| 2009-04-14 07:30:20 | 1" PE REQUIRED FOR POOL HEATER |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-04-13 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2009-04-13 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2009-04-13 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2009-04-13 11:40:35 | GAS PLAN REVIEW: | | | DENIED: | | | | | | PLAN REVIEW UNDER THE 2007 FLORIDA BUILDING CODES, CITY | | | OF WEST PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), | | | FLORIDA ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA | | | STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE REFERENCED CODE N.F.G.C. IS INCORRECT. | | | FBC FUEL GAS 2007 IS REQUIRED. TABLES 402.4(2) AND | | | 402.4(19) APPLY. | | | | | | 2. FROM TABLE 402.4(19) 1" PIPE SIZE IS REQUIRED FOR | | | THE POOL HEATER. | | | | | | REVIEW BY LARRY WAGNER | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
|