Plan Review Details - Permit 09040031
Plan Review Stops For Permit 09040031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-05-11 Cont ID  
Sent By jwitmer Date 2009-05-11 Time 14:44 Rev Time 0.66
Received By jwitmer Date 2009-05-11 Time 14:01 Sent To PC
Notes
2009-05-11 14:51:26BUILDING PLAN REVIEW
 PERMIT: 09040031
 ADD: 401 N DIXIE HWY
 CONT: M. A. C. CONSTRUCTION, INC.
 TEL: (786)236-1006
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
  
 1) SHEET M-601 DETAIL SUPPLY FAN ROOF CURB DETAIL,
 NOTE# 12 SECURE ROOF CURB TO ROOF ASSEMBLY PER
 MANUFACTURERS INSTALATION INSTRUCTIONS AND STRUCTURAL
 NOTES.
 PLEASE PROVIDE TYPE OF ROOF-DECK, AND THE CONNECTION
 BETWEEN THE ROOF FRAMING, ROOF DECK AND CURBING.
 THE CITY IS LOCATED WITHIN A 140 M. P.H. 3SECOND GUST
 WIND ZONE.FIGURE 1609.
  
 1604.8.1 GENERAL. ANCHORAGE OF THE ROOF TO WALLS AND
 COLUMNS, AND OF WALLS AND COLUMNS TO FOUNDATIONS, SHALL
 BE PROVIDED TO RESIST THE UPLIFT AND SLIDING FORCES
 THAT RESULT FROM THE APPLICATION OF THE PRESCRIBED
 LOADS.
  
 1604.4 ANALYSIS. EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS .
 PLEASE PROVIDE BY ROUGH INSPECTION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-04-10 Cont ID  
Sent By mjacobs Date 2009-04-10 Time 07:40 Rev Time 0.00
Received By mjacobs Date 2009-04-10 Time 07:15 Sent To  
Notes
2009-04-10 07:40:48PROVISO: PROVIDE SIGN, SEAL AND DATED INFORMATION FOR
 THE CURB AND FASTENERS FOR THE FAN. THE WIND
 INFORMATION SHALL PER FBC 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
  
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (M/S).
  
 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE. WHERE MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 THE MECHANICAL INSPECTOR SHALL INSPECT ALL WORK BEFORE
 IT IS SEALED UP.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-05-06 Cont ID  
Sent By dpalmer Date 2009-05-06 Time 17:03 Rev Time 0.00
Received By dpalmer Date 2009-05-06 Time 17:03 Sent To  
Notes
2009-05-06 17:03:34STMPED,
  
 LV UNDER SEPARATE PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-04-13 Cont ID  
Sent By dpalmer Date 2009-04-13 Time 15:23 Rev Time 0.00
Received By dpalmer Date 2009-04-13 Time 15:23 Sent To  
Notes
2009-04-13 15:23:46** DENIED
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING MINIMUM
 CODES ARE STATED ON PLANS.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLANS HAVE OLDER CODES ON THEM
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE ROOFTOP GFI
 RECEPTACLES PER 210.63, 210.8B3, PLEASE SHOW
 CIRCUITING.
  
 ** THESE ITEMS ARE ITEMS WHICH COULD HAVE BEEN REDLINED
 HOWEVER PLANS WILL MOST LIKELY HAVE COMMENTS FROM OTHER
 TRADES SUCH AS MECHANICAL FOR ROOF-TOP EQUIPMENT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-05-08 Cont ID  
Sent By mawillia Date 2009-05-08 Time 13:46 Rev Time 0.00
Received By mawillia Date 2009-05-08 Time 13:27 Sent To  
Notes
2009-05-08 13:46:00*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS M-201, M-202, & M-301 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-04-15 Cont ID  
Sent By mawillia Date 2009-04-15 Time 16:42 Rev Time 0.00
Received By mawillia Date 2009-04-15 Time 15:48 Sent To  
Notes
2009-04-15 16:42:38*****UNSAT*****
  
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 2. THE 2006 EDITION OF NFPA 101 SHALL BE REFERENCED.
 AMEND SECTION F UNDER GENERAL REQUIREMENTS ON SHEET
 E-200.
  
  
 PLAN SHEETS M202 & M301 TO BE FIRE-STAMPED WHEN THE
 OTHER PLAN EXAMINERS AS WELL AS THE ABOVE COMMENT HAS
 BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-04-28 Cont ID  
Sent By dpalmer Date 2009-04-28 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2009-04-28 Time 15:24 Sent To  
Notes
2009-04-28 15:24:36C-11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-04-15 Time   Rev Time 0.00
Received By adarroug Date 2009-04-06 Time 11:08 Sent To  
Notes
2009-04-06 13:37:12TO "B5"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-04-30 Cont ID  
Sent By rregueir Date 2009-04-30 Time 14:33 Rev Time 0.00
Received By rregueir Date 2009-04-30 Time 13:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-04-15 Cont ID  
Sent By rregueir Date 2009-04-15 Time 12:48 Rev Time 0.00
Received By jwitmer Date 2009-05-11 Time 13:30 Sent To  
Notes
2009-04-15 12:48:18REVIEW #: 1ST
 ACTION: PASSED WITH PROVISO
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ***PROVISO***
 1. PROVIDE INSTALLATION DETAIL SHOWING HOW CURBS ARE TO
 BE ATTACHED TO BUILDING STRUCTURE AND HOW NEW SF-1 AND
 EF-1 ARE TO BE SECURED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
 2. PROVIDE DATA FROM SF-1 AND EF-1 MANUFACTURER SHOWING
 THESE APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
 NOTE: THE ABOVE SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 INSPECTION AND CONSEALMENT OF ANY WORK RELATED TO THIS
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-04-09 Cont ID  
Sent By mflis Date 2009-04-09 Time 13:48 Rev Time 0.00
Received By mflis Date 2009-04-09 Time 13:48 Sent To  
Notes
***NONE***