Plan Review Details - Permit 09040136
Plan Review Stops For Permit 09040136
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 10:57 Rev Time 2.00
Received By jwitmer Date 2009-04-29 Time 10:56 Sent To Z
Notes
2009-04-29 11:07:28RESTAMP OF PERMIT 05010754

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 11:07 Rev Time 0.77
Received By jwitmer Date 2009-04-29 Time 11:07 Sent To  
Notes
2009-04-29 11:12:44RESTAMP OF PERMIT 05010754
 ELECTRIC PROVISO: ELECTRICAL AS BUILTS TO BE REQUIRED,
 THE RESTAMP SET 07120109 SHEET 5 HAS
 PENCIL DRAWN AS BUILTS,AS-BUILT PLAN WILL REQUIRE A
 PANEL SCHEDULE .

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By btrobaug Date 2009-04-15 Time 12:12 Rev Time 0.00
Received By btrobaug Date 2009-04-15 Time 11:55 Sent To  
Notes
2009-04-15 12:11:59 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 2} THERE ARE TWO RISER DIAGRAMS ON SHEET #5. REMOVE THE
 ONE NOT BEING USED.
  
 3} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-05-01 Cont ID  
Sent By shill Date 2009-05-01 Time 10:47 Rev Time 0.00
Received By shill Date 2009-04-08 Time 15:38 Sent To  
Notes
2009-04-08 15:38:39TO "R18"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-23 Cont ID  
Sent By rregueir Date 2009-04-23 Time 13:59 Rev Time 0.00
Received By rregueir Date 2009-04-23 Time 13:58 Sent To  
Notes
2009-04-23 13:59:47NO COPY OF MECHANICAL PLANS INCLUDED WITH THIS
 SUBMISSION. PLANS PREVIOUSLY PASSED BY PAT RAFTER UNDER
 EXPIRED PERMIT #05061522.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By hmoser Date 2009-04-17 Time 13:41 Rev Time 0.00
Received By hmoser Date 2009-04-17 Time 13:41 Sent To  
Notes
2009-04-17 13:42:49NO PLANS .

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-04-29 Cont ID  
Sent By jwitmer Date 2009-04-29 Time 11:13 Rev Time 0.55
Received By jwitmer Date 2009-04-29 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-04-17 Cont ID  
Sent By kstevens Date 2009-04-17 Time 08:48 Rev Time 0.00
Received By kstevens Date 2009-04-17 Time 08:48 Sent To  
Notes
2009-04-17 08:58:57DENIED
 REFERENCE:
 FBC-2004 W/2007 REVISIONS CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS PREPARED BY A DESIGN PROFESSIONAL, (ARCHITECT)
 SHALL BE SIGNED, SEALED AND DATED BY THE DESIGN
 PROFESSIONAL OF RECORD. SECTION 106.1, FAC
 61G1-16.004(5) & FC 481.2055.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2009-04-30 Cont ID  
Sent By mcruz Date 2009-04-28 Time 14:10 Rev Time 0.00
Received By mcruz Date 2009-04-28 Time 12:22 Sent To  
Notes
2009-04-28 14:10:13***UPDATE 4/30/09*** - AS PER AJV - PLANS ARE OKAY TO
 PASS. ORIGINAL APPROVAL WAS OBTAINED PRIOR TO CODE
 CHANGE. MC
  
  
  
 PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 NO NEW PLANS SUBMITTED
  
 REPEAT COMMENTS FROM PERMIT # 07120109:
  
 1) PROVIDE TWO (2) CURRENT COPIES OF A SURVEY SHOWING
 THE LOCATION OF THE PROPOSED STRUCTURE WITH SETBACK
 DIMENSIONS FROM ALL PROPERTY LINES. NOTE: PURSUANT TO
 SECTION 94-304(B)(2) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS:
 SETBACKS.
 FRONT: 25 FEET.
 SIDE: FIVE FEET FROM THE LOT LINES.
 CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. REAR:
 FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE OF THE
 ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS
 GREATER.
  
 2) INDICATE HEIGHT DIMENSIONS ON ELEVATIONS FROM GRADE
 TO THE MIDPOINT OF THE ROOF'S PITCH. NOTE: PURSUANT TO
 SECTION 94-304(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS: HEIGHT. ACCESSORY STRUCTURES
 SHALL NOT EXCEED 25 FEET.
  
 3) SHOW ANY PROPOSED A/C EQUIPMENT AND INDICATE SETBACK
 DIMENSIONS FROM PROPOSED A/C EQUIPMENT TO THE PROPERTY
 LINES. AS PER SECTION 94-305(B)(4) OF THE ZLDRS:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO
 A REQUIRED SETBACK.
  
 4) ACCESSORY STRUCTURE EXCEEDS MAXIMUM SQUARE FOOTAGE
 ALLOWABLE. PURSUANT TO SECTION 94-304(B)(1) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS: MAXIMUM
 SQUARE FOOTAGE. THE TOTAL FLOOR AREA OF ALL ROOFED
 ACCESSORY BUILDINGS ON A PROPERTY (INCLUDING ANY OTHER
 ACCESSORY STRUCTURES THAT MAY EXIST) SHALL NOT EXCEED
 75 PERCENT OF THE GROSS FLOOR AREA OF THE PRIMARY
 STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 SQUARE
 FEET.
  
  
 NOTE: ACCESSORY APARTMENTS/DWELLING UNITS ARE
 PROHIBITED WITHIN THE SF7 ZONING DISTRICT. STRUCTURE
 SHALL SERVE AS A POOL CABANA ONLY. NO DWELLING UNIT
 PERMITTED. NO RENTAL LICENSE SHALL BE GRANTED IN THE
 FUTURE.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED BACK ON RES RACK - R18