Plan Review Details - Permit 09040109
Plan Review Stops For Permit 09040109
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-04-14 Cont ID  
Sent By lwagner Date 2009-04-14 Time 07:29 Rev Time 0.00
Received By lwagner Date 2009-04-14 Time 07:29 Sent To  
Notes
2009-04-14 07:30:201" PE REQUIRED FOR POOL HEATER

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By lwagner Date 2009-04-13 Time 11:18 Rev Time 0.00
Received By lwagner Date 2009-04-13 Time 09:02 Sent To  
Notes
2009-04-13 11:40:35GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2007 FLORIDA BUILDING CODES, CITY
 OF WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.),
 FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA
 STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE REFERENCED CODE N.F.G.C. IS INCORRECT.
 FBC FUEL GAS 2007 IS REQUIRED. TABLES 402.4(2) AND
 402.4(19) APPLY.
  
 2. FROM TABLE 402.4(19) 1" PIPE SIZE IS REQUIRED FOR
 THE POOL HEATER.
  
 REVIEW BY LARRY WAGNER
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  