| Plan Review Stops For Permit 09040031 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-05-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-05-11 |
Time |
14:44 |
Rev Time |
0.66 |
| Received By |
jwitmer |
Date |
2009-05-11 |
Time |
14:01 |
Sent To |
PC |
|
| Notes |
| 2009-05-11 14:51:26 | BUILDING PLAN REVIEW | | | PERMIT: 09040031 | | | ADD: 401 N DIXIE HWY | | | CONT: M. A. C. CONSTRUCTION, INC. | | | TEL: (786)236-1006 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | | | | 1) SHEET M-601 DETAIL SUPPLY FAN ROOF CURB DETAIL, | | | NOTE# 12 SECURE ROOF CURB TO ROOF ASSEMBLY PER | | | MANUFACTURERS INSTALATION INSTRUCTIONS AND STRUCTURAL | | | NOTES. | | | PLEASE PROVIDE TYPE OF ROOF-DECK, AND THE CONNECTION | | | BETWEEN THE ROOF FRAMING, ROOF DECK AND CURBING. | | | THE CITY IS LOCATED WITHIN A 140 M. P.H. 3SECOND GUST | | | WIND ZONE.FIGURE 1609. | | | | | | 1604.8.1 GENERAL. ANCHORAGE OF THE ROOF TO WALLS AND | | | COLUMNS, AND OF WALLS AND COLUMNS TO FOUNDATIONS, SHALL | | | BE PROVIDED TO RESIST THE UPLIFT AND SLIDING FORCES | | | THAT RESULT FROM THE APPLICATION OF THE PRESCRIBED | | | LOADS. | | | | | | 1604.4 ANALYSIS. EVERY STRUCTURE SHALL BE DESIGNED TO | | | RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL | | | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR | | | WIND LOADS . | | | PLEASE PROVIDE BY ROUGH INSPECTION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-04-10 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2009-04-10 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2009-04-10 |
Time |
07:15 |
Sent To |
|
|
| Notes |
| 2009-04-10 07:40:48 | PROVISO: PROVIDE SIGN, SEAL AND DATED INFORMATION FOR | | | THE CURB AND FASTENERS FOR THE FAN. THE WIND | | | INFORMATION SHALL PER FBC 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (M/S). | | | | | | 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE. WHERE MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | THE MECHANICAL INSPECTOR SHALL INSPECT ALL WORK BEFORE | | | IT IS SEALED UP. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-05-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-05-06 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-05-06 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2009-05-06 17:03:34 | STMPED, | | | | | | LV UNDER SEPARATE PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-04-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-13 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-13 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2009-04-13 15:23:46 | ** DENIED | | | | | | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM | | | CODES ARE STATED ON PLANS. | | | 2007 FBC W/ 2009 REVISIONS. | | | 2006 NFPA-101 | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | | | | ** PLANS HAVE OLDER CODES ON THEM | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE ROOFTOP GFI | | | RECEPTACLES PER 210.63, 210.8B3, PLEASE SHOW | | | CIRCUITING. | | | | | | ** THESE ITEMS ARE ITEMS WHICH COULD HAVE BEEN REDLINED | | | HOWEVER PLANS WILL MOST LIKELY HAVE COMMENTS FROM OTHER | | | TRADES SUCH AS MECHANICAL FOR ROOF-TOP EQUIPMENT. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-05-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-08 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-08 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2009-05-08 13:46:00 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED; PLAN SHEETS M-201, M-202, & M-301 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-04-15 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-04-15 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2009-04-15 16:42:38 | *****UNSAT***** | | | | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | 2. THE 2006 EDITION OF NFPA 101 SHALL BE REFERENCED. | | | AMEND SECTION F UNDER GENERAL REQUIREMENTS ON SHEET | | | E-200. | | | | | | | | | PLAN SHEETS M202 & M301 TO BE FIRE-STAMPED WHEN THE | | | OTHER PLAN EXAMINERS AS WELL AS THE ABOVE COMMENT HAS | | | BEEN ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-04-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-04-28 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-04-28 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-04-06 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2009-04-06 13:37:12 | TO "B5" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-04-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-30 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-04-30 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2009-04-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-04-15 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-05-11 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2009-04-15 12:48:18 | REVIEW #: 1ST | | | ACTION: PASSED WITH PROVISO | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | ***PROVISO*** | | | 1. PROVIDE INSTALLATION DETAIL SHOWING HOW CURBS ARE TO | | | BE ATTACHED TO BUILDING STRUCTURE AND HOW NEW SF-1 AND | | | EF-1 ARE TO BE SECURED FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBC-M 301.12. | | | 2. PROVIDE DATA FROM SF-1 AND EF-1 MANUFACTURER SHOWING | | | THESE APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBC-M 301.12. | | | NOTE: THE ABOVE SHALL BE SUBMITTED FOR REVIEW PRIOR TO | | | INSPECTION AND CONSEALMENT OF ANY WORK RELATED TO THIS | | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-04-09 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2009-04-09 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2009-04-09 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|