Plan Review Details - Permit 09040078
Plan Review Stops For Permit 09040078
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-04-10 Cont ID  
Sent By mjacobs Date 2009-04-10 Time 13:25 Rev Time 0.00
Received By mjacobs Date 2009-04-10 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By dpalmer Date 2009-04-30 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2009-04-30 Time 16:51 Sent To M
Notes
2009-04-30 16:53:29PLANS REDLINED:
  
 THE CONNECTION OF THE TRANSFORMER INTO THE DECK ABOVE
 SHALL BE VERIFIED BY THE ARCHITECT/STRUCTURAL ENGINEER.
 THE STRUCTURAL INTEGRITY OF THE CONNECTIONS AS SHOWN ON
 ELECTRICAL PLANS IS NOT PART OF THE ELECTRICAL REVIEW.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By dpalmer Date 2009-04-13 Time 16:40 Rev Time 0.00
Received By dpalmer Date 2009-04-13 Time 16:40 Sent To  
Notes
2009-04-13 16:40:47** DENIED**
  
  
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM
 CODES ARE STATED ON PLANS.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
  
 2) NOTE: THE PLANS SUBMITTED WITH PROJECT BY INTEGRATED
 SECURITY SYSTEMS HAVE THE FOLLOWING TWO COMMENTS:
  
 A) NOTE: TITLE BLOCK FOR ENGINEERING FIRM IS MISSING
 THE REQUIRED CERTIFICATE OF AUTHORIZATION NUMBER PER FS
 471.023 AND FAC 61G15-23.002
  
 B) NOTE: PLANS NOTING ADA COMPLIANCE PER 1992 ADA
 GUIDELINES.
  
 C) PLANS NOTING CODES WHICH ARE NO LONGER IN EFFECT.
 EXAMPLE: PLANS SHOW THE 2002 NEC.( NFPA70) HOWEVER THE
 STATE OF FLORIDA ADOPTED THE 2005 NEC IN DECEMBER 2006
 EXAMPLE: PLANS NOTE THE 2003 NFPA-101. FAC 69A-60.003
 AND .004 HAS ADOPTED THE NEW 2006 NFPA-101 AND NFPA-1
 AS OF DECEMBER 31ST, 2008.
  
 ** PLEASE ADJUST NOTES AND PLANS.
  
 3) NOTE: PLANS SUBMITTED CONTAIN THE LIGHTING
 PERFORMANCE CALCULATIONS, ALLOWANCES AND CODE SECTIONS
 FROM THE 2004 FBC CHAPTER 13. PLEASE KNOW THIS PROJECT
 IS UNDER THE 2007 FBC AND THE NEW SECTIONS AND CODE
 REQUIREMENT OF 2007 FBC WITH 2009 REVISION APPLY.
 THE PREVIOUS CODE ALLOWANCES FOR ACCENT LIGHTING NO
 LONGER EXISTS IN THE NEW CODE.
 PLANS STATING ANY PRESCRIPTIVE *C* REQUIREMENTS IS NOT
 ACCURATE AS THAT SECTION OF THE CODE NO LONGER EXISTS.
  
 *** IMPORTANT; EMERGENCY LIGHTING WHICH IS ALSO USED
 AND GENERAL LIGHTING IS NOT EXEMPT. THE ONLY TYPE OF
 EMERGENCY FIXTURES WHICH ARE EXEMPT IS THE BATTERY BACK
 UP TYPES ONLY ON UNDER EMERGENCY CONDITIONS.
 ** THE LIGHTING SHOWN ON PLANS EXCEEDS THE ALLOWANCES
 BY THE CODE.
  
 *** CALLED FAE CONSULTING ENGINEERS AND SPOKE TO MIKE.
 THEY ARE NOW AWARE OF THE NEW CODE REQUIREMENTS AND
 WILL BE MAKING CORRECTIONS.
  
 4) NOTE: TRANSFORMER HANDING DETAIL NEEDED FOR
 STRUCTURAL INTEGRITY. FBC 1606.2 WILL BE PART OF
 STRUCTURAL REVIEW.
  
 5) NOTE: NOTES ON PLANS INDICATE OVER RIDES FOR
 LIGHTING TO SOME SORT OF TIME CLOCK HOWEVER THERE ARE
 NO DETAILS ON PLANS FOR PROPOSED LIGHTING CONTROLS.
 13-415.1.AB.1.1, .1.2, .1.3
  
 6) NOTE: NOTES REQUIRED ON PLANS PER 13-413.AB.2
  
 7) NOTE: PLEASE PLACE NOTE ON PLANS FOR ROOM 901 WHICH
 STATES WIRING METHODS PERMITTED IN NEC 645 SHALL NOT BE
 USED. THIS ROOM DOES NOT MEET REQUIREMENTS IN 645.4
 (1-5) FOR THE LESS STRINGENT WIRING METHODS IN 645.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-05-01 Cont ID  
Sent By mawillia Date 2009-05-01 Time 13:58 Rev Time 0.00
Received By mawillia Date 2009-05-01 Time 13:35 Sent To  
Notes
2009-05-01 13:57:42*****RE-STAMP*****
  
 PLAN SHEET E2.01 AND THE FIRE ALARMS SHEETS (WHICH WERE
 PREVIOULSY FIRE-STAMPED ON 4/10/09 BY CAPT. WENNERGREN)
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-04-10 Cont ID  
Sent By mwennerg Date 2009-04-10 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2009-04-10 Time 14:51 Sent To  
Notes
2009-04-10 14:53:11PLANS STAMPED WITH REQUIREMENT FOR SEPARATE SHOP
 DRAWINGS AND PERMITS FOR FIRE SPRINKLER AND FIRE ALARM
 REMODEL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-30 Cont ID  
Sent By dpalmer Date 2009-04-30 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2009-04-30 Time 16:54 Sent To E
Notes
2009-04-30 16:56:51PLANS NOT PLACED ON BOARD. ROUTE TO EACH TRADE. NEEDS
 FIRE, AND MECHANICAL.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 16:21 Rev Time 0.00
Received By kstevens Date 2009-04-06 Time 16:48 Sent To  
Notes
2009-04-06 16:48:22TO "B2"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-05-04 Cont ID  
Sent By rregueir Date 2009-05-04 Time 08:39 Rev Time 0.00
Received By rregueir Date 2009-05-04 Time 08:39 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-04-15 Cont ID  
Sent By rregueir Date 2009-04-15 Time 15:53 Rev Time 0.00
Received By rregueir Date 2009-04-15 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-04-15 Cont ID  
Sent By kstevens Date 2009-04-15 Time 16:21 Rev Time 0.00
Received By kstevens Date 2009-04-15 Time 16:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-07 Cont ID  
Sent By eschneid Date 2009-04-07 Time 14:52 Rev Time 0.25
Received By eschneid Date 2009-04-07 Time 14:52 Sent To  
Notes
2009-04-07 14:53:209TH FLOOR BUILD OUT