CLAIM DEEDS
 WERE FILED ON MAY 1, 2009 (OFFICIAL RECORD BOOK 23207,
 PAGES 706-707 & 708-709) TO INCLUDE BOTH PROPERTY OWNER
 NAMES (LARS BOLANDER & NADEGE KALACHNIKOFF) FOR THE TWO
 PROPERTIES. I E-MAILED CHERYL HORTON OF PAPA TO INQUIRE
 AS TO WHAT THE RESULTING EFFECT WOULD BE. THE FACT
 REMAINED THAT THE COUNTY'S GIS PARCELS LAYER STILL
 SHOWED THEM AS SEPARATE ENTITIES & SO DID THE PAPA WEB
 SITE. I ASKED HER IF THE ORIGINAL UNITY OF TITLE DEED
 WOULD BE HONORED TO EVENTUALLY SHOW THESE TWO
 PROPERTIES AS ITS OWN SINGLE ENTITY OF PCN#
 74434403220000030 - 260 PALMETTO LN EXCLUSIVELY (AS A
 RESULT OF THE QUIT CLAIM DEEDS SHOWING THE SAME
 PROPERTY OWNER NAMES)? CHERYL RESPONDED, "THE QUIT
 CLAIM DEEDS WILL BE REVIEWED FOR THE 2010 TAX ROLL & IF
 THE TITLE FOR BOTH PCN#S IS OK? WE WILL COMBINE PER THE
 UNITY OF TITLE DEED. IT LOOKS LIKE TAXES ARE STILL
 UNPAID ON PCN# 74434403220000030 FOR 2008. WE WILL
 CHECK AGAIN BEFORE WE COMBINE FOR 2010 IN A FEW MONTHS,
 BUT TAXES MUST BE CURRENT BEFORE COMBINATIONS CAN BE
 PROCESSED." EVERYTHING APPEARS READY IN LINE TO PROCEED
 WITH MAKING THIS MERGER OFFICIAL (WITH THE EXCEPTION OF
 THE UNPAID TAXES). IN THE MEANTIME, I HAVE CHANGED THE
 STATUS OF THIS PERMIT TO PASS REGARDING THE ADDRESSING
 STOP. IN COMMUNITYPLUS, PLEASE MOVE THIS PERMIT RECORD
 FROM PCN# 74434403220000040 - 250 PALMETTO LN TO BE
 CORRECTLY ATTACHED INSTEAD TO PCN# 74434403220000030 -
 260 PALMETTO LN (THE PARCEL CONTROL NUMBER THAT WILL
 REMAIN). I HAVE RETURNED THE FOLDER OF DOCUMENTS BACK
 TO THE R9 BOX.
2009-04-20 11:59:13 
 UPDATE ON 4-20-2009: I RECEIVED AN E-MAIL RESPONSE FROM
 CHERYL HORTON TO CLARIFY THE ISSUE CONCERNING THE UNITY
 OF TITLE DEED. ACCORDING TO HER, THE PROPERTY
 APPRAISER'S OFFICE MADE CONTACT WITH LARS BOLANDER
 (OWNER OF PCN# 74434403220000040) AND NADEGE
 KALACHNIKOFF (OWNER OF PCN# 74434403220000030) ON MARCH
 16, 2009 AND INFORMED THEM THAT THE PROPERTY CONTROL
 NUMBERS COULD NOT BE COMBINED DUE TO THE PROPERTIES
 BEING IN DIFFERENT NAMES. IN THE MEANTIME, BOTH
 PROPERTIES ARE STILL BEING RECOGNIZED AS THEIR OWN
 SEPARATE ENTITIES. THEREFORE, THIS PERMIT SHOULD
 REFERENCE PCN# 74434403220000040 AT 250 PALMETTO LN. I
 HAVE E-MAILED THE CONTRACTOR TO CHANGE IT ON HIS COPY
 OF THE PERMIT APPLICATION & SITE PLANS TO REFERENCE
 PCN# 74434403220000040 AT 250 PALMETTO LN. LATER ON, I
 ALSO RECEIVED A CALL FROM JOHN ENCK OF THE PROPERTY
 APPRAISER'S OFFICE. HE RELAYED TO ME THAT THEY CAN'T DO
 ANYTHING ABOUT THIS ISSUE, DESPITE THE FACT THAT THE
 PROPERTY OWNERS HAVE FILED TO UNIFY THE PARCELS. HE
 SAID THAT THE REASON WAS IF THE TITLES ARE NOT THE
 SAME, THEN THEY WILL NOT & CANNOT COMBINE THE PARCELS.
 THE ARCHITECT, MICHAEL JOHNSON HAS CALLED ME & SAID HE
 WAS WORKING WITH THE PROPERTY APPRAISER'S OFFICE TO
 RESOLVE THIS ISSUE WITH THE TITLES. HE IS WORKING ON
 OBTAINING A QUIT CLAIM DEED & THE PROCESS WILL BE
 EXPEDITED WITH THE AID OF CHERYL HORTON. SHE WILL WRITE
 DIRECTLY TO THE CITY ONCE THE QUIT CLAIM DEED HAS BEEN
 COMPLETE. IN THE MEANTIME, UNTIL THIS ISSUE IS RESOLVED
 THIS PERMIT WILL REMAIN IN ITS SUSPENDED STATE.
2009-04-14 13:19:32 
 UPDATE ON 4-14-2009: I HAVE RESCINDED ISSUING THE
 SECONDARY ADDRESSES OF 254 & 256 PALMETTO LN FOR THE
 CABANAS SINCE THEY'RE JUST STRUCTURES ON A SINGLE
 FAMILY LOT. I SENT OUT ANOTHER NOTIFICATION E-MAIL TO
 EVERYONE THAT INSTRUCTED THEM TO DELETE THESE TWO
 ADDRESSES FROM THEIR DATABASES (AS THEY DO NOT EXIST
 OFFICIALLY). THE PRIMARY ADDRESS OF 250 PALMETTO LN
 JUST REFERENCES THE GENERAL LOT OF PCN#
 74434403220000040, WHERE THE SWIMMING POOL AND THE
 PROPOSED PAVILION & CABANAS WILL BE LOCATED. HOWEVER,
 THERE IS STILL A PENDING ISSUE REGARDING THE UNITY OF
 TITLE DEED (ORB 21641 PG 0659) THAT APPARENTLY MERGED
 THESE PCN#S 74434403220000030 & 74434403220000040 INTO
 ONE (DATED APRIL 2007). UNFORTUNATELY, OURS & THE
 COUNTY'S GIS PARCEL BOUNDARIES STILL SHOWED THESE TWO
 PARCELS, PCN#S 74434403220000030 & 74434403220000040 AS
 THEIR OWN SINGLE DISTINCT ENTITIES (NOT AS ONE
 PROPERTY). OUR SOURCE FOR THE GIS PARCEL BOUNDARIES
 LAYER IS THE COUNTY. THEREFORE, I SENT AN E-MAIL TO
 PAPA (SPECIFICALLY JOHN ENCK & BRENDA DYE) TO HELP
 CLARIFY THIS ISSUE, AS TO WHICH PCN# 74434403220000030
 OR 74434403220000040 TOOK PRECEDENT? UNLIKELY, BUT A
 NEW & DIFFERENT PCN# MAY HAVE BEEN ISSUED TOO? I ALSO
 CONTACTED THE PALM BEACH COUNTY ISS DEPARTMENT TO
 INQUIRE AS TO WHY THE PARCEL BOUNDARIES WERE NOT
 UPDATED IF THIS MERGER WAS OFFICIAL. IN THE MEANTIME,
 UNTIL I RECEIVE FURTHER CLARIFICATION ON THIS ISSUE
 (ONE OR TWO PARCELS), I WILL NOT CHANGE THE STATUS TO
 PASS.
2009-04-14 10:14:20 
 DISREGARD THE FOLLOWING MESSAGE: THIS PERMIT# 09040157
 IS INDEED BEING APPLIED TO THE CORRECT PCN#
 74434403220000040 WITH A PRIMARY ADDRESS OF 250
 PALMETTO LN, WHICH NOW REFERENCES THE PROPOSED
 PAVILION. THE ADDRESS OF 260 PALMETTO LN ON THE SITE
 PLAN ONLY REFERS TO THE RESIDENTIAL STRUCTURE ON THE
 PARCEL TO THE WEST, PCN# 74434403220000030. UNDER PCN#
 74434403220000040 IN COMMUNITYPLUS, I HAVE CREATED THE
 SECONDARY ADDRESSES OF: 254 PALMETTO LN (ASSIGNED TO
 THE PROPOSED CABANA #1) AS SEQUENTIAL UNIT RECORD 0001
 & 256 PALMETTO LN ASSIGNED TO THE PROPOSED CABANA #2)
 AS SEQUENTIAL UNIT RECORD 0002. I HAVE ALSO SENT OUT A
 NOTIFICATION E-MAIL TO ALL OF THE RELEVANT PARTIES TO
 INFORM THEM OF THESE NEW SECONDARY ADDRESSES FOR 254 &
 256 PALMETTO LN ON PCN# 74434403220000040 (COPIED THE
 E-MAIL TO THE CONTRACTOR, WILDES BUILDERS LLC TOO). I
 RECEIVED A CALL FROM RUBY OF WILDES BUILDERS LLC, WHERE
 I CLARIFIED THE ISSUES WITH THE NEW ADDRESSES TO HER. I
 HAVE RETURNED THE FOLDER OF DOCUMENTS & SITE PLANS TO
 THE R10 BOX DOWNSTAIRS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-06-09 Cont ID  
Sent By jgomez Date 2009-05-27 Time 11:28 Rev Time 0.00
Received By jgomez Date 2009-05-27 Time 11:27 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By jgomez Date 2009-04-13 Time 18:39 Rev Time 0.00
Received By jgomez Date 2009-04-13 Time 18:38 Sent To  
Notes
2009-04-13 19:10:23RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2008
 REVISIONS.
  
 1- PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD (233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE
 DUE.
  
 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY
 DCA RULE 9B-72 FOR BATH EXTERIOR DOOR.
  
 3- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE COMPLETE MANUFACTURER SPECIFICATIONS FOR
 ICYNENE INSULATION TO VERIFY COMPLIANCE WITH SEC. R314
 AND R316 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 5- SHEET S-1: PAVILION ROOF FRAMING PLAN IS MISSING THE
 ROOF CONNECTOR FOR 2X8 RAFTERS ON CANTILEVER SIDE. THIS
 INFORMATION IS MISSING ALSO ON DETAIL 1/S-2.
  
 6- SHEET S-3; REVISE WIND LOAD INFORMATION. EDGE
 DISTANCE TO BE 4'-0" MIN. AS REQUIRED BY FIGURE
 R301.2(7) OF 2007 FLORIDA RESIDENTIAL CODE.
  
 7- SHEET A-2: SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION ON TYPICAL WALL SECTIONS A AND B AS REQUIRED
 BY SEC. R602.1.2 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 8- OWES $9.88 FOR RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-06-09 Cont ID  
Sent By dpalmer Date 2009-06-09 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2009-06-09 Time 08:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-05-22 Cont ID  
Sent By dpalmer Date 2009-05-22 Time 16:11 Rev Time 0.00
Received By dpalmer Date 2009-05-22 Time 16:11 Sent To  
Notes
2009-05-22 16:12:06**TEMPORARY FAILED STATUS. **
  
 1) NOTE: PLANS ARE STAMPED HOWEVER ARE REDLINED FOR THE
 FOLLOWING:
  
 A) PLANS SHOW SMOKE ALARM TOO CLOSE TO FAN. MUST MEET
 NFPA-72 11.8.3.
 B) METER/SERVICE AS SHOWN IS GRANTED PER ANGELA
 JONES-VANN
  
 2) NOTE: IN TEMP FAILED STATUS UNTIL ADDRESSING IS
 CLEARED FOR UNITY OF TITLE AND ADDRESS HAS BEEN
 UPDATED.
 ONCE ADDRESS IS CONFIRMED WITH CORRECT UNITY OF TITLE
 ETC BEING RECORDED THEN REVIEW STATUS WILL BE ADJUSTED
 TO *P*. PLANS ARE ALREADY STAMPED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-12 Cont ID  
Sent By dpalmer Date 2009-04-12 Time 13:22 Rev Time 0.00
Received By dpalmer Date 2009-04-12 Time 13:22 Sent To  
Notes
2009-04-12 13:22:14** DENIED**
  
 1) NOTE: PLANS SUBMITTED STATE 260 PALMETTO LANE
 HOWEVER THE SCOPE OF WORK ON THE PERMIT APPLICATION
 STATES 250 PALMETTO LANE.
 THE INFORMATION FOR PERMITTING AND PLANS HAS BEEN
 FORWARD TO ADDRESSING AND ZONING.
 THIS AREA IS ZONED SF-7 WHICH IS SINGLE FAMILY. PLANS
 SHOW SEPARATE METER FOR THESE DETACHED BUILDINGS WHICH
 NEEDS TO BE CONFIRMED WITH ZONING. THIS IS A SEPARATE
 PROPERTY.
 THE COMMENTS FROM ZONING MAY OR MAY NOT AFFECT
 ELECTRICAL PLANS.
 THE TITLE BLOCKS NEED TO BE CORRECTED FOR ACTUAL
 LOCATION ONCE REVIEWS CONFIRM FINAL ADDRESS.
  
 2) NOTE: ELECTRICAL PANELS MAY NOT BE LOCATED IN
 STORAGE CLOSETS.
 110.26,240.24D
  
 3) NOTE: SMOKE ALARMS REQUIRED PER NFPA-72 11.5.1 SHOWN
 ON PLANS. HOWEVER PLEASE BE SURE ALL DEVICES ARE
 LOCATED IN AREAS AS REQUIRED PER 11.8.3 (SLOPED
 CEILINGS)
  
 4) NOTE: PLEASE SEE 225.31-225.39 FOR DISCONNECTING
 MEANS REQUIRED AT THE DETACHED PAVILION.
  
 5) NOTE: PLEASE SEE 250.32 FOR REQUIRED GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED PAVILION. THE ONLY
 EXCEPTION DEPENDS ON CIRCUITING. BASED ON PANEL
 SCHEDULE, GROUNDING ELECTRODE TO FOOTER STEEL, GROUND
 RODS ARE REQUIRED.250.50
 THIS IS ALSO FOR EACH OF THE CABANA BUILDING AS THERE
 IS NO GROUNDING ELECTRODE SYSTEM AT EITHER STRUCTURE
 WHICH IS REQUIRED.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2009-05-22 Cont ID  
Sent By kstevens Date 2009-05-22 Time 08:44 Rev Time 0.00
Received By kstevens Date 2009-05-22 Time 08:44 Sent To  
Notes
2009-05-22 08:45:24SEPARATE GAS PERMIT & PLANS TO BE SUBMITTED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 07:51 Rev Time 0.00
Received By kstevens Date 2009-04-13 Time 07:51 Sent To  
Notes
2009-04-13 08:00:33DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
  
  
 ****4-20-09 J.FOSTER WILL SUBMIT GAS APPLICATION/PLANS
 SEPARATELY****
  
  
 A. SHT R-2 INDICATES A GAS TANKLESS WATER TO BE
 INSTALLED. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUBMIT THE FOLLOWING INFORMATION REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007
 RESIDENTIAL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 RESIDENTIAL FUEL GAS CODE SECS. G2412.8
 THRU G2413.4 AND TABLES G2413.4(1) THRU
 G2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-05-14 Cont ID  
Sent By shill Date 2009-05-14 Time 11:14 Rev Time 0.00
Received By shill Date 2009-05-14 Time 11:14 Sent To  
Notes
2009-05-14 11:15:10TO RES BOARD #9
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-17 Time   Rev Time 0.00
Received By adarroug Date 2009-04-10 Time 10:08 Sent To  
Notes
2009-04-10 10:36:12TO "R10"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-06-01 Cont ID  
Sent By rregueir Date 2009-06-01 Time 16:38 Rev Time 0.00
Received By rregueir Date 2009-06-01 Time 16:29 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-14 Cont ID  
Sent By rregueir Date 2009-04-14 Time 19:08 Rev Time 0.00
Received By rregueir Date 2009-04-14 Time 18:27 Sent To  
Notes
2009-04-14 19:07:56REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. CONDENSATE FROM ALL COOLING COILS SHALL BE CONVEYED
 FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF
 DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO A STREET,
 ALLEY OR OTHER AREAS WHERE IT WOULD CAUSE A NUISANCE.
 SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-R M1411.3. DRAIN PIPE JOINTS SHALL
 BE SEALED GAS TIGHT AND SHALL TERMINATE OUTSIDE THE
 BUILDING PERIMETER AT A HEIGHT OF AT LEAST 6 INCHES
 ABOVE THE FINISHED GRADE GROUND LEVEL IN ACCORDANCE
 WITH FBC-R F307.1.2. CONDENSATE LINESSHALL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE SIDEWALL IN
 ACCORDANCE WIT FBC-R320.7.
  
 2. PORVIDE DETAIL FOR INSTALLATION OF OUTDOOR
 CONDENSING UNITS. MECHANICAL APPLIANCES AND SUPPORTS
 THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND
 INSTALLED TO RESIST THE WIND PRESSURES AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING PER
 FBC-R M1307.3.
  
 3. ONCE ADDRESSING AND UNITY-OF-TITLE ISSUES ARE
 RESOLVED, PLEASE PROVIDE THE CORRECT ADDRESS OF THE
 PROPOSED WORK ON EVERY SHEET OF THE PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-06-09 Cont ID  
Sent By kstevens Date 2009-06-09 Time 10:42 Rev Time 0.00
Received By kstevens Date 2009-06-09 Time 10:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-05-22 Cont ID  
Sent By kstevens Date 2009-05-22 Time 08:46 Rev Time 0.00
Received By kstevens Date 2009-05-22 Time 08:46 Sent To  
Notes
2009-05-22 08:46:34PLANS ARE APPROVED FOR PLUMBING BUT STATUS WILL REMAIN
 IN FAILED STATUS UNTIL THE ADDRESSING ISSUE IS
 RESOLVED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 07:44 Rev Time 0.00
Received By kstevens Date 2009-04-13 Time 07:43 Sent To  
Notes
2009-04-13 07:51:01DENIED
 REFERENCE:
 FBC-2004 CHAPTER 1
  
 1. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION OF THE WORK PROPOSED.
 SECTIONS 106.1.1 & 106.3.5. APPLICATION AND CITY
 DATABASE INDICATE THE ADDRESS AS 250 PALMETTO LN, BUT
 THE PLANS INDICATE THE ADDRESS AS 260 PALMETTO LN.
 PLANS WILL BE FORWARDED TO ADDRESSING FOR CONFORMATION
 OF ADDRESS.
  
 2. PLANS ARE APPROVED FOR PLUMBING BUT STATUS WILL
 REMAIN IN FAILED STATUS UNTIL THE ADDRESSING ISSUE IS
 RESOLVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-06-09 Cont ID  
Sent By mcruz Date 2009-06-09 Time 09:13 Rev Time 0.00
Received By mcruz Date 2009-05-28 Time 08:11 Sent To E
Notes
2009-05-29 08:26:49ADDITIONAL RESEARCH BEING CONDUCTED. ROUTED TO
 MECHANICAL IN THE MEANTIME.
  
 ************************************************
  
 6/9/09 - OKAY TO PASS PER ANGELLA VAN-JONES, ZONING
 ADMINISTRATOR
  
 ROUTED TO DP

Review Stop Z ZONING
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By mcruz Date 2009-04-17 Time 12:45 Rev Time 0.00
Received By mcruz Date 2009-04-17 Time 12:38 Sent To  
Notes
2009-04-17 12:45:15PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE A COPY OF A RECORDED UNITY OF TITLE,
 UNIFYING SUBJECT PROPERTY TO A PRINCIPLE STRUCTURE.
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-304(A)(1):
 ACCESSORY STRUCTURES MUST BE CONSTRUCTED SIMULTANEOUSLY
 WITH, OR FOLLOWING THE CONSTRUCTION OF THE MAIN
 BUILDING AND SHALL NOT BE OCCUPIED UNTIL AFTER THE
 PRINCIPAL STRUCTURE HAS RECEIVED A CERTIFICATE OF
 OCCUPANCY. NO ACCESSORY STRUCTURE SHALL BE CONSTRUCTED
 OR ESTABLISHED ON ANY LOT PRIOR TO THE TIME OF
 CONSTRUCTION OR RELOCATION OF THE PRINCIPAL STRUCTURE
 TO WHICH IT IS ACCESSORY.
  
 3. IT SEEMS THAT THE PROPOSED MECHANICAL EQUIPMENT ON
 THE EAST SIDE OF THE PROPERTY EXCEEDS THE MAXIMUM
 SETBACK ALLOWED. PURSUANT THE ZLDR, SECTION
 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  